Plan Review Details - Permit 19071630
Plan Review Stops For Permit 19071630
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-19 Cont ID  
Sent By pvalenti Date 2019-08-19 Time 16:49 Rev Time 0.00
Received By pvalenti Date 2019-08-19 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-06 Cont ID  
Sent By pvalenti Date 2019-08-06 Time 15:38 Rev Time 0.00
Received By pvalenti Date 2019-08-06 Time 15:38 Sent To  
Notes
2019-08-06 16:01:32***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED.
  
  
 1. PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
 2. FBC B 2403.2 GLASS SUPPORTS. FBC B 2403.2. WHERE ONE
 OR MORE SIDES OF ANY PANE OF GLASS ARE NOT FIRMLY
 SUPPORTED, OR ARE SUBJECTED TO UNUSUAL LOAD CONDITIONS,
 DETAILED CONSTRUCTION DOCUMENTS, DETAILED SHOP DRAWINGS
 AND ANALYSIS OR TEST DATA ENSURING SAFE PERFORMANCE FOR
 THE SPECIFIC INSTALLATION SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-19 Cont ID  
Sent By pvalenti Date 2019-08-19 Time 16:49 Rev Time 0.00
Received By pvalenti Date 2019-08-16 Time 16:03 Sent To  
Notes
2019-08-19 16:04:04RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-06 Cont ID  
Sent By pvalenti Date 2019-08-06 Time 16:01 Rev Time 0.00
Received By pvalenti Date 2019-07-31 Time 14:07 Sent To  
Notes
2019-08-01 14:07:53ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-05 Cont ID  
Sent By lcrespo Date 2019-08-05 Time 15:44 Rev Time 0.00
Received By lcrespo Date 2019-08-05 Time 15:44 Sent To  
Notes
2019-08-05 15:44:3308/05/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  