Plan Review Details - Permit 19080055
Plan Review Stops For Permit 19080055
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By dbattles Date 2019-11-12 Time 09:58 Rev Time 0.00
Received By dbattles Date 2019-11-12 Time 09:58 Sent To  
Notes
2019-11-12 09:58:28PROVISO:
 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
2019-10-04 14:45:52BUILDING PLANS EXAMINER, PLEASE EVALUATE EXPIRED
 PERMITS AND COMMUNICATE EACH STATUS TO OWNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By dbattles Date 2019-09-09 Time 15:52 Rev Time 0.00
Received By dbattles Date 2019-09-09 Time 14:01 Sent To  
Notes
2019-09-09 15:54:22BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19080055
 REVIEWED: SEPTEMBER 9, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED]THE TWO SETS OF DRAWINGS
 PROVIDED DO NOT MATCH. ONE SET INCLUDES REVISIONS AND
 THE OTHER DOES NOT.
 ALSO, SHEET S4 IS MISSING FROM THE SET WITHOUT
 REVISIONS.
 I?M REVIEWING THE SET WITH REVISIONS.
  
 2) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502. UNALTERED PORTIONS OF
 THE EXISTING BUILDING OR BUILDING SUPPLY SYSTEM SHALL
 NOT BE REQUIRED TO COMPLY WITH THIS CODE.
 -PLEASE CHOOSE METHOD (R502.1.1, R502.1.2 OR
 R502.1.3)AND SUPPLY DOCUMENTAION TO COMPLY WITH THE
 METHOD CHOOSEN.
  
 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, MULL BAR AND DOORS W/SIDELITES IN ADDITION, OR
 INDICATE THAT YOU WOULD LIKE IT DEFERRED.
  
 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 TILE ROOFING AND ADHESIVE, OR INDICATE THAT YOU WOULD
 LIKE IT DEFERRED.
  
 5) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
 - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-12-03 Cont ID  
Sent By ppetty Date 2019-12-03 Time 11:00 Rev Time 0.00
Received By ppetty Date 2019-12-03 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-11-05 Cont ID  
Sent By ppetty Date 2019-11-05 Time 11:49 Rev Time 0.00
Received By ppetty Date 2019-11-05 Time 11:49 Sent To  
Notes
2019-11-05 11:49:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS #1 WIRE FEEDING A 200 AMP
 DISCONNECT AND PANEL. THIS WIRE IS NOT RATED FOR200
 AMPS. IN ADDITION, THE LOAD CALCULATION SHOWS A LOAD OF
 170 AMPS. THE #1 WIRE IS RATED FOR 130 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16); FBC RE E3603.1, E3705.1
 2. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING
 CONDUCTOR IN THE FEED FOR THE 200 AMP PANEL. THIS WIRE
 IS NOT SIZED PROPERLY, PROVIDE CORRECTION. NEC 250.122;
 FBC RE E3704.6, 3607.3.1
 3. OK
 4. RISER DIAGRAM DOES NOT SHOW THE WIRE SIZE TO THE 60
 AMP DISCONNECT. PROVIDE CORRECTION. NEC 215.5; FBC RE
 E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 5. RISER DIAGRAM INDICATES THE 60 AMP DISCONNECT WILL
 BE FED FROM THE DUAL LUGS IN THE METER CAN. HOWEVER,
 THE LOAD IS SHOWN AS PART OF THE MAIN. WHERE IS THIS
 PANEL FED FROM? PROVIDE CLARIFICAITONS AND CORRECTIONS.
 WPB FBC 107.2.1
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 7. THE MECHANICAL PLAN SHOWS THE NEW ROOM AS A DINING
 ROOM. IF SO, THE RECEPTACLE OUTLETS IN THIS ROOM ARE
 REQUIRED TO BE ON A SMALL APPLIANCE BRANCH CIRCUIT WITH
 A 20 AMP RATING AND WIRE SIZE. PROVIDE CORRECTION. NEC
 210.52(B)(2); FBC RE E3703.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-21 Cont ID  
Sent By jpearson Date 2019-08-21 Time 14:42 Rev Time 0.00
Received By jpearson Date 2019-08-21 Time 14:42 Sent To  
Notes
2019-08-21 13:59:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS #1 WIRE FEEDING A 200 AMP
 DISCONNECT AND PANEL. THIS WIRE IS NOT RATED FOR200
 AMPS. IN ADDITION, THE LOAD CALCULATION SHOWS A LOAD OF
 170 AMPS. THE #1 WIRE IS RATED FOR 130 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16); FBC RE E3603.1, E3705.1
 2. RISER DIAGRAM SHOWS A # 8 EQUIPMENT GROUNDING
 CONDUCTOR IN THE FEED FOR THE 200 AMP PANEL. THIS WIRE
 IS NOT SIZED PROPERLY, PROVIDE CORRECTION. NEC 250.122;
 FBC RE E3704.6, 3607.3.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. RISER DIAGRAM DOES NOT SHOW THE WIRE SIZE TO THE 60
 AMP DISCONNECT. PROVIDE CORRECTION. NEC 215.5; FBC RE
 E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 5. RISER DIAGRAM INDICATES THE 60 AMP DISCONNECT WILL
 BE FED FROM THE DUAL LUGS IN THE METER CAN. HOWEVER,
 THE LOAD IS SHOWN AS PART OF THE MAIN. WHERE IS THIS
 PANEL FED FROM? PROVIDE CLARIFICAITONS AND CORRECTIONS.
 WPB FBC 107.2.1
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 7. THE MECHANICAL PLAN SHOWS THE NEW ROOM AS A DINING
 ROOM. IF SO, THE RECEPTACLE OUTLETS IN THIS ROOM ARE
 REQUIRED TO BE ON A SMALL APPLIANCE BRANCH CIRCUIT WITH
 A 20 AMP RATING AND WIRE SIZE. PROVIDE CORRECTION. NEC
 210.52(B)(2); FBC RE E3703.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2019-12-12 Cont ID  
Sent By dbattles Date 2019-12-12 Time 09:58 Rev Time 0.00
Received By dbattles Date 2019-12-12 Time 09:58 Sent To  
Notes
2019-12-12 09:59:11OK-PLANS STAMPED
 MU-2019-038543-0000

