Plan Review Details - Permit 19071321
Plan Review Stops For Permit 19071321
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-08 Cont ID  
Sent By dbattles Date 2019-10-08 Time 15:57 Rev Time 0.00
Received By dbattles Date 2019-10-08 Time 15:57 Sent To  
Notes
2019-10-08 15:59:05PROVISO:
 ONCE CONTRACTOR DETERMINED, THE VALUE SHOULD BE
 ADJUSTED PER THE CONTRACT VALUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By cthroop Date 2019-09-24 Time 13:06 Rev Time 0.00
Received By cthroop Date 2019-09-24 Time 10:05 Sent To  
Notes
2019-09-24 13:13:51BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1) 109.3 FBC[AMENDED] PROJECT VALUE APPEARS LOW. (NO
 PROPOSAL PROVIDED FOR REVIEW)
 PLEASE PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO SHOW
 WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT
 APPLICATION, OR PROVIDE ESTIMATE TO SHOW ANTICIPATED
 COSTS.
  
 2) CORRECTED
  
 3) CORRECTED
  
 NEW COMMENT
  
 RESPONSE TO PLUMBING COMMENT # 4 INDICATES PERMIT TYPE
 WILL CHANGE TO OWNER/BUILDER. PLEASE CLARIFY.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-07 Cont ID  
Sent By dbattles Date 2019-08-07 Time 14:59 Rev Time 0.00
Received By dbattles Date 2019-08-07 Time 14:59 Sent To  
Notes
2019-08-07 15:00:15BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19071321
 REVIEWED: AUGUST 7, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[RE] = FBC ENERGY CONSERVATION
  
 1) 109.3 FBC[AMENDED] PROJECT VALUE APPEARS LOW.
 PLEASE PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO SHOW
 WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT
 APPLICATION, OR PROVIDE ESTIMATE TO SHOW ANTICIPATED
 COSTS.
  
 2) 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET
 REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 -PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLISTS AND
 EPL CARD.
 2A) HOW IS CEILING INSULATED? PLEASE INCLUDE IN THE
 ENERGY CALCULATIONS.
  
 3) WIND DESIGN CRITERIA.
 RISK CATEGORY = ___(II)
 EXPOSURE CATEGORY = ___(B,C OR D)
 BUILDING CLASSIFICATION = __________(ENCLOSED)
 MEAN BLDG. HGT. = ___FT. ___IN.(TOP OF ROOF DECK)
 WIND SPEED V ULT = _____(170)
 WIND SPEED V ASD = _____(132)
 DESIGN PRESSURE FOR EACH OPENING = +___ & -___
 ZONE OF OPENING = (4 OR 5?)
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-07 Cont ID  
Sent By ppetty Date 2019-10-07 Time 12:52 Rev Time 0.00
Received By ppetty Date 2019-10-07 Time 12:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-09-18 Cont ID  
Sent By ppetty Date 2019-09-18 Time 12:53 Rev Time 0.00
Received By ppetty Date 2019-09-18 Time 12:53 Sent To  
Notes
2019-09-18 12:53:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE FOR MAIN
 HOUSE. PROVIDE DETAILS OF FEED TO PANEL A. NEC 215.5;
 WPB FBC 107.2.1
 3. OK
 4. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 5. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 6. 240.24-E PANEL IN BATHROOM
 7. PROVIDE ACCURATE LOAD CALCULATION FOR MAIN SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By jpearson Date 2019-08-13 Time 11:17 Rev Time 0.00
Received By jpearson Date 2019-08-13 Time 09:25 Sent To  
Notes
2019-08-13 10:28:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IT APPEARS THAT A SERVICE IS INTENDED FOR THIS
 STRUCTURE. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB
 FBC 107.2.1; NEC 230.2; FBC RE E3601.2
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE FOR MAIN
 HOUSE. PROVIDE DETAILS OF FEED TO PANEL A. NEC 215.5;
 WPB FBC 107.2.1
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 4. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 5. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 7. PROVIDE ACCURATE LOAD CALCULATION FOR MAIN SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-09 Cont ID  
Sent By cpuell Date 2019-10-09 Time 11:36 Rev Time 0.00
Received By cpuell Date 2019-10-03 Time 11:42 Sent To  
Notes
2019-10-04 11:42:31R24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-27 Cont ID  
Sent By cpuell Date 2019-09-27 Time 10:47 Rev Time 0.00
Received By cpuell Date 2019-09-11 Time 13:50 Sent To  
Notes
2019-09-12 13:50:19R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-19 Cont ID  
Sent By hmoser Date 2019-08-19 Time 14:33 Rev Time 0.00
Received By hmoser Date 2019-07-25 Time 16:33 Sent To  
Notes
2019-07-26 16:35:17R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-10-08 Cont ID  
Sent By dbattles Date 2019-10-08 Time 15:59 Rev Time 0.00
Received By dbattles Date 2019-10-08 Time 15:59 Sent To  
Notes
2019-10-08 16:00:42OK-PLANS STAMPED
 MU -2019-027170-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-09-24 Cont ID  
Sent By cthroop Date 2019-09-24 Time 13:29 Rev Time 0.00
Received By cthroop Date 2019-09-24 Time 13:29 Sent To  
Notes
2019-09-24 13:31:27PLANS ARE STAMPED WITH IMPACT FEE STAMP
 #MU-2019-027170-0000. PROVIDE RECIEPT FROM PALM BEACH
 COUNTY IN THE AMOUNT OF $180.65. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-08-07 Cont ID  
Sent By dbattles Date 2019-08-07 Time 15:01 Rev Time 0.00
Received By dbattles Date 2019-08-07 Time 15:01 Sent To  
Notes
2019-08-07 15:01:41109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By hmoser Date 2019-09-16 Time 11:35 Rev Time 0.00
Received By hmoser Date 2019-09-16 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By hmoser Date 2019-08-19 Time 14:33 Rev Time 0.00
Received By hmoser Date 2019-08-19 Time 14:04 Sent To I
Notes
2019-08-19 14:33:13PLAN DENIED
 1) REFER TO SECTION R403.7 HEATING AND COOLING
 EQUIPMENT SIZING.
 ENERGY CALCULATIONS REQUIRED 2017 FLORIDA ENERGY CODE
 2) PROVIDE EQUIPMENT SCHEDULE ON THE PLAN. SECTION 107
 FBC 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By jesmith Date 2019-09-24 Time 11:12 Rev Time 0.00
Received By jesmith Date 2019-09-24 Time 09:17 Sent To  
Notes
2019-09-24 11:03:02PLUMBING COMMENTS: APPROVED W/PROVISO
 SEE RED LINED COMMENTS AND DRAWING CONFIGURATIONS ON
 PLAN SHEET P101

