Plan Review Details - Permit 19080142
Plan Review Stops For Permit 19080142
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By J.Walker Date 2019-10-11 Time   Rev Time 0.00
Received By jwalker Date 2019-10-11 Time   Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-08-19 Cont ID  
Sent By J.Walker Date 2019-08-19 Time   Rev Time 0.00
Received By jwalker Date 2019-08-19 Time   Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-10-22 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-10 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-16 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By ccole Date 2019-10-22 Time 09:12 Rev Time 0.00
Received By ccole Date 2019-10-21 Time 17:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By ccole Date 2019-09-13 Time 12:21 Rev Time 0.00
Received By ccole Date 2019-09-13 Time 11:20 Sent To  
Notes
2019-09-13 12:43:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080142
 9/132019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE MAIN PERMIT- #19070090- FOR THE PROPOSED RESTAURANT
 HAS NOT BEEN APPROVED AND ISSUED. COMMENT #5 FROM MY
 REVIEW ON 8/9/2019 IS APPLICABLE TO THIS HOOD PERMIT
 REVIEW.
  
 5) ADVISORY: THE HOOD IS UNDER SEPARATE PERMIT HOWEVER
 MEETING COMPLIANCE WITH SECTION 508.1.1 MAY REQUIRE
 CHANGES TO THE MAIN HVAC DESIGN. VERIFY THAT THE
 TEMPERATURE DIFFERENTIAL BETWEEN THE EXHAUST HOOD
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE DOES
 NOT EXCEED 10 DEGREES F- SECTION 508.1.1 FBC M.
 508.1.1MAKEUP AIR TEMPERATURE. THE TEMPERATURE
 DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT
 WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP
 AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 NEW COMMENTS.
  
 1) THERE IS NO VALUE FOR THE HOOD PROJECT LISTED ON THE
 APPLICATION, AND THE STATED REASON IS IT WAS COVERED
 UNDER THE MAIN PERMIT. PLEASE PROVIDE DOCUMENTATION
 SUCH AS A COPY OF THE CONTRACT OR COST BREAKDOWN TO
 VERIFY, OTHERWISE PROVIDE A VALUE FOR THE HOOD PROJECT
 THAT INCLUDES LABOR, MATERIALS, EQUIPMENT AND DESIGN
 FEES- SECTION 109.3 WPB.
  
 2) THE M1.0 AND M2.0 PLANS ARE NOT ELECTRONICALLY
 SIGNED AND SEALED- SECTION 61G15-23.005 FAC.
  
 3) VERIFY THE REQUIRED 18 IN. CLEARANCES TO
 COMBUSTIBLES FOR THE GREASE DUCT AND THE EXHAUST - SEE
 SECTIONS 506.3.6 AND 507.2.6 FBC M. PROVIDE A FRONT
 VIEW DETAIL SHOWING THE HOOD WITH ALL REQUIRED
 CLEARANCES, AND EXHAUST AND MAKEUP AIR DUCT RUNS AND
 CLEARANCES. IF GREASE DUCT WRAP IS TO BE USED PLEASE
 INDICATE WHICH PRODUCT WILL BE USED AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By ccole Date 2019-10-22 Time 09:18 Rev Time 0.00
Received By ccole Date 2019-10-22 Time 09:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By ccole Date 2019-09-13 Time 13:08 Rev Time 0.00
Received By ccole Date 2019-09-13 Time 13:08 Sent To  
Notes
2019-09-13 13:09:06SHEETS M1.0 & M2.0 ARE NOT ELECTRONICALLY SIGNED AND
 SEALED.