Plan Review Details - Permit 19080327
Plan Review Stops For Permit 19080327
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-09 Cont ID  
Sent By rmcdouga Date 2019-10-09 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2019-10-09 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-12 Cont ID  
Sent By rmcdouga Date 2019-09-12 Time 17:17 Rev Time 0.00
Received By rmcdouga Date 2019-09-12 Time 11:36 Sent To I
Notes
2019-09-12 15:40:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THIS PROJECT IS A CHANGE OF USE WITH NO CHANGE OF
 OCCUPANCY CLASSIFICATION FBC EXISTING BUILDING SECTION
 1001.2.1
  
 1) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS AS
 REQUIRED BY FBC ENERGY CONSERVATION SECTION R101.5.1.
  
 2) SPECIFY THE BUILDINGS THERMAL ENVELOPE ON THE PLANS.
 INDICATE THE INSULATION MATERIAL AND R-VALUE OF THE
 CEILING INSULATION. FBC ENERGY CONSERVATION R103.2
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 WINDOW TYPES AND EXTERIOR DOOR TYPES.
  
 4) SHOW THAT SECTION 6 ON SHEET S-2G IS IN COMPLIANCE
 WITH FBC-R318.7 INSPECTION FOR TERMITES. IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND
 GARAGE SLABS AND ENTRY AREAS.
  
 5) VERIFY THE ROOF TO WALL CONNECTIONS AND MITIGATE IF
 REQUIRED. FBC-R301.1 APPLICATION. BUILDINGS AND
 STRUCTURES, AND PARTS THEREOF, SHALL BE CONSTRUCTED TO
 SAFELY SUPPORT ALL LOADS, INCLUDING DEAD LOADS, LIVE
 LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS, WIND LOADS
 AND SEISMIC LOADS AS PRESCRIBED BY THIS CODE. THE
 CONSTRUCTION OF BUILDINGS AND STRUCTURES IN ACCORDANCE
 WITH THE PROVISIONS OF THIS CODE SHALL RESULT IN A
 SYSTEM THAT PROVIDES A COMPLETE LOAD PATH THAT MEETS
 THE REQUIREMENTS FOR THE TRANSFER OF LOADS FROM THEIR
 POINT OF ORIGIN THROUGH THE LOAD-RESISTING ELEMENTS TO
 THE FOUNDATION. BUILDINGS AND STRUCTURES CONSTRUCTED AS
 PRESCRIBED BY THIS CODE ARE DEEMED TO COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION.
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-28 Cont ID  
Sent By jpearson Date 2019-08-28 Time 14:05 Rev Time 0.00
Received By jpearson Date 2019-08-28 Time 14:05 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-10-08 Cont ID  
Sent By fmittner Date 2019-10-08 Time 14:50 Rev Time 0.00
Received By fmittner Date 2019-10-08 Time 14:50 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-08-30 Cont ID  
Sent By fmittner Date 2019-08-30 Time 15:25 Rev Time 0.00
Received By fmittner Date 2019-08-30 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-09 Cont ID  
Sent By gjohnson Date 2019-10-09 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2019-10-01 Time 14:11 Sent To  
Notes
2019-10-02 14:12:01R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-12 Cont ID  
Sent By rmcdouga Date 2019-09-12 Time 17:17 Rev Time 0.00
Received By rmcdouga Date 2019-08-06 Time 13:36 Sent To  
Notes
2019-08-07 13:36:12R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-10-16 Cont ID  
Sent By rmcdouga Date 2019-10-16 Time 09:09 Rev Time 0.00
Received By rmcdouga Date 2019-10-16 Time 09:09 Sent To  
Notes
2019-10-16 09:10:22MU 2019-032113-0000, NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-09-12 Cont ID  
Sent By rmcdouga Date 2019-09-12 Time 12:53 Rev Time 0.00
Received By rmcdouga Date 2019-09-12 Time 12:52 Sent To  
Notes
2019-10-09 11:30:04DUE TO THIS PROJECT BEING A CHANGE FORM NON-HABITABLE
 TO HABITABLE SPACE THE PLANS REQUIRE REVIEW BY THE PBC
 IMPACT FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL,
 YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE
 FOR REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF
 THE PAID RECEIPT AS APPLICABLE. PLEASE PROVIDE THE
 MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO THE PBC
 IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: HTTP://DIS
 COVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORM
 S/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-09-09 Cont ID  
Sent By cmontell Date 2019-09-09 Time 10:36 Rev Time 0.00
Received By cmontell Date 2019-09-09 Time 10:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-09 Cont ID  
Sent By gjohnson Date 2019-10-09 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2019-10-09 Time 15:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-23 Cont ID  
Sent By lcrespo Date 2019-08-23 Time 07:17 Rev Time 0.00
Received By lcrespo Date 2019-08-23 Time 06:54 Sent To  
Notes
2019-08-23 07:17:4708/23/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-09-12 Cont ID  
Sent By rmcdouga Date 2019-09-12 Time 12:53 Rev Time 0.00
Received By rmcdouga Date 2019-09-12 Time 12:53 Sent To  
Notes
2019-09-12 12:53:43NO ROOFING WORK SPECIFIED ON PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-30 Cont ID  
Sent By fmittner Date 2019-08-30 Time 15:25 Rev Time 0.00
Received By fmittner Date 2019-08-30 Time 15:25 Sent To  
Notes
***NONE***