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-15 Cont ID  
Sent By lcrespo Date 2019-08-15 Time 15:26 Rev Time 0.00
Received By lcrespo Date 2019-08-15 Time 07:23 Sent To  
Notes
2019-08-15 15:24:0308/14/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CLEAN OUT AT THE END OF THE SYSTEM NEEDS TO BE
 IN THE OTHER SIDE OF BUILDING AS A CLEAN-OUT REQUIRED
 AT THE BUILDING JUNCTION PER 2017 FBC RES. SEC.
 3005.2.3 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
  
 THE JUNCTION OF THE BUILDING DRAIN AND THE BUILDING
 SEWER SHALL BE SERVED BY A CLEANOUT THAT IS LOCATED AT
 THE JUNCTION OR WITHIN 10 FEET (3048 MM) DEVELOPED
 LENGTH OF PIPING UPSTREAM OF THE JUNCTION. FOR THE
 REQUIREMENTS OF THIS SECTION, REMOVAL OF A WATER CLOSET
 SHALL NOT BE REQUIRED TO PROVIDE CLEANOUT ACCESS.
  
 2. IF THE SHOWER PAN IS NOT RECEDED AND NOT IN A
 CONTINUOUS POOR IT SHALL COMPLY WITH REQUIRE LINING PER
 2017 FBC RES. SEC. 2709.2.
  
 3. CITY OF WEST PALM BEACH ORD 2853-95 REQUIRES A
 BACKFLOW FOR A MULTI-DWELLING, BY A LICENSED CONTRACTOR
 WITH PERMIT APPLICATION INSPECTION AND CERTIFICATION
 FROM UTILITIES DEPARTMENT.
  
 4. THERE IS A VALUE LISTED ON THE APPLICATION AND THE
 OVERALL VALUE IS LOW. WPB AMENDMENTS TO THE FBC 109.3
 BUILDING PERMITS VALUATIONS. IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-10-09 Cont ID  
Sent By llouie Date 2019-10-09 Time   Rev Time 0.00
Received By llouie Date 2019-10-09 Time   Sent To  
Notes
2019-10-09 09:21:30NO KITCHEN FACILITIES PERMITTED, AS AN ACCESSORY
 DWELLING UNIT IS PROHIBITED IN THE SF7 ZONING DISTRICT.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By llouie Date 2019-09-26 Time   Rev Time 0.00
Received By llouie Date 2019-09-26 Time   Sent To  
Notes
2019-09-27 08:25:25NO KITCHEN FACILITIES PERMITTED, AS AN ACCESSORY
 DWELLING UNIT IS PROHIBITED IN THE SF7 ZONING DISTRICT.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-09 Cont ID  
Sent By llouie Date 2019-08-09 Time   Rev Time  
Received By llouie Date 2019-08-09 Time   Sent To  
Notes
2019-08-09 09:59:26** FAILED **
  
 1.) AN ACCESSORY DWELLING UNIT IS NOT PERMITTED IN THE
 SF7 ZONING DISTRICT.
  
  
 NOTES:
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  