Plan Review Details - Permit 19071480
Plan Review Stops For Permit 19071480
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-26 Cont ID  
Sent By jbrooks Date 2019-09-26 Time 08:10 Rev Time 0.00
Received By jbrooks Date 2019-09-26 Time 08:10 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By shill Date 2019-08-12 Time 14:52 Rev Time 0.00
Received By shill Date 2019-08-12 Time 14:52 Sent To  
Notes
2019-08-12 14:52:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FS471, DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. THE PLANS PROVIDED ARE PRINTOUTS OF
 DIGITALLY SIGNED PLANS; ORIGINAL "WET" SIGNATURE AND
 SEAL REQUIRED AS THIS IS A PAPER SUBMITTAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-26 Cont ID  
Sent By jleahy Date 2019-09-26 Time 16:44 Rev Time 0.00
Received By jleahy Date 2019-09-26 Time 16:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By fgiaquin Date 2019-08-26 Time 06:40 Rev Time 0.00
Received By fgiaquin Date 2019-08-26 Time 06:39 Sent To I
Notes
2019-08-26 06:40:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE
 AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 2. VALUE LOW FOR AMOUNT OF WORK SHOWN.WE NEED AN
 ACCURATE VALUE FOR THE WORK BEING PERFORMED, TO INCLUDE
 ALL MATERIALS AND LABOR. THIS SHOULD EVEN INCLUDE ITEMS
 THAT ARE CUSTOMER SUPPLIED. PLEASE RECALCULATE YOUR
 VALUE AND PROVIDE AN ACCURATE ESTIMATE. THE FEE FOR A
 PERMIT IS BASED ON A PERCENTAGE OF THE JOB VALUE, SO AN
 INCREASE IN VALUE TYPICALLY MAKES A SMALL DIFFERENCE IN
 THE PERMIT FEES. HOWEVER, CONFIRMING AN ACCURATE VALUE
 FOR THE PROPOSED WORK IS INCLUDED IN THE JOB
 DESCRIPTION FOR A PLAN REVIEWER. AS SUCH, YOUR PERMIT
 CANNOT BE APPROVED UNTIL THIS ISSUE IS RESOLVED.
  
 IN THE FUTURE YOUR PERMIT VALUE SHOULD INCLUDE ALL
 MATERIALS SUPPLIED BY YOU THE CONTRACTOR AND ANY
 CUSTOMER RELATED ITEMS AND LABOR TO INSTALL THE WORK
 PER FBC 109.3. BELOW YOU WILL FIND THE FBC SECTION FOR
 VALUATION OF THE WORK FOR A PERMIT.
  
 CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-26 Cont ID  
Sent By jbrooks Date 2019-09-26 Time 16:44 Rev Time  
Received By jleahy Date 2019-09-10 Time 13:53 Sent To  
Notes
2019-09-12 13:53:48RESUB ROUTED TO ZONING INBOX
 **TRAVELLING TOGETHER 19071477, 19071478, 19071480**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-26 Cont ID  
Sent By fgiaquin Date 2019-08-26 Time 06:40 Rev Time 0.00
Received By fgiaquin Date 2019-07-29 Time 13:02 Sent To  
Notes
2019-08-12 14:52:53TO ELEC
2019-07-31 13:03:02ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-13 Cont ID  
Sent By rfalcone Date 2019-09-13 Time 10:31 Rev Time 0.00
Received By rfalcone Date 2019-09-13 Time 10:31 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-06 Cont ID  
Sent By ajones Date 2019-08-06 Time 12:13 Rev Time 0.00
Received By ajones Date 2019-08-06 Time 12:13 Sent To B
Notes
***NONE***