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-03 Cont ID  
Sent By ppetty Date 2019-12-03 Time 11:01 Rev Time 0.00
Received By ppetty Date 2019-11-19 Time 14:15 Sent To  
Notes
2019-11-20 14:15:48RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-12 Cont ID  
Sent By dbattles Date 2019-11-12 Time 10:07 Rev Time 0.00
Received By dbattles Date 2019-10-21 Time 13:23 Sent To  
Notes
2019-10-22 13:23:09R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-09 Cont ID  
Sent By dbattles Date 2019-09-09 Time 15:52 Rev Time 0.00
Received By dbattles Date 2019-08-01 Time 14:41 Sent To  
Notes
2019-08-02 14:41:42R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-12-12 Cont ID  
Sent By dbattles Date 2019-12-12 Time 10:11 Rev Time 0.00
Received By dbattles Date 2019-12-12 Time 10:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By dbattles Date 2019-09-09 Time 15:35 Rev Time 0.00
Received By dbattles Date 2019-09-09 Time 15:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-08-23 Cont ID  
Sent By cmontell Date 2019-08-23 Time 13:39 Rev Time 0.00
Received By cmontell Date 2019-08-23 Time 13:39 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-11-12 Cont ID  
Sent By dbattles Date 2019-11-12 Time 10:00 Rev Time 0.00
Received By dbattles Date 2019-11-12 Time 10:00 Sent To  
Notes
2019-11-12 10:07:25PROVIDE PRODUCT APPROVAL FOR ROOF TILE ATTACHMENT.
 TILE AND SEAL APPROVED PER PRODUCT APPROVALS BELOW:
 NOA 18-0829.02 AND NOA 18-0502.03

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-09-09 Cont ID  
Sent By dbattles Date 2019-09-09 Time 15:35 Rev Time 0.00
Received By dbattles Date 2019-09-09 Time 15:35 Sent To  
Notes
2019-09-09 15:36:08SEE BUILDING COMMENT FOR ROOFING

Review Stop Z ZONING
Rev No 3 Status P Date 2019-11-21 Cont ID  
Sent By awooten Date 2019-11-21 Time   Rev Time 0.00
Received By awooten Date 2019-11-21 Time   Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-10-29 Cont ID  
Sent By awooten Date 2019-10-29 Time   Rev Time 0.00
Received By awooten Date 2019-10-29 Time   Sent To  
Notes
2019-10-29 09:11:36*************************ZONING REVIEW
 FAILED*********************
  
 PLEASE PROVIDE A COPY OF SURVEY OF PROPRETY.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]