Plan Review Details - Permit 19080334
Plan Review Stops For Permit 19080334
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-09-26 Cont ID  
Sent By jgomez Date 2019-09-26 Time 16:06 Rev Time 0.00
Received By jgomez Date 2019-09-26 Time 14:36 Sent To  
Notes
2019-09-26 16:06:46ASBESTOS REVIEW
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 SEC. 469.003 FLORIDA STATUTES.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 12:51 Sent To  
Notes
2019-08-26 06:59:05ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS
 IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-27 Cont ID  
Sent By jgomez Date 2019-09-27 Time 14:04 Rev Time 0.00
Received By jgomez Date 2019-09-27 Time 08:45 Sent To  
Notes
2019-09-27 14:16:34SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 ORIGINAL COMMENT:
 1) THE COVERSHEET LIST THE PROJECT DATA. THE PLAN
 INDICATES THIS NEW TENANT SPACE IS TO BE A BUSINESS
 OCCUPANCY. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS
 A MERCANTILE OCCUPANCY. PLEASE SEE CHAPTER 10 OF THE
 EXISTING BUILDING CODE SECTION 1001.2.2.1 FOR PARTIAL
 CHANGE OF OCCUPANCY REQUIREMENTS. WHERE A PORTION OF A
 BUILDING IS CHANGING OCCUPANCIES SECTION 1012 OF THE
 EXISTING BUILDING CODE SHALL APPLY.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 RESPONSE:
 A) THE PROJECT DATA INFORMATION ON THE COVERSHEET IS
 NOT CLEAR. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS
 MERCANTILE OCCUPANCY. IT LOOKS LIKE A PORTION OF THE
 DRUG STORE IS PROPOSED TO BE A BEAUTY SALON WHICH IS
 BUSINESS OCCUPANCY. ACCORDING TO FIRST FLOOR PLAN ON
 SHEET A-1 THE PHARMACY WILL REMAIN ON THE OTHER PART OF
 THE BUILDING. THEREFORE, THE DRUG STORE MERCANTILE
 OCCUPANCY STILL REMAINS. THIS IS A PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION WITHOUT SEPARATION. PROJECT
 DATA SHALL BE CLEAR IN STATING THE EXISTING OCCUPANCY
 GROUP AND THE PROPOSED PARTIAL OCCUPANCY GROUP. SINCE
 THERE IS NOT SEPARATION AMONG THE OCCUPANCY
 CLASSIFICATIONS, THEN THE MOST RESTRICTIVE OCCUPANCY
 WILL PREVAIL FOR ENTIRE BUILDING. SECTION 1012.1.1.1
 FBC-EXISTING BUILDING.
  
 B) PROPOSED FLOOR PLAN DOESN'T SHOW THE LAYOUT OF THE
 PHARMACY AREA TO REMAIN. PROVIDE PLANS SHOWING THE
 AREAS THAT ARE GOING TO BE OCCUPIED BY THE PHARMACY.
 SHOW ALL THE ISLES, ETC. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. 1012.4.2 FBC-EXISTING BUILDING. SEC. 1018
 FBC-BUILDING.
  
 C) THERE IS NO DIMENSION FOR THE CORRIDOR (HALL 108).
 PROVIDE DIMENSION. SEC. 1012.4.2 FBC-EXISTING BUILDING.
 SEC. 1020.2 FBC-BUILDING.
  
  
 2) OK
  
 3A) OK
  
 ORIGINAL COMMENT:
 3B) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. ABOVE THIS AREA THE AIR
 COMMUNICATES WITH THE EXIT CORRIDOR AND OTHER TENANT
 SPACES. IN THE 2017 FBC-B SECTION 2801.1. MECHANICAL
 APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE CONSTRUCTED,
 INSTALLED AND MAINTAINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL. IN THE MECHANICAL CODE UNDER
 VENTILATION TABLE 403.3.1.1 SPECIALTY SHOPS PLEASE SEE
 BEAUTY SALON REQUIREMENTS (SEE FOOTNOTE B) FOR
 VENTILATION AND IF MANICURES AND OR PEDICURE STATIONS
 SOURCE CAPTURE SYSTEMS ARE REQUIRED AT EACH STATION,
 SEE FOOTNOTES B & H. FOOTNOTE B STATES MECHANICAL
 EXHAUST REQUIRED AND THE RECIRCULATION OF AIR FROM SUCH
 SPACES IS PROHIBITED. RECIRCULATION OF AIR THAT IS
 CONTAINED COMPLETELY WITHIN SUCH SPACES SHALL NOT BE
 PROHIBITED (SEE SECTION 403.2.1, ITEM 3).
  
