Plan Review Details - Permit 19080080
Plan Review Stops For Permit 19080080
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-11-13 Cont ID  
Sent By shill Date 2019-11-13 Time 16:56 Rev Time 0.00
Received By shill Date 2019-11-13 Time 16:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-11-06 Cont ID  
Sent By shill Date 2019-11-06 Time 18:08 Rev Time 0.00
Received By shill Date 2019-11-06 Time 18:07 Sent To  
Notes
2019-11-06 18:09:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE THE PRIVATE PROVIDER AFFIDAVIT FOR THE
 REVISED PAGES, FAC61G20.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-09 Cont ID  
Sent By pvalenti Date 2019-10-09 Time 06:38 Rev Time 0.00
Received By pvalenti Date 2019-10-09 Time 06:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By pvalenti Date 2019-10-02 Time 07:07 Rev Time 0.00
Received By pvalenti Date 2019-10-02 Time 07:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-18 Cont ID  
Sent By pvalenti Date 2019-08-18 Time 13:51 Rev Time 0.00
Received By pvalenti Date 2019-08-18 Time 13:51 Sent To  
Notes
2019-08-18 13:53:16PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 APPROVED WITH PROVISO:
  
 PLEASE PROVIDE THE PRIVATE PROVIDER AFFIDAVIT OF
 APPROVAL FOR PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By jpearson Date 2019-10-02 Time 06:29 Rev Time 0.00
Received By jpearson Date 2019-10-02 Time 06:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-15 Cont ID  
Sent By jpearson Date 2019-08-15 Time 07:14 Rev Time 0.00
Received By jpearson Date 2019-08-15 Time 07:14 Sent To  
Notes
2019-08-15 07:14:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR THE SIGN TO BE REVIEWED,
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
 2. THIS SUBMISSION WAS FLAGGED AS REVIEWED BY PRIVATE
 PROVIDER, BUT THERE IS NO PAPERWORK FROM A PRIVATE
 COMPANY INCLUDED. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1, 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-11-13 Cont ID  
Sent By lmarchan Date 2019-11-13 Time 16:13 Rev Time 0.00
Received By lmarchan Date 2019-11-01 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-10 Cont ID  
Sent By lmarchan Date 2019-10-10 Time 14:33 Rev Time 0.00
Received By lmarchan Date 2019-10-08 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-07 Cont ID  
Sent By cpuell Date 2019-10-07 Time 14:16 Rev Time 0.00
Received By cpuell Date 2019-09-26 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-19 Cont ID  
Sent By lmarchan Date 2019-09-19 Time 10:59 Rev Time 0.00
Received By lmarchan Date 2019-08-14 Time 16:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-11-06 Cont ID  
Sent By shill Date 2019-11-06 Time 18:09 Rev Time 0.00
Received By shill Date 2019-11-06 Time 18:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-10-16 Cont ID  
Sent By shill Date 2019-10-16 Time 07:11 Rev Time 0.00
Received By shill Date 2019-10-16 Time 07:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By jpearson Date 2019-10-02 Time 06:29 Rev Time 0.00
Received By jpearson Date 2019-10-02 Time 06:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-15 Cont ID  
Sent By jpearson Date 2019-08-15 Time 07:15 Rev Time 0.00
Received By jpearson Date 2019-08-15 Time 07:15 Sent To  
Notes
2019-08-15 07:15:09THE DIGITAL SIGNATURES IN THIS SUBMISSION ARE GOOD, ANY
 NEW SUBMISSIONS WILL NEED TO BE CHECKED. WPB FBC 107.1

Review Stop Z ZONING
Rev No 4 Status P Date 2019-11-13 Cont ID  
Sent By elevesqu Date 2019-11-13 Time 13:58 Rev Time 0.00
Received By elevesqu Date 2019-11-13 Time 13:58 Sent To  
Notes
2019-11-13 13:58:23PROVISOS:
 FENCE REQUIRES SEPARATE PERMIT
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 3 Status F Date 2019-10-10 Cont ID  
Sent By elevesqu Date 2019-10-10 Time 14:31 Rev Time 0.00
Received By elevesqu Date 2019-10-10 Time 14:31 Sent To  
Notes
2019-10-10 14:31:14PLEASE ADDRESS ALL PREVIOUS ZONING COMMENTS FROM REVIEW
 STOP 1 AND 2
  
  
 PREVOIUS COMMENTS NOT ADDRESSED:
  
 PLAZA PLAN DOES NOT MATCH LATEST APPROVAL - STILL SHOWS
 THREE ROWS OF PAVERS, SHOWS HATCH STRIPING INSTEAD OF
 EXTENDED CURB, ETC.
  
