Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By gjohnson Date 2019-08-27 Time 12:02 Rev Time 0.00
Received By jesmith Date 2019-08-27 Time 12:02 Sent To  
Notes
2019-08-27 12:02:31PLUMBING COMMEMTS: APPROVED W/PROVISO
 ON P4.0, SANITARY RISER, CONNECT THE FLOOR DRAIN TO THE
 WET VENT AHEAD OF THE WATER CLOSET (SEE RED LINED
 COMMENT AND MARK UPS ON P4.0) AS SHOWN ON P1.0 PLAN
 VIEW.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 09:52 Rev Time 0.00
Received By gjohnson Date 2019-08-19 Time 08:23 Sent To  
Notes
2019-08-19 09:52:511ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P4.0 THE SANITARY ISOMETRIC IS TO CONGESTED TO
 DETERMINE CODE COMPLIANCE PLEASE CORRECT THE FOLLOWING:
 ENLARGE DRAWING, THE BRANCH DRAIN FOR THE TOILET FLOOR
 DRAIN AND LAVATORY CONNECT TO MULTIPLE POINTS ALONG THE
 BUILDING DRAIN AND TO EACH OTHER THEY SHALL ONLY
 CONNECT ONCE. THE DIRECTION OF FLOW ON THE TOILET
 BRANCH IS OPPOSITE OF THE OTHER PIPING. PER WPB AMEND
 TO FBC 107.2.1
  
 2. THE WATER FOUNTAIN SHALL NOT CONNECT TO THE WET VENT
 OF THE BATHROOM GROUP. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By jesmith Date 2019-08-27 Time 12:03 Rev Time 0.00
Received By jesmith Date 2019-08-27 Time 12:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 09:54 Rev Time 0.00
Received By gjohnson Date 2019-08-19 Time 09:54 Sent To  
Notes
2019-08-19 09:55:40ANY REVISED SHEETS SHALL BE DIGITALLY SIGNED AND
 SEALED.