 RESPONSE:
 THIS ITEMS NEEDS TO BE COORDINATED WITH THE MECHANICAL
 PLANS EXAMINER AND THE ENGINEER OF RECORD. (MECHANICAL
 PLANS EXAMINER FOR THIS JOB IS OUT OF THE OFFICE TODAY.
 I WILL TALK TO HIM WHEN HE IS BACK). IT IS NOT CLEAR IF
 MECHAICAL PLAN REVIEWER AND THE ENGINEER OF RECORD ARE
 AWARE OF THE FACT THAT THE TENANT SEPARATION WALLS
 DON'T GO ALL THE WAY UP TO THE CEILING. (SEC. 1009.1
 FBC-EXISTING BUILDING). ALSO, THE EXHAUST LOCATION
 NEEDS TO BE REVIEWED. ACCORDING TO SEC. 502.1.1
 FBC-MECHANICAL, THE INLET TO AN EXHAUST SYSTEM SHALL BE
 LOCATED IN THE AREA OF HEAVIEST CONCENTRATION OF
 CONTAMINANTS. HEAVIEST CONCENTRATION MAY BE BY THE
 STYLING AREA.
  
  
 3C) OK
  
 3D) OK
  
 3E) OK
  
 ORIGINAL COMMENT:
 3F) SHEET A-2 SHOWS 3 DETAILS, 3, 4 & 5. DETAIL 5 SHOWS
 THE USE OF (2) 2X6 BUCKS BEING FASTENED TO STEEL BEAM
 AND COLUMNS WITH 2 INCH SCREWS AT 12 INCHES ON CENTER.
 3F)(2) DETAILS 3 AND 4 DO NOT SHOW THE INSTALLATION OF
 A DOUBLE BUCK ATTACHED TO THE STEEL BEAM OR COLUMN.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 RESPONSE:
 DETAIL IS NOT CLEAR. DETAIL 5 SHOWS DOUBLE 2X4 BUCKS.
 SIZE OF SCREW SPECIFIED DOESN'T SEEM TO BE LONG ENOUGH
 TO FASTEN THE TWO BUCKS TO THE STEEL COLUMN/BEAM. IN
 ADDITION, THE TWO 2X4 BUCKS ARE THE STRUCTURAL BUCKS
 TRANSFERRING THE NEW DOORS AND STOREFRONT WIND LOADS TO
 THE STEEL COLUMN/BEAM. PROVIDE CALCULATIONS SHOWING
 THAT THE PROPOSED CONNECTION DETAIL WILL SUPPORT ALL
 THE LOADS. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. 1609.1
 FBC-BUILDING.
  
 4) OK. THIS WILL BE PROVIDED AT TIME OF INSPECTION.
  
 SHEET A-2 SHOWS THE USE OF WELDED AND BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
  
 DEFERRED SUBMITTAL:
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS
  
 DEFERRED SUBMITTAL:
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) OK.
  
 8) ASBESTOS:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
 SEC. 469.003 FLORIDA STATUTES.
  