 NEED DIMENSIONS OF CURVED PART OF SIGN - COUNTS TOWARDS
 TOTAL SIGNAGE WIDTH PERMITTED (400 LINEAR FEET PER
 STREET FRONTAGE, TOTAL OF 800 LINEAR FEET).
 PLEASE BREAK DOWN BY LINEAR FEET PER FACADE AND TOTAL
 (THE 37 3/4" SECTION WOULD NOT COUNT TOWARDS THE PER
 SIDE LINEAR FEET).
  
 PLEASE BREAK DOWN BY INDIVIDUAL SECTION TO SHOW SF PER
 SIDE, AND TOTAL SF
 FOR EXAMPLE, LEFT SIDE IS 10X20, PLUS 14X10'1", PLUS
 ... ETC.
  
 SIGN REGULATIONS FOR ELECTRONIC MONUMENT SIGN IS:
 DIMENSION REQUIREMENTS:
 I.MAXIMUM HEIGHT: 24 FEET
 II.MAXIMUM WIDTH: 40 FEET
 III.MAXIMUM SIZE PER FRONTAGE: 400 SF
  
 ON PAGE 3, THE DIMENSION OF THE SHORT SIDE OF THE ARC
 DOES NOT MATCH THE DIMENSION SHOWN ON PAGE 2. PLEASE
 CLARIFY
  
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 2 Status F Date 2019-10-03 Cont ID  
Sent By elevesqu Date 2019-10-03 Time 14:14 Rev Time 0.00
Received By elevesqu Date 2019-10-03 Time 14:14 Sent To  
Notes
2019-10-03 14:14:05PREVOIUS COMMENTS NOT ADDRESSED:
  
 PLAZA PLAN DOES NOT MATCH LATEST APPROVAL - STILL SHOWS
 THREE ROWS OF PAVERS, SHOWS HATCH STRIPING INSTEAD OF
 EXTENDED CURB, ETC.
  
 NEED DIMENSIONS OF CURVED PART OF SIGN - COUNTS TOWARDS
 TOTAL SIGNAGE WIDTH PERMITTED (400 LINEAR FEET PER
 STREET FRONTAGE, TOTAL OF 800 LINEAR FEET).
 PLEASE BREAK DOWN BY LINEAR FEET PER FACADE AND TOTAL
 (THE 37 3/4" SECTION WOULD NOT COUNT TOWARDS THE PER
 SIDE LINEAR FEET).
  
 PLEASE BREAK DOWN BY INDIVIDUAL SECTION TO SHOW SF PER
 SIDE, AND TOTAL SF
 FOR EXAMPLE, LEFT SIDE IS 10X20, PLUS 14X10'1", PLUS
 ... ETC.
  
 SIGN REGULATIONS FOR ELECTRONIC MONUMENT SIGN IS:
 DIMENSION REQUIREMENTS:
 I.MAXIMUM HEIGHT: 24 FEET
 II.MAXIMUM WIDTH: 40 FEET
 III.MAXIMUM SIZE PER FRONTAGE: 400 SF
  
 ON PAGE 3, THE DIMENSION OF THE SHORT SIDE OF THE ARC
 DOES NOT MATCH THE DIMENSION SHOWN ON PAGE 2. PLEASE
 CLARIFY
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-19 Cont ID  
Sent By aaponte Date 2019-09-19 Time 10:56 Rev Time 0.00
Received By elevesqu Date 2019-09-19 Time 10:43 Sent To  
Notes
2019-09-19 10:56:37PLAZA PLAN DOES NOT MATCH LATEST APPROVAL - STILL SHOWS
 THREE ROWS OF PAVERS, SHOWS HATCH STRIPING INSTEAD OF
 EXTENDED CURB, ETC.
  
 NEED DIMENSIONS OF CURVED PART OF SIGN - COUNTS TOWARDS
 TOTAL SIGNAGE WIDTH PERMITTED (400 LINEAR FEET PER
 STREET FRONTAGE, TOTAL OF 800 LINEAR FEET).
 PLEASE BREAK DOWN BY LINEAR FEET PER FACADE AND TOTAL
 (THE 37 3/4" SECTION WOULD NOT COUNT TOWARDS THE PER
 SIDE LINEAR FEET).
  
 PLEASE BREAK DOWN BY INDIVIDUAL SECTION TO SHOW SF PER
 SIDE, AND TOTAL SF
 FOR EXAMPLE, LEFT SIDE IS 10X20, PLUS 14X10'1", PLUS
 ... ETC.
  
 SIGN REGULATIONS FOR ELECTRONIC MONUMENT SIGN IS:
 DIMENSION REQUIREMENTS:
 I.MAXIMUM HEIGHT: 24 FEET
 II.MAXIMUM WIDTH: 40 FEET
 III.MAXIMUM SIZE PER FRONTAGE: 400 SF
  
 ON PAGE 3, THE DIMENSION OF THE SHORT SIDE OF THE ARC
 DOES NOT MATCH THE DIMENSION SHOWN ON PAGE 2. PLEASE
 CLARIFY
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]