Plan Review Details - Permit 19080226
Plan Review Stops For Permit 19080226
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-15 Cont ID  
Sent By jbrooks Date 2019-08-15 Time 09:41 Rev Time 0.00
Received By jbrooks Date 2019-08-15 Time 09:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-08 Cont ID  
Sent By jbrooks Date 2019-08-08 Time 13:17 Rev Time 0.00
Received By jbrooks Date 2019-08-08 Time 13:17 Sent To  
Notes
2019-08-08 13:19:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1.FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: COLUMN HEADING
 ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT
 APPROVAL?; PROVIDE INFORMATION FROM SHEETS 6 & 7 OF
 FL1850 USE ALPHABETICAL LETTER THAT CORRESPONDS WITH
 THE CONNECTION TYPE FOR THE TOP AND BOTTOM CONNECTIONS.
 COLUMN HEADING ?SHUTTER GLASS SEPARATION?; PROVIDE
 INFORMATION FROM SHEET 11 FL1850. COLUMN HEADING
 ?SHUTTER SPAN?; PROVIDE INFORMATION FROM SHEET 5
 FL1850, THE TOP OF THE SHUTTER BLADE TO THE BOTTOM OF
 THE SHUTTER BLADES LENGTH. COLUMN HEADING ?MINIMUM EDGE
 DISTANCE?; PROVIDE INFORMATION FROM SHEET 13 FL1850.
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
 REDUCE ANCHOR SPACING BY MUTIPLYING SPACING SHOWN ON
 SCHEDULE BY THE FACTOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-15 Cont ID  
Sent By jbrooks Date 2019-08-15 Time 09:42 Rev Time 0.00
Received By jbrooks Date 2019-08-13 Time 13:28 Sent To  
Notes
2019-08-14 13:28:51RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-08 Cont ID  
Sent By jbrooks Date 2019-08-08 Time 13:19 Rev Time 0.00
Received By jbrooks Date 2019-08-05 Time 13:28 Sent To  
Notes
2019-08-06 13:28:16BLDG MISC 1