  
 9) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT
 ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTE:
 SEPARATE FIRE SPRINKLER PERMIT IS REQUIRED SHOWING THE
 PROPOSED ALTERATIONS TO THIS BUILDING.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 12:51 Sent To  
Notes
2019-08-26 07:00:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080334
 ADD: 416 CLEMATIS ST.
 CONT: MONTIERRE DEVELOPMENT
 TEL: 407-562-6311
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: TUES. AUGUST 20, 2019
 ACTION: DENIED
  
 1) THE COVERSHEET LIST THE PROJECT DATA. THE PLAN
 INDICATES THIS NEW TENANT SPACE IS TO BE A BUSINESS
 OCCUPANCY. CURRENTLY THE SPACE IS A DRUG STORE WHICH IS
 A MERCANTILE OCCUPANCY. PLEASE SEE CHAPTER 10 OF THE
 EXISTING BUILDING CODE SECTION 1001.2.2.1 FOR PARTIAL
 CHANGE OF OCCUPANCY REQUIREMENTS. WHERE A PORTION OF A
 BUILDING IS CHANGING OCCUPANCIES SECTION 1012 OF THE
 EXISTING BUILDING CODE SHALL APPLY.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2) THE SHEET A-1 SHOWS A PROPOSED BEAUTY SHOP/ HAIR
 STYLING SHOP WITH AN OCCUPANT LOAD OF 14 PEOPLE. NO
 LIFE SAFETY PLAN WAS SUBMITTED SHOWING THE EGRESS PATH
 FOR THIS TENANT SPACE. SHEET E-1 SHOWS AN EXIT LIGHT AT
 THE NEW EXTERIOR DOOR OPENING ON CLEMATIS ST. PLEASE
 SEE DOOR 2 & 5 BOTH ARE MANUALLY SLIDING DOORS, THEY
 CANNOT BE THE REQUIRED EGRESS DOORS. DOOR # 8 WILL HAVE
 TO BE THE EGRESS DOOR WITH EXIT LIGHT.
 PLEASE REVIEW THE 2017 FBC-B SECTION 1010.1.2.
 EXCEPTION # 9. EXCEPTION 9. IN OTHER THAN GROUP H
 OCCUPANCIES, MANUALLY OPERATED HORIZONTAL SLIDING DOORS
 ARE PERMITTED IN A MEANS OF EGRESS FROM SPACES WITH AN
 OCCUPANT LOAD OF 10 OR LESS.
 3A) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. THE SCALE ON THE DRAWING
 INDICATES 1 ? INCH = 1 FOOT. IT WOULD APPEAR THIS IS A
 TYPO AND THE SCALE SHOULD READ ? INCH SCALE EQUALS 1
 FOOT. DISCREPANCY IN PLAN. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
 3B) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. ABOVE THIS AREA THE AIR
 COMMUNICATES WITH THE EXIT CORRIDOR AND OTHER TENANT
 SPACES. IN THE 2017 FBC-B SECTION 2801.1. MECHANICAL
 APPLIANCES, EQUIPMENT AND SYSTEMS SHALL BE CONSTRUCTED,
 INSTALLED AND MAINTAINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL. IN THE MECHANICAL CODE UNDER
 VENTILATION TABLE 403.3.1.1 SPECIALTY SHOPS PLEASE SEE
 BEAUTY SALON REQUIREMENTS (SEE FOOTNOTE B) FOR
 VENTILATION AND IF MANICURES AND OR PEDICURE STATIONS
 SOURCE CAPTURE SYSTEMS ARE REQUIRED AT EACH STATION,
 SEE FOOTNOTES B & H. FOOTNOTE B STATES MECHANICAL
 EXHAUST REQUIRED AND THE RECIRCULATION OF AIR FROM SUCH
 SPACES IS PROHIBITED. RECIRCULATION OF AIR THAT IS
 CONTAINED COMPLETELY WITHIN SUCH SPACES SHALL NOT BE
 PROHIBITED (SEE SECTION 403.2.1, ITEM 3).
