| 2019-09-13 12:43:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19080142 |
| | 9/132019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE MAIN PERMIT- #19070090- FOR THE PROPOSED RESTAURANT |
| | HAS NOT BEEN APPROVED AND ISSUED. COMMENT #5 FROM MY |
| | REVIEW ON 8/9/2019 IS APPLICABLE TO THIS HOOD PERMIT |
| | REVIEW. |
| | |
| | 5) ADVISORY: THE HOOD IS UNDER SEPARATE PERMIT HOWEVER |
| | MEETING COMPLIANCE WITH SECTION 508.1.1 MAY REQUIRE |
| | CHANGES TO THE MAIN HVAC DESIGN. VERIFY THAT THE |
| | TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST HOOD |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE DOES |
| | NOT EXCEED 10 DEGREES F- SECTION 508.1.1 FBC M. |
| | 508.1.1MAKEUP AIR TEMPERATURE. THE TEMPERATURE |
| | DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE |
| | CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT |
| | WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP |
| | AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| | |
| | NEW COMMENTS. |
| | |
| | 1) THERE IS NO VALUE FOR THE HOOD PROJECT LISTED ON THE |
| | APPLICATION, AND THE STATED REASON IS IT WAS COVERED |
| | UNDER THE MAIN PERMIT. PLEASE PROVIDE DOCUMENTATION |
| | SUCH AS A COPY OF THE CONTRACT OR COST BREAKDOWN TO |
| | VERIFY, OTHERWISE PROVIDE A VALUE FOR THE HOOD PROJECT |
| | THAT INCLUDES LABOR, MATERIALS, EQUIPMENT AND DESIGN |
| | FEES- SECTION 109.3 WPB. |
| | |
| | 2) THE M1.0 AND M2.0 PLANS ARE NOT ELECTRONICALLY |
| | SIGNED AND SEALED- SECTION 61G15-23.005 FAC. |
| | |
| | 3) VERIFY THE REQUIRED 18 IN. CLEARANCES TO |
| | COMBUSTIBLES FOR THE GREASE DUCT AND THE EXHAUST - SEE |
| | SECTIONS 506.3.6 AND 507.2.6 FBC M. PROVIDE A FRONT |
| | VIEW DETAIL SHOWING THE HOOD WITH ALL REQUIRED |
| | CLEARANCES, AND EXHAUST AND MAKEUP AIR DUCT RUNS AND |
| | CLEARANCES. IF GREASE DUCT WRAP IS TO BE USED PLEASE |
| | INDICATE WHICH PRODUCT WILL BE USED AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |