Plan Review Details - Permit 19080089
Plan Review Stops For Permit 19080089
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2020-03-09 Cont ID  
Sent By cpuell Date 2020-03-09 Time 16:29 Rev Time 0.00
Received By cpuell Date 2020-03-09 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By jwitmer Date 2019-09-10 Time 09:11 Rev Time 0.00
Received By jwitmer Date 2019-09-09 Time 16:57 Sent To  
Notes
2019-09-10 08:58:242017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090089
 ADD: 1022 CLEARWATER PARK
 CONT: MASTER CONTRACTORS
 TEL: 561-248-5498
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 10/2019
 ACTION: DENIED
  
 1) SHEET COVERSHEET:
 1A) OCCUPANT LOADS BUSINESS OCCUPANCY IS STATED AT 20
 SQ. FT. PLEASE REVIEW 2017 FBC-B TABLE 1004.1.2
 BUSINESS OCCUPANCY OCCUPANT LOAD FACTOR IS 100 SQ. FT.
 PER OCCUPANT. BUSINESS AREA 4347/ 100= 44 OCCUPANTS.
  
 1B) OCCUPANT LOADS STORAGE OCCUPANCY IS STATED AT 300
 SQ. FT. THIS IS CORRECT. PLEASE REVIEW 2015 FBC-B
 COMMENTARY THAT THERE CANNOT BE FRACTIONAL PARTS OF AN
 OCCUPANT YOU ALWAYS ROUND UP TO THE NEXT WHOLE NUMBER.
 ALSO SEE BOAF INFORMAL INTERPRETATION ON LINE.
  
 1C) OCCUPANT LOADS. THE BUSINESS OCCUPANCY AS STATED
 218 PLUS THE 1 OCCUPANT FROM THE STORAGE OCCUPANCY IS
 219 OCCUPANTS. HOW DO YOU COME UP WITH 230 OCCUPANTS?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. TOTAL
 OCCUPANTS 44 +1 = 45 TOTAL OCCUPANTS.
  
 1D) THE SQUARE FOOT AREAS OF THE EXISTING BUILDINGS
 DOES NOT TOTAL THE GROSS SQUARE FOOT AREA GIVEN BY
 DEFINITION. FLOOR AREA, GROSS. THE FLOOR AREA OF A
 BUILDING, OR PORTION THEREOF, NOT PROVIDED WITH
 SURROUNDING EXTERIOR WALLS SHALL BE THE USABLE AREA
 UNDER THE HORIZONTAL PROJECTION OF THE ROOF OR FLOOR
 ABOVE. THE GROSS FLOOR AREA SHALL NOT INCLUDE SHAFTS
 WITH NO OPENINGS OR INTERIOR COURTS. IT WOULD APPEAR
 THE AREA BETWEEN BUILDINGS 1-2 AND BUILDING 3 THE AREA
 6.25 FT. X 75.5 = 471.875 SQ. FT. IS NOT BEING INCLUDED
 IN THE AREA CALCULATION FOR FLOOR AREA GROSS. THEN ADD
 THE ADDITIONAL SQ. FEET OF THE ADDITION995 SQ. FT.
  
 1E) DISCREPANCY IN PLANS. DEPENDING ON WHICH PAGE IN
 THE PLANS YOU GET A DIFFERENT SQUARE FOOT NUMBER FOR
 THE ADDITION. ADDITIONAL INFORMATION IS REQUIRED
 107.2.1.2. PLEASE CORRECT THE SQUARE FOOTAGE OF THE
 ADDITION.
 COVERSHEET FLOORPLAN THE ADDITION IS---------995 SQ.
 FT.
 SHEET SP-2 BUILDING 3 ADDITION CALCS. IS------985 SQ.
 FT.
 SHEET A-1 BUILDING 3 ADDITION IS---------------985 SQ.
 FT.
 SHEET M-1 BUILDING 3 ADDITION IS LISTED AS--795 SQ. FT.
  
 1F) UNDER THE HEADING CALCULATION OF WORK THE PLANS
 STATE A LEVEL III ALTERATION. PLEASE REVIEW THE 2017
 EXISTING BUILDING CODE CLASSIFICATION OF WORK SECTION
 507. 507.1 SCOPE. PROVISIONS FOR ADDITIONS SHALL APPLY
 WHERE WORK IS CLASSIFIED AS AN ADDITION AS DEFINED IN
 CHAPTER 2. ADDITION. AN EXTENSION OR INCREASE IN FLOOR
 AREA, NUMBER OF STORIES, OR HEIGHT OF A BUILDING OR
 STRUCTURE. ADDITIONS ARE FOUND IN CHAPTER 11 OF THE
 2017 EXISTING BUILDING CODE. NOT LEVEL III.
  
 2) SHEET A-1, A-3 & A-4 THE WALL PLAN LEGEND INDICATES
 THE NEW INTERIOR WALLS OF THE ADDITION SOME ARE
 INDICATED AS NEW AND SOME AS EXISTING AS WELL AS IN THE
 EXISTING BUILDING THE WALL DESIGNATION TYPE IS
 INDICATED AS ALL NEW WALLS? THE CITY FILE NET FOR
 RECORD RETENTION SHOWS PERMIT 15060795 FOR THIS SAME
 BUILDING AND THE WALL LOCATION UNDER THAT PERMIT ARE IN
 THE SAME LOCATION. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) SHEET A-2 NOTE ON THE PLAN EAST ELEVATION THAT
 INDICATES THE USE OF NEW JOIST HANGER TO BE SIMPSON SEE
 A-4. SHEET A-4 DOES NOT SHOW THE USE OF ANY JOIST
 HANGER. SHEET A-5 DOES SHOW THE NEW ROOF FRAMING
 MEMBERS TO BE PRESSURE TREATED 2X10 YELLOW PINE. DETAIL
 1 OF SHEET A-5 SHOWS THE 2X10 NOT IN A HANGER BUT
 SITTING ON TOP OF THE EXISTING CONCRETE BEAM.
 DISCREPANCY IN PLANS. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) SHEET A-5 DETAIL 1 INDICATES THE USE OF P. T. 2X10
 RAFTERS. AS DEPICTED THEY ARE DRAWN IN THE SAME SIZE AS
 THE 2X4 BOTTOM CHORD OF THE TRUSSES. THE ROOF LINE WILL
 INTERSECT FURTHER UP THE TRUSS LINE WHEN DRAWN AS A
 2X10. PLEASE NOTE THE EXISTING CONCRETE BEAM SHEET A-2
 INDICATES THE BEAM ELEVATION AT 8 FEET ABOVE FINISH
 FLOOR. DETAIL 1 SHEET A-5 ALSO SHOWS THE FURTHEST WALL
 FROM THE EXISTING BUILDING (WALL THE RAFTERS SIT ON AT
 8 FEET ELEVATION ABOVE FINISH FLOOR OR NO SLOPE ON THE
 RAFTERS. THE DESIGNER OF RECORD HAS SUBMITTED GAF
 RUBEROID MODIFIED BITUMEN ROOFING SYSTEM NOA
 18-0919.12. PLEASE NOTE UNDER THE 2017 FBC-B SECTION
 1507.11.1 THE SLOPE SHALL BE 2-PERCENT SLOPE OR NOT
 LESS THAN ? UNIT VERTICAL IN 12 UNITS HORIZONTAL OR A 4
 INCH DIFFERENCE IN HEIGHT MINIMUM.
  
 5) SHEET A-5 DETAILS 1 & 2 SHOW P. T. 2X10 RAFTERS AT 2
 FEET ON CENTER. SHEET A-5 DOES NOT GIVE US THE LIVE AND
 DEAD LOADS NOR THE GRADE OF WOOD NOR THE BENDING DESIGN
 VALUES FB. PLEASE NOTE ON THE SHEET A-0 THERE ARE NO
 DESIGN VALUES FOR DIMENSIONAL 2X10S. THERE ARE DESIGN
 VALUES FOR TRUSSES OF 30 PSF ROOF LIVE LOAD AND 25 PSF
 FOR SUPERIMPOSED DEAD LOADS. WITHIN THE FBC-B THE
 TABLES 2308.7.2(2) THE DEAD LOAD STOPS AT 20 PSF AND
 DEFLECTION OF 240. THE SAME HOLDS TRUE FOR SPAN TABLES
 FOR JOIST AND RAFTERS FROM THE AMERICAN WOOD COUNCIL
 TABLE R-10. PLEASE PROVIDE ADDITIONAL INFORMATION FOR
 GRADE OF WOOD TO BE USED AND DEAD LOAD AND DEFLECTION
 TO BE ABLE TO DETERMINE THE TIMBER SIZE.
  
 6) SHEET A-5 DETAIL # 2 INDICATES THE FINISH FLOOR
 LEVEL BUT DOES NOT PROVIDE WHAT FINISH GRADE WILL BE?
 DETAIL # 1 ON THE SAME SHEET DOES SHOW GRADE 6 INCHES
 LOWER THAN FINISH FLOOR. THERE ARE 2 AREAS OF CONCERN:
 6A) THAT THE FOUNDATION SHALL COMPLY WITH 2017 FBC-B
 SECTION 1809.4. THE MINIMUM DEPTH OF THE FOUNDATION
 BELOW THE UNDISTURBED GROUND SURFACE SHALL BE 12
 INCHES.
  
 6B) THE SECOND ISSUE FOUND IS THE NOT KNOWING WHERE THE
 FINISH GRADE IS AND THE USE OF STUCCO AND WOOD
 SUB-SHEATHING POSSIBLY AT GRADE. 2017 FBC-B SECTION
 2304.12.1.5. BETWEEN GRADE AND WOOD SIDING AND OR WOOD
 SUB-SHEATHING ON THE EXTERIOR OF THE BUILDING SHALL NOT
 BE LESS THAN 6 INCHES UNLESS THE WALL SHEATHING IS
 NATURALLY DURABLE WOOD OR PRESSURE TREATED WOOD.
  
 7) SHEET A-0 DOES NOT REQUIRE A SOILS TEST, PLEASE SHOW
 COMPLIANCE WITH 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 8) SHEET A-5 SHOWS DETAIL 1 & 2 OF THE EXISTING ROOF
 AND THE TIE-IN OF THE NEW ADDITION AND ROOF LINE. THE
 PLANS ARE SILENT AS TO HOW VENTILATION FOR ATTICS WILL
 BE ACHIEVED? PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION 1203.2.
  
 9) THIS REVIEW THERE WERE NO DOCUMENTS SUBMITTED FOR
 ENERGY COMPLIANCE. PLEAS SHOW HOW COMPLIANCE WITH THE
 2017 ENERGY CODE WILL BE ACHIEVED.
 C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
  
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
  
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
  
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 C101.5 COMPLIANCE.
  
 COMMERCIAL BUILDINGS SHALL MEET THE PROVISIONS OF
 FLORIDA BUILDING CODE, ENERGY CONSERVATION?COMMERCIAL
 PROVISIONS.
  
 C101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING
 COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE.
 THE CODE OFFICIAL SHALL BE PERMITTED TO APPROVE
 WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR
 MATERIALS THAT MEET THE INTENT OF THIS CODE.
  
  
 10) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-09-12 Cont ID  
Sent By jpearson Date 2019-09-12 Time 15:48 Rev Time 0.00
Received By jpearson Date 2019-09-12 Time 09:51 Sent To  
Notes
2019-09-12 15:12:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE MORE DETAIL ON RISER DIAGRAM, SHOWING ALL
 DETAILS OF FEEDERS FROM FPL. SHOW GEC SIZE AND SYSTEM,
 SHOW INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5,
 230, 250.50, 250.94, 408.30; WPB FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. SEVERAL ITEMS APPEAR TO BE MISSING
 OR INCORRECT. NEC 215.2, 220, 408.30
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 4. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 5. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 6. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 7. PLUMBING PLAN SHOWS A TANKLESS WATER HEATER THAT IS
 NOT INCLUDED IN THE PANEL SCHEDULES OR THE LOAD
 CALCULATION. PROVIDE SPEC SHEET FOR TANKLESS WATER
 HEATER AND PROVIDE CORRECTIONS. NEC 110.3; WPB FBC
 107.2.1
 8.THERE ARE FOUR APPLIANCES SHOWN IN THE UTILITY AREA
 THAT ARE NOT IDENTIFIED. THE CIRCUIT NUMBERS SHOWN FOR
 THESE FROM PANEL A EITHER DO NOT PROVIDE DETAIL, OR
 APPEAR TO BE WRONG. PROVIDE CLARIFICATIONS AND
 CORRECTIONS. LABEL APPLIANCES. WPB FBC 107.2.1
 9. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-09-12 Cont ID  
Sent By shill Date 2019-09-12 Time 14:42 Rev Time 0.00
Received By shill Date 2019-09-12 Time 14:42 Sent To  
Notes
2019-09-12 14:42:49CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-06 Cont ID  
Sent By pleduc Date 2019-08-06 Time   Rev Time 0.00
Received By pleduc Date 2019-08-06 Time 13:17 Sent To  
Notes
2019-08-06 13:41:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 3 - THERE ARE NO INDICATIONS OF REVIEW AND
 COMPLIANCE WITH NFPA 150, FIRE AND LIFE SAFETY IN
 ANIMAL HOUSING FACILITIES
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 COMPLIANCE.
  
  
  
  
 2) SHEET A 1 - THERE APPEARS TO BE AN OPENING OF THE
 REAR WALL BETWEEN THE BATHROOMS AND NEW LAUNDRY ROOM
 THAT SHOWS NO DETAIL.
  
 IS THIS AN EXTERIOR WALL PORTION THAT NEEDS TO REMOVED
 AND FINISHED?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET A 1 - THERE APPEARS TO BE NEW WALLS ALONG A
 PORTION OF THE BIG DOG ROOM/LAUNDRY ROOM SEPARATION
 THAT ARE INDICATED AS EXISTING WALLS.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
 4) SHEET A 3 & E 1 - THE ARE NO EXIT SIGNS AT THE EXIT
 DISCHARGE OR EXIT PATH PER THE LIFE SAFETY PLAN.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 PLEASE REVIEW AND PROVIDE EXIT SIGNS WHERE REQUIRED.
  
  
  
 5) SHEET A 1 - THERE APPEARS TO BE WINDOWS THAT ARE
 BEING FILLED IN HOWEVER, THERE IS NO DETAIL ON THE
 IN-FILL, INCLUDING INTERIOR FINISH TYPE.
  
 PER NFPA 101, CH 38, NEW BUSINESS
  
 38.3.3 INTERIOR FINISH.
 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 38.3.3.2 INTERIOR WALL AND CEILING FINISH.
 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL
 COMPLYING WITH
 SECTION 10.2 SHALL BE CLASS A OR CLASS B IN EXITS AND
 IN EXIT ACCESS
 CORRIDORS.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
 6) SHEET A 3 - THE NEW ADDITIONS DOES NOT INDICATED TWO
 EXITS OUT OF EACH AREA.
  