 3C) SHEET A1 DETAIL 1 SHOWS THE TENANT WALLS EXTENDING
 UP HALFWAY TO THE CEILING. THE PLAN DOES NOT SHOW HOW
 THE TENANT SEPARATION WALLS ARE GOING TO BE PERMANENT
 AND NO FLEXING AND LEANING. 2017 FBC-B 1604.3
 SERVICEABILITY. STRUCTURAL SYSTEMS AND MEMBERS THEREOF
 SHALL BE DESIGNED TO HAVE ADEQUATE STIFFNESS TO LIMIT
 DEFLECTIONS AND LATERAL DRIFT.
 1604.3.1 DEFLECTIONS. THE DEFLECTIONS OF STRUCTURAL
 MEMBERS SHALL NOT EXCEED THE MORE RESTRICTIVE OF THE
 LIMITATIONS OF SECTIONS 1604.3.2 THROUGH 1604.3.5 OR
 THAT PERMITTED BY TABLE 1604.3.
 3D) SHEET A1 DETAIL 1 SHOWS NEW DRYWALL BEAMS SEE
 DETAIL 2/ A2. THIS DETAIL INDICATES THE NEW DRYWALL
 BEAMS ARE TO BE 10 INCHES TALL AND 2 FEET WIDE. THE
 CHARTS FROM THE STEEL STUD MANUFACTURERS ASSOCIATION
 SHOWS THE LARGEST CEILING SPAN MEMBERS AS 600S162 WHEN
 AT 2 FEET ON CENTER AND THICKNESS IN (43MILS) A SPAN OF
 15 FEET 2 INCHES AND ALLOWABLE DEFLECTION OF L/240. THE
 SAME SIZE FRAMING MEMBER AT 16 INCHES ON CENTER A SPAN
 OF 16 FEET 11 INCHES AND IF THE SPACING IS AT 12 INCHES
 ON CENTER A SPAN OF 18 FEET 4 INCHES WHEN THERE IS NO
 SUPPORT AT THE MID-POINT. PLEASE PROVIDE WHERE YOU ARE
 GETTING YOUR SPAN INFORMATION FROM? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED. 2017 FBC-B 2211.1.
 3E) SHEET A-1 WALL LEGEND SHOWS WALL TYPE A, SEE
 SECTION 1/ A-2. THIS DETAIL SHOWS A NEW ALCOVE SET BACK
 FROM THE FRONT STOREFRONT, A NEW ENTRY. WHAT SHEET A-1
 NOR SHEET A-2 SHOW IS THE NEW WHAT APPEARS TO BE NEW
 CONCRETE COLUMNS JUST TO THE WEST OF THIS NEW ALCOVE?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED AS TO THE
 SIZE OF THE CONCRETE COLUMN, REBAR SIZE, AND AMOUNT OF
 VERTICAL REBAR AND AT WHAT CENTER AND SIZE OF HOOPS FOR
 THIS COLUMN AS WELL AS EMBEDMENT INTO THE SLAB AND
 CONCRETE BEAM ABOVE.
 3F) SHEET A-2 SHOWS 3 DETAILS, 3, 4 & 5. DETAIL 5 SHOWS
 THE USE OF (2) 2X6 BUCKS BEING FASTENED TO STEEL BEAM
 AND COLUMNS WITH 2 INCH CREWS AT 12 INCHES ON CENTER.
 3F)(1) IS THE 2X6 BUSKS TO BE RIPPED DOWN TO BE A FULL
 4 INCHES WIDE TO BE THE SAME WIDTH AS THE 4 INCH STEEL
 BEAM? OR IS THIS A TYPO? 107.2.1.2 ADDITIONAL
 INFORMATION REQUIRED.
 3F)(2) DETAILS 3 AND 4 DO NOT SHOW THE INSTALLATION OF
 A DOUBLE BUCK ATTACHED TO THE STEEL BEAM OR COLUMN.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED.
 3F) IN DETAIL #4 & 5 IT APPEARS THE BOTTOM PLATE IS TO
 BE TURNED SIDEWAYS, THE QUESTION IS THE BOTTOM STEEL
 PLATE SUPPOSE TO SIT ON TOP OF THE CONCRETE FLOOR OR BE
 SUNKEN, IF SO HOW MUCH? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
 4) SHEET A-2 SHOWS THE USE OF WELDED AND BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 9) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT
 ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2019-08-20 14:52:49BUILDING REVIEW IN PROGRESS.
 J. WITMER

