Plan Review Details - Permit 19080310
Plan Review Stops For Permit 19080310
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2019-08-13 Cont ID  
Sent By jwitmer Date 2019-08-13 Time 06:25 Rev Time 0.00
Received By jwitmer Date 2019-08-13 Time 06:06 Sent To  
Notes
2019-08-13 06:25:32NOTICE: CONTRACTORS RESPONSIBILITY.
 ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. THIS
 IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-02 Cont ID  
Sent By pvalenti Date 2019-10-02 Time 15:15 Rev Time 0.00
Received By pvalenti Date 2019-10-02 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-17 Cont ID  
Sent By jwitmer Date 2019-09-17 Time 12:40 Rev Time 0.00
Received By jwitmer Date 2019-09-17 Time 06:31 Sent To  
Notes
2019-09-17 12:40:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080310
 ADD: 525 S. FLAGLER DR. SUITE: 10A
 CONT: CAPITAL 1 CONSTRUCTION
 TEL: 954-608-7908
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUESDAY/ SEPT. 17 2019
 ACTION: DENIED
  
 1) 2ND REVIEW. THE PLANS ON THE 2ND REVIEW INDICATE THE
 INSTALLATION OF MAPESOUND 90 FLOOR UNDERLAYMENT. AS
 STATED IN MY TELEPHONE CALL TO YOUR ANSWER MACHINE THIS
 IS A SALES BROCHURE NOT A TEST. IN THE SALES BROCHURE
 THE BROCHURE STATES YOU CAN USE THIS PRODUCT FOR TILE,
 NATURAL STONE OR WOOD FLOORS TO BE ADHERRED TO 6 INCH
 CONCRETE DECK. WITHIN THE BROCHURE THE ACTUAL TEST WAS
 FOR PORCELAIN TILE WITH A SUSPENDED CEILING. IICOF 66
 AND STC 64. TEST WITH NO DROPPED CEILING RENGE FROM 50
 TO 54 IIC AND STC RATINGS. THE SUBMITTED MAPESOUND 90
 DOESN NOT INDICATE ANYWHERE THAT THEY TESTED FOR
 FLAMESPREAD .
  
  
 1ST ROUND OF COMMENTS. THE SUBMITTED UNDERLAYMENT
 PRODUCT TESTING FOR PROTECTO WRAP WHISPERMAT CS
 MEMBRANE UNDERLAYMENT IS THE WRONG TESTING REPORTS. THE
 SUBMITTED REPORTS ARE FOR AN INSTALLATION ON A 8 INCH
 CONCRETE FLOOR AND FOR QUARRY TILE. THE SUBMITTED
 ARCHITECTURAL SHEET A3 INDICATES THE USE OF WOOD FLOORS
 THROUGHOUT THE UNIT, LIVING ROOM, DINING ROOM, KITCHEN,
 & BEDROOMS.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By jwitmer Date 2019-08-13 Time 06:24 Rev Time 0.00
Received By jwitmer Date 2019-08-13 Time 06:06 Sent To  
Notes
2019-08-13 06:23:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080310
 ADD: 525 S. FLAGLER DR. SUITE: 10A
 CONT: CAPITAL 1 CONSTRUCTION
 TEL: 954-608-7908
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY/ AUGUST 13TH/ 2019
 ACTION: DENIED
  
 1) THE SUBMITTED UNDERLAYMENT PRODUCT TESTING FOR
 PROTECTO WRAP WHISPERMAT CS MEMBRANE UNDERLAYMENT IS
 THE WRONG TESTING REPORTS. THE SUBMITTED REPORTS ARE
 FOR AN INSTALLATION ON A 8 INCH CONCRETE FLOOR AND FOR
 QUARRY TILE. THE SUBMITTED ARCHITECTURAL SHEET A3
 INDICATES THE USE OF WOOD FLOORS THROUGHOUT THE UNIT,
 LIVING ROOM, DINING ROOM, KITCHEN, & BEDROOMS.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-19 Cont ID  
Sent By jpearson Date 2019-09-19 Time 13:36 Rev Time 0.00
Received By jpearson Date 2019-09-19 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-11 Cont ID  
Sent By jpearson Date 2019-08-11 Time 10:01 Rev Time 0.00
Received By jpearson Date 2019-08-11 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By J.Walker Date 2019-09-20 Time   Rev Time 0.00
Received By jwalker Date 2019-09-20 Time   Sent To  
Notes
2019-09-20 13:55:58RETURNED TO B-33

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-08 Cont ID  
Sent By J.Walker Date 2019-08-08 Time   Rev Time 0.00
Received By jwalker Date 2019-08-08 Time   Sent To  
Notes
2019-08-08 14:46:34RETURNED TO B-25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-02 Cont ID  
Sent By pvalenti Date 2019-10-02 Time 15:15 Rev Time 0.00
Received By pvalenti Date 2019-09-26 Time 14:07 Sent To  
Notes
2019-09-27 14:07:19RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-20 Cont ID  
Sent By shill Date 2019-09-20 Time 17:53 Rev Time 0.00
Received By shill Date 2019-09-06 Time 09:55 Sent To  
Notes
2019-09-09 09:57:47B33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-22 Cont ID  
Sent By jesmith Date 2019-08-22 Time 14:26 Rev Time 0.00
Received By jesmith Date 2019-08-22 Time 14:26 Sent To  
Notes
2019-08-07 14:28:54B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-08-13 Cont ID  
Sent By jwitmer Date 2019-08-13 Time 06:22 Rev Time 0.00
Received By jwitmer Date 2019-08-13 Time 06:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-10-02 Cont ID  
Sent By ccole Date 2019-10-02 Time 13:06 Rev Time 0.00
Received By ccole Date 2019-10-02 Time 12:00 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By hmoser Date 2019-09-16 Time 11:21 Rev Time 0.00
Received By hmoser Date 2019-09-16 Time 11:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-22 Cont ID  
Sent By hmoser Date 2019-08-22 Time 11:55 Rev Time 0.00
Received By hmoser Date 2019-08-22 Time 11:20 Sent To  
Notes
2019-08-22 11:55:43PLAN DENIED
 REFER TO SECTION 403.3.2.3 LOCAL EXHAUST.
 EXHAUST SHALL BE PROVIDED IN BATHROOMS AND
 TOILET ROOMS, ALSO SHOW THE TERMINATION OF THE
 BATHROOM EXHAUST ON THE PLAN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By jesmith Date 2019-09-17 Time 12:46 Rev Time 0.00
Received By jesmith Date 2019-09-17 Time 12:43 Sent To  
Notes
2019-09-17 12:46:05PLUMBING COMMEMTS: APPROVED W/PROVISO
  
 1. PER WPB FBC 107.2.1 AND 107.3.4.1, SUBMIT AS A
 DEFERRED SUBMITTAL CROSS SECTIONAL DETAIL OF SHOWER
 CONSTRUCTION SHOWING COMPLIANCE WITH FBC PL SECTION
 417. BOTH SHOWERS SHALL SHALL BE RECONSTRUCTED TO
 COMPLY. SUBMITTAL SHALL BE SUBMITTED, APPROVED AND IN
 PLACE PRIOR TO FIRST PLUMBING INSPECTION. SEE WPB FBC
 107.3.4.1 BELOW.
 A. REFER TO RED LINED COMMENTS ON PLAN SHEET P-1
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-22 Cont ID  
Sent By jesmith Date 2019-08-22 Time 14:26 Rev Time 0.00
Received By jesmith Date 2019-08-22 Time 14:07 Sent To  
Notes
2019-08-22 14:15:59PLUMBING COMMEMTS: APPROVED W/PROVISO
  
 1. PER WPB FBC 107.2.1 AND 107.3.4.1, SUBMIT AS A
 DEFERRED SUBMITTAL CROSS SECTIONAL DETAIL OF SHOWER
 CONSTRUCTION SHOWING COMPLIANCE WITH FBC PL SECTION
 417. BOTH SHOWERS SHALL BE RECONSTRUCTED TO COMPLY.
 SUBMITTAL SHALL BE SUBMITTED, APPROVED AND IN PLACE
 PRIOR TO FIRST PLUMBING INSPECTION. SEE WPB FBC
 107.3.4.1 BELOW.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  