 PER NFPA 150
  
 8.1.2.1 NUMBER OF MEANS OF EGRESS.
 8.1.2.1.1 TWO MEANS OF EGRESS FOR HUMAN AND ANIMAL
 OCCUPANTS,
 AS A MINIMUM, SHALL BE PROVIDED IN EVERY FACILITY,
 SECTION,
 AND AREA WHERE SIZE, OCCUPANCY, AND ARRANGEMENT
 ENDANGER
 OCCUPANTS ATTEMPTING TO USE A SINGLE MEANS OF EGRESS
 THAT IS BLOCKED BY FIRE OR SMOKE.
 8.1.2.1.2 WHERE TWO MEANS OF EGRESS ARE REQUIRED, THEY
 SHALL
 BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT BOTH MIGHT
 BE
 RENDERED IMPASSABLE BY THE SAME EMERGENCY CONDITION.
  
 PLEASE REVIEW AND INDICATED TWO EXITS AND ROUTES FROM
 EACH AREA.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-09-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-01 Time 14:09 Sent To  
Notes
2019-08-15 10:16:38ROUTED FROM ZONING TO PERMIT LIBRARIAN 8/15/19 EL
2019-08-02 14:09:58C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By jwitmer Date 2019-09-10 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2019-09-09 Time 16:57 Sent To  
Notes
2019-09-10 08:59:08IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-13 Cont ID  
Sent By ccole Date 2019-09-13 Time 14:37 Rev Time 0.00
Received By ccole Date 2019-09-13 Time 13:42 Sent To  
Notes
2019-09-13 15:25:111ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080089
 9/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M1 & M2: PROVIDE A SCOPE OF WORK FOR BUILDING
 3 WITH KEYNOTES ON THE PLAN. IT APPEARS A NEW 5-TON AC
 SYSTEM IS BEING INSTALLED, AND NEW SUPPLY AND EXHAUST
 FANS- SECTION 107.1WPB.
  
 2) M2: THE AC EQUIPMENT SCHEDULE FOR THE ADDITION
 INDICATES A RHEEM CONDENSER AND TRANE AIRHANDLER WHCH
 ARE MISMATCHED UNITS. PROVIDE A MATCHED SYSTEM OR
 CALCULATIONS AND SUPPORTING DATA FROM THE DESIGN
 PROFESSIONAL THAT DEMONSTRATES THE SYSTEM WILL MEET THE
 REQUIRED EFFICIENCY RATING- SECTION C403.2.3 FBC EC.
  
 3) M1 & M2: SHOW HOW O/A IS BEING PROVIDED TO THE NEW
 AND EXISTING AIRHANDLERS IN THE ADDITION AND BUILDING
 3- SECTION 401.2 FBC M. ACCORDING TO THE SCHEDULE THE
 NEW ADDITON SYSTEM IS PROVIDING 300 CFMS OF O/A AIR BUT
 NO O/A DUCT IS SHOWN.
  
 4) M1 & M2: IT APPEARS BY THE PLAN THAT INADEQUATE
 MAKEUP AIR IS BEING PROVIDED FOR THE EXHAUST SYSTEMS.
 REFER TO SECTION 501.4 AND PROVIDE AIR BALANCE
 CALCULATIONS FOR THE NEW ADDITION AND BUILDING 3.
  
 5) SHOW THE LOCATIONS OF THE NEW CONDENSERS AND PROVIDE
 INSTALLATION DETAILS- SEE SECTION 301.15 AND 301.16 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-10 Cont ID  
Sent By gjohnson Date 2019-09-10 Time 18:42 Rev Time 0.00
Received By gjohnson Date 2019-09-10 Time 17:16 Sent To  
Notes
2019-09-10 18:42:161ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT P-1 THE UPSTREAM WASHING MACHINE IS NOT VENTED
 PLEASE SHOW VENT ON SANITARY ISOMETRIC. PER FBC PL
 901.2.1
  
 2. SHT P-1 PLEASE SIZE ALL PIPING ON SANITARY
 ISOMETRIC. THE BRANCH DRAIN TO NEW WASHERS SHALL BE 3"
 MIN. PER FBC PL 406.2
  