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By jpearson Date 2019-10-02 Time 13:18 Rev Time 0.00
Received By jpearson Date 2019-10-02 Time 08:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-27 Cont ID  
Sent By jpearson Date 2019-08-27 Time 11:05 Rev Time 0.00
Received By jpearson Date 2019-08-27 Time 08:02 Sent To  
Notes
2019-08-27 10:11:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SHOW WINDOW RECEPTACLES. NEC 210.62
 2. PROVIDE LOCATION OF ELECTRICAL PANEL ON PLAN. WPB
 FBC 107.2.1
 3. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By J.Walker Date 2019-09-20 Time   Rev Time 0.00
Received By jwalker Date 2019-09-20 Time 13:59 Sent To  
Notes
2019-09-20 14:00:17RETURNED TO B-06

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-13 Cont ID  
Sent By J.Walker Date 2019-08-13 Time   Rev Time 0.00
Received By jwalker Date 2019-08-08 Time   Sent To  
Notes
2019-08-08 14:50:12RETURNED TO B-02

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-22 Cont ID  
Sent By shill Date 2019-10-09 Time 16:42 Rev Time 0.00
Received By shill Date 2019-09-16 Time 09:27 Sent To  
Notes
2019-10-09 11:22:35TO LAURA MARCHAN.
2019-09-18 09:27:44B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-10 Cont ID  
Sent By hmoser Date 2019-09-10 Time 15:43 Rev Time 0.00
Received By hmoser Date 2019-08-06 Time 14:39 Sent To  
Notes
2019-08-07 14:39:46B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-09-27 Cont ID  
Sent By jgomez Date 2019-09-27 Time 14:17 Rev Time 0.00
Received By jgomez Date 2019-09-27 Time 14:17 Sent To  
Notes
2019-09-27 14:17:55PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 12:51 Sent To  
Notes
2019-08-26 06:59:41PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-09-23 Cont ID  
Sent By hmoser Date 2019-09-23 Time 14:25 Rev Time 0.00
Received By hmoser Date 2019-09-23 Time 14:16 Sent To  
Notes
2019-09-23 14:24:56PLAN DENIED
 RESPONSE TO COMMENT #1 SEE OUTSIDE AIR SUMMARY
 ON SHEET M-2 FOR VENTILATION RATES. THERE IS NO PAGE
 M-2 WITH THE PLAN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By hmoser Date 2019-09-10 Time 15:42 Rev Time 0.00
Received By hmoser Date 2019-09-10 Time 14:02 Sent To I
Notes
2019-09-10 15:42:50PLAN DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3.1.1
 FBC (M) 2017
 MINIMUM VENTILATION RATES. EXISTING CALCULATIONS WERE
 FOR A PHARMACY
 NEW CALCULATIONS SHALL BE FOR A HAIR SALON.
 2) EXHAUST FAN IN HAIR TREATMENT ROOM SAYS REFER TO
 NOTE 2
 PLEASE EXPLAIN.
 3) PLEASE EXPLAIN HOW ROOMS 106 $ 107 WILL NOT BE IN A
 NEGATIVE PRESSURE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-09-26 Cont ID  
Sent By jesmith Date 2019-09-26 Time 13:09 Rev Time 0.00
Received By jesmith Date 2019-09-26 Time 12:46 Sent To  
Notes
2019-09-26 13:09:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
  
