| 2019-09-16 13:17:54 | 09/16/2019 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. THE SECOND REQUEST, THIS COPY FOR THE TIE-DOWN OF |
| | SIGNATURE OR SEAL IS NOT IN ACCORDANCE WITH FLORIDA |
| | ADMINISTRATIVE CODE PER 61G15-23.001, FLORIDA STATUTE |
| | 471. THE PROVIDED DOCUMENT FOR YOUR TIE-DOWN HAS SEAL |
| | AND SIGNATURE IS A COPY SIGNATURE AND NOT AN ORIGINAL |
| | WET STAMP. |
| | |
| | 2. THE METHOD OF REQUIRED PROTECTION FOR THE LP TANK |
| | AND APPURTENANCES PER NFPA 58 IS MISSING INFORMATION. |
| | THE DETAIL ONLY SHOWS A COVER AND MUST SUBMIT A BASE |
| | AND COVER FOR VEHICLE TRAFFIC PROTECTION AS IT IS BELOW |
| | GROUND IT SHALL BE CONSTRUCTED AND PROTECTED PER NFPA |
| | 58 SEC.3-2.2.7 (H). THE HOUSING FOR THE LID IS ALSO |
| | REQUIRED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP |
| | TANK TIE-DOWN METHOD AND IF YOU ARE USING FLAT STRAPS |
| | OR ISOLATION CABLES, IF ISOLATION CABLES, PLEASE |
| | CLARIFY HOW IS IT PROTECTED FOR THE LP TANK AND |
| | APPURTENANCES PER THE NFPA 58. WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. THE DOCUMENT SUBMITTED ARE NOT TO CODE COMPLIANCE |
| | AND CONTINUE TO HAVE NO SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES, AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. PLEASE MAKE AN APPOINTMENT TO DISCUSS THESE |
| | ITEMS THAT SHALL CONTAIN INFORMATION, IN THE FORM OF |
| | NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES PER THE WPB AMENDMENTS TO FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |