| 2019-08-26 06:38:30 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT |
| | CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA |
| | STATUTES. PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE |
| | AND SEALS. |
| | |
| | PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE |
| | LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S |
| | SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED |
| | ON PHYSICALLY TRANSMITTED DOCUMENTS. |
| | CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL |
| | SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON |
| | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| | SIGNATURE SHALL NOT BE USED. |
| | |
| | AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED |
| | DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A |
| | WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART |
| | OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO |
| | PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT |
| | THE SIGNATURE IS NOT MADE ILLEGIBLE. |
| | CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN |
| | USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN |
| | EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE |
| | SIGNATURE ILLEGIBLE. |
| | |
| | 2. VALUE LOW FOR AMOUNT OF WORK SHOWN.WE NEED AN |
| | ACCURATE VALUE FOR THE WORK BEING PERFORMED, TO INCLUDE |
| | ALL MATERIALS AND LABOR. THIS SHOULD EVEN INCLUDE ITEMS |
| | THAT ARE CUSTOMER SUPPLIED. PLEASE RECALCULATE YOUR |
| | VALUE AND PROVIDE AN ACCURATE ESTIMATE. THE FEE FOR A |
| | PERMIT IS BASED ON A PERCENTAGE OF THE JOB VALUE, SO AN |
| | INCREASE IN VALUE TYPICALLY MAKES A SMALL DIFFERENCE IN |
| | THE PERMIT FEES. HOWEVER, CONFIRMING AN ACCURATE VALUE |
| | FOR THE PROPOSED WORK IS INCLUDED IN THE JOB |
| | DESCRIPTION FOR A PLAN REVIEWER. AS SUCH, YOUR PERMIT |
| | CANNOT BE APPROVED UNTIL THIS ISSUE IS RESOLVED. |
| | |
| | IN THE FUTURE YOUR PERMIT VALUE SHOULD INCLUDE ALL |
| | MATERIALS SUPPLIED BY YOU THE CONTRACTOR AND ANY |
| | CUSTOMER RELATED ITEMS AND LABOR TO INSTALL THE WORK |
| | PER FBC 109.3. BELOW YOU WILL FIND THE FBC SECTION FOR |
| | VALUATION OF THE WORK FOR A PERMIT. |
| | |
| | CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT |
| | VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |