Plan Review Details - Permit 19080244
Plan Review Stops For Permit 19080244
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By pleduc Date 2019-08-30 Time   Rev Time 0.00
Received By pleduc Date 2019-08-30 Time 10:47 Sent To M
Notes
2019-08-30 10:48:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FIRE INSPECTOR SHALL REVIEW THE CAUTION POINTS
 ON THE MANUFACTURES SPEC SHEET TO ENSURE FIRE SAFETY
 AND COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-07 Cont ID  
Sent By pleduc Date 2019-08-07 Time   Rev Time 0.00
Received By pleduc Date 2019-08-07 Time 14:55 Sent To M
Notes
2019-08-07 15:05:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO FLOOR PLAN SHEET LOCATING THE PROPOSED
 INSTALLATION.
  
 PLEASE PROVIDE A DETAILED FLOOR PLAN INCLUDING
 DIMENSIONS.
  
  
  
 2) THERE ARE ONLY LIMITED SHEETS PROVIDED FOR THE
 PROPOSED EQUIPMENT.
  
 PAGES ARE MISSING,
  
 PLEASE PROVIDE THE ENTIRE SPEC SHEET PACKET WITH ALL
 PAGES TO CONFIRM ALL SPECS ARE MET.
  
  
  
 3) WHAT IS THE POWER SOURCE FOR THE PROPOSED.
  
 PLEASE PROVIDE THE WIRING DIAGRAMS AND LOCATIONS AND
 SIZE OF EXISTING POWER SOURCE.
  
  
  
 4) THERE IS NO INDICATION OF A AUTOMATIC SHUT OFF AS
 PER NFPA 96.
  
 PER NFPA 96
  
 10.5 MANUAL ACTIVATION.
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL
 BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. AND 48
 IN.)
 ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT OF A FIRE,
 BE LOCATED
 IN A PATH OF EGRESS, AND CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED
 A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT)
 FROM
 THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH OF
 EGRESS
 OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ.
 10.5.1.2 MANUAL ACTIVATION USING A CABLE-OPERATED PULL
 STATION
 SHALL NOT REQUIRE MORE THAN 178 N (40 LB) OF FORCE,
 WITH A
 PULL MOVEMENT NOT TO EXCEED 356 MM (14 IN.) TO ACTIVATE
 THE
 AUTOMATIC FIRE-EXTINGUISHING EQUIPMENT.
 10.5.2 THE AUTOMATIC AND MANUAL MEANS OF SYSTEM
 ACTIVATION
 EXTERNAL TO THE CONTROL HEAD OR RELEASING DEVICE SHALL
 BE SEPARATE
 AND INDEPENDENT OF EACH OTHER SO THAT FAILURE OF ONE
 WILL NOT
 IMPAIR THE OPERATION OF THE OTHER EXCEPT AS PERMITTED
 BY 10.5.3.
  
 PLEASE REVIEW, PROVIDE AND INCLUDE LOCATION ON FLOOR
 PLAN.
  
  
  
 5) THERE IS NO INDICATION OF SYSTEM ACTIVATION PER NFPA
 96
  
 10.6 SYSTEM ANNUNCIATION.
 10.6.1 UPON ACTIVATION OF AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM,
 AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE PROVIDED
 TO
 SHOW THAT THE SYSTEM HAS ACTIVATED.
 10.6.2 WHERE A FIRE ALARM SIGNALING SYSTEM IS SERVING
 THE OCCUPANCY
 WHERE THE EXTINGUISHING SYSTEM IS LOCATED, THE
 ACTIVATION
 OF THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL
 ACTIVATE
 THE FIRE ALARM SIGNALING SYSTEM.
  
  
 PLEASE REVIEW AND PROVIDE.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-29 Time 14:54 Sent To  
Notes
2019-08-29 14:54:43RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-12 Cont ID  
Sent By cmontell Date 2019-08-12 Time 11:31 Rev Time 0.00
Received By cmontell Date 2019-08-12 Time 11:31 Sent To  
Notes
2019-08-06 13:06:14ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-05 Cont ID  
Sent By hmoser Date 2019-09-05 Time 10:28 Rev Time 0.00
Received By hmoser Date 2019-09-05 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By cmontell Date 2019-08-12 Time 11:29 Rev Time 0.00
Received By cmontell Date 2019-08-12 Time 11:29 Sent To I
Notes
***NONE***