 3. A LINT TRAP IS REQUIRED ON WASHER DRAINS. PER FBC PL
 1003.6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-09-10 Cont ID  
Sent By jwitmer Date 2019-09-10 Time 09:10 Rev Time 0.00
Received By jwitmer Date 2019-09-10 Time 09:00 Sent To  
Notes
2019-09-10 09:10:11REVIEWED AND APPROVED.
 NOA: 18-0919.12 GAF RUBEROID MODIFIED BITUMEN ROOFING
 SUB-SYSTEM, PAGE 53
 FASTENING OPTION # 3. MAXIMUM DESIGN PRESSUE -52.5
 LIMITATION # 7.
 ENHANCED FASTENING APPROVED.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-15 Cont ID  
Sent By aaponte Date 2019-08-15 Time 10:16 Rev Time 0.00
Received By elevesqu Date 2019-08-15 Time 09:46 Sent To  
Notes
2019-08-15 10:16:15PLEASE SHOW THE ADDITION ON A SITE PLAN AND INDICATE
 SETBACKS
  
 PER TABLE IV-12 OF SECTION 94-116, BUILDING
 REQUIREMETNS FOR CLEARLAKE DISTRICT -25, NEW BUILDING
 ADDITIONS REQUIRED TO MEET ACTIVE USE AND TRANSPARENCY
 RQUIREMENTS
 THE ACTIVE USE REQUIREMETN IS 30% OF THE BUILDING
 FACADE (ADDITION ONLY) AND TRANSPARENCY IS 30% OF THE
 BUIDING FACADE (ADDITION ONLY). PLEASE SEE DEFINITION
 OF ACTIVE USE AND TRANSPARENCY IN SECTION 94-109
  
 A SEPARATE LANDSCAPE PERMIT IS REQUIRED FOR ADDITION OF
 LANDSCAPE MATERIAL. REQUIRED PRIOR TO APPROVAL OF
 BUILDING PERMIT. THE PLAN INDICATES HIBISCUS HEDGE IS
 BEING REPLACED, BUT THE LATEST APPROVED LANDSCAPE PLAN
 WAS APPROVED FOR COCOPLUM HEDGE. IT ALSO APPEARS THAT
 THERE ARE TREES MISSING FROM THE SOD AREA WHERE THE NEW
 ADDITION IS BEING PROPOSED. IF THESE WERE REMOVED, THEY
 WILL NEED TO BE MITIGATED.
 THE CORRECT BASE PLAN TO USE FOR LANDSCAPE AND SITE
 PLAN ARE FROM PERMITS 15060795 AND 15110106
 (LANDSCAPE). COORDINATE WITH RAY CARANCI, LANDSCAPE
 PLANNER FOR LANDSCAPE QUESTIONS. 561 822 1462
  
 PLEASE CLEAN UP THE PARKING NUMBERS AS THEY ARE
 INCORRECT AND PLEASE PROVIDE THE PARKING DATA ON THE
 PLANS
 PLEASE INCLUDE UPDATED PERVIOUS AND IMPERVIOUS DATA
  
 THE STREET VIEW FROM APRIL 2019 SHOWS A CONSTRUCTION OR
 STORAGE TRAILER IN THE REAR PARKING LOT, WHICH IS NOT
 PERMITTED. PLEASE VERIFY WITH TIME STAMPED IMAGES THAT
 THIS TRAILER IS NO LONGER ON SITE
  
 PLEASE INCLUDE THE DATA FOR THE TOTAL BUILDING SQUARE
 FOOTAGE (EXISTING THREE BUILDINGS, AND ADDITION)
  
 NEW FENCES REQUIRE A SEPARATE FENCE PERMIT, PLEASE MAKE
 A NOTE ON THE PLANS "THROUGH SEPARATE PERMIT" FOR ANY
 FENCE ADDITIONS OR REMOVE REFERENCE IF NO FENCE
 MODIFICATIONS ARE BEING DONE
  
 PLEASE SUBMIT A COMMENT RESPONSE MEMO WITH RESUBMITTAL
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  