 PLUMBING COMMEMTS: DENIED
 1. SECOND REQUEST; IT IS NOTED THAT THE ARCHITECT HAS
 DELETED THE S-2 SINK AND ASSOCIATED MILL WORK. HOWEVER,
 AS PER WPB FBC 107.2.1, THE ELEVATION DETAIL OF
 MILLWORK FOR PLUMBING FIXTURE S-1 INDICATING MAXIMUM 2
 FEET-10 INCHES TO THE TOP OF THE CABINET OR THE FIXTURE
 RIM, WHICHEVER IS HIGHER IS STILL REQUIRED, AS WELL AS
 DIMENSIONED CLEAR FLOOR SPACE FOR THE SINK. COMPLY WITH
 FBC ACC SECTIONS 212, 804, 305 AND 606. REVISE TO
 COMPLY.
 2. PLAN SHEET A-1 NO LONGER SHOWS THE SINK OR MILLWORK
 FOR SINK S-2. PLAN SHEET P-2 INDICATES PLUMBING AND
 FIXTURE FOR S-2. PLEASE CLARIFY
 3. PLAN SHEET P-1 IS NOT INCLUDED IN THE SUBMITTAL AND
 IS REQUIRED PER WPB FBC 107.2.1.
 4. REGARDING SPECIFICATION FOR THE OWNER SUPPLIED
 SHAMPOO BOWL, PLEASE SEE THE ADDITIONAL DOCUMENTATION
 PROVIDED BY THE MANUFACTURER AND ATTACHED TO THE
 OVERVIEW SHEET OF THE AVERY BACKWASH SHAMPOO SYSTEM.
 THIS DOCUMENTATION IS CERTIFICATION THAT THE BACKFLOW
 PREVENTER COMPLIES WITH THE REQUIREMENTS OF FBC PL
 608.2 BUT IS INVALID AFTER SEPTEMBER OF 2019. PER WPB
 FBC 107.2.1, PROVIDE A NEW CERTIFICATE SHOWING
 COMPLIANCE AT THE TIME OF PERMIT ISSUANCE. CALL MINERVA
 BEAUTY 888-332-0123 TECHNICAL SUPPORT FOR UPDATED
 CERTIFICATE.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080334 416 CLEMATIS ST
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-29 Cont ID  
Sent By jesmith Date 2019-08-29 Time 10:46 Rev Time 0.00
Received By jesmith Date 2019-08-29 Time 10:45 Sent To  
Notes
2019-08-29 10:46:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMEMTS: DENIED
  
 1. RE: PLAN SHEET P-2, WATER ISOMETRIC NOTE #2; FBC
 2318.1.15 AND 2517.5.1.1 DO NOT APPEAR TO ADDRESS
 ANYTHING CONCERNING WALL HUNG PLUMBING FIXTURES. PER
 WPB FBC 107.2.1, PLEASE CLARIFY.
 2. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR THE
 OWNER SUPPLIED SHAMPOO BOWL. SPECIFICATION SHALL
 INCLUDE PROVISION FOR BACKFLOW PREVENTION AS REQUIRED
 BY FBC PL SECTION 608. IF THERE IS NO PROVISION THEN
 THE ENGINEER SHALL PROVIDE FOR SAID PROTECTION AND
 SPECIFY TYPE ON THE PLANS.
 3. PER WPB FBC 107.2.1, PROVIDE ELEVATION DETAIL OF
 MILLWORK FOR PLUMBING FIXTURES S-1 AND S-2 SHOWING
 MAXIMUM 2?-10? TO THE TOP OF THE CABINET OR THE FIXTURE
 RIM, WHICHEVER IS HIGHER. ADDITIONALLY, PROVIDE
 DIMENSIONED CLEAR FLOOR SPACES AND ANY REQUIRED TURNING
 RADIUS TO THE FIXTURES AND AFFECTED APPLIANCES. COMPLY
 WITH FBC ACC SECTIONS 212, 804, 305 AND 606. PLEASE
 NOTE THAT THE U-SHAPED CABINET CONFIGURATION DOES NOT
 COMPLY WITH THE REQUIREMENTS OF FBC ACC 804.2.2. REVISE
 TO COMPLY.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080334 416 CLEMATIS ST
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-10-09 Cont ID  
Sent By aaponte Date 2019-10-09 Time 10:37 Rev Time 0.00
Received By aaponte Date 2019-10-09 Time 10:37 Sent To  
Notes
2019-10-09 11:22:171. PLEASE PROVIDE THE DRAWINGS OF THE EXISTING
 ELEVATION AND THE PROPOSED CHANGES.
 2. NEW STOREFRONT GLASS SHALL BE CLEAR WITH NO TINT.
 3. IF THE PHARMACY TENANT IS REMOVED FROM THE FRONT OF
 THE SPACE, THE PHARMACY IS ONLY ALLOWED TO HAVE A
 PEDESTRIAN BLADE SIGN, AND THE EXISTING PHARMACY SIGN
 SHALL BE REMOVED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  
  