Plan Review Details - Permit 19071238
Plan Review Stops For Permit 19071238
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By rmcdouga Date 2019-09-09 Time 17:05 Rev Time 0.00
Received By rmcdouga Date 2019-09-09 Time 17:05 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-13 Cont ID  
Sent By rmcdouga Date 2019-08-13 Time 10:15 Rev Time 0.00
Received By rmcdouga Date 2019-08-13 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By rfalcone Date 2019-09-10 Time 13:42 Rev Time 0.00
Received By jleahy Date 2019-09-09 Time 16:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-08-16 Cont ID  
Sent By jleahy Date 2019-08-16 Time 08:01 Rev Time 0.00
Received By jleahy Date 2019-08-16 Time 08:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-09 Cont ID  
Sent By rmcdouga Date 2019-09-09 Time 17:05 Rev Time 0.00
Received By rmcdouga Date 2019-08-26 Time 12:31 Sent To  
Notes
2019-08-26 12:32:02RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-16 Cont ID  
Sent By jleahy Date 2019-08-16 Time 08:01 Rev Time 0.00
Received By jleahy Date 2019-07-24 Time 13:11 Sent To  
Notes
2019-07-25 13:11:51ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-09 Cont ID  
Sent By tklarge Date 2019-09-09 Time 12:36 Rev Time 0.00
Received By tklarge Date 2019-09-09 Time 12:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By tklarge Date 2019-08-05 Time 14:57 Rev Time 0.00
Received By tklarge Date 2019-08-05 Time 14:31 Sent To  
Notes
2019-08-05 14:56:581) SHOW THE POOL PIPING LAYOUT ON THE PLANS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) THE SPECIFICATION ON THE PLAN FOR THE AQUASTAR
 CHANNEL DRAIN IS BLURRED AND BARELY LEGIBLE. SUBMIT A
 CLEAR AND LEGIBLE DETAIL. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) SUBMIT AN EXPANDED AND LEGIBLE PUMP CURVE FOR THE
 JET PUMP FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE PLANS REFER TO THE 2006 EDITION OF APSP - 7. THE
 2013 EDITION OF APSP 7 HAS BEEN ADOPTED PER THE 2017
 FBC-BUILDING.
 5) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING
 SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER,
 FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT
 THE PUMP.
 6) IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1
 7) A BACKFLOW IS REQUIRED ON THE AUTOFILL PER 2017
 FBC-PLUMBING SEC.608.1.
 8) A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL BE
 REQUIRED AT THE WATER METER PER THE CITY OF WEST PALM
 CROSS CONNECTION CONTROL MANUAL.
 9) THE PLANS SHOW DUAL SUCTION OUTLETS ON THE SWIMMING
 POOL. DUAL OUTLETS SHALL BE SEPARATED BY A MINIMUM OF 3
 FEET PER APSP 7-2013 SEC.5.3.1.
 10) THE FLOW RATE FOR THE RECIRCULATION PUMP LISTED IN
 THE BOX UNDER "ANSI-7/15" AT THE LISTED TDH DOES NOT
 CORRELATE WITH PUMP CURVE FOR THE FLOW RATE AND TDH
 SHOWN ON THE CURVE. CLARIFY.
 11) THE POOL HEATER SHALL HAVE A MIMIMUM THERMAL
 EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC.
 R403.10.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By rfalcone Date 2019-08-27 Time   Rev Time 0.00
Received By rfalcone Date 2019-09-10 Time 13:42 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-08-01 Cont ID  
Sent By ajones Date 2019-08-01 Time 10:15 Rev Time 0.00
Received By ajones Date 2019-08-01 Time 10:15 Sent To  
Notes
2019-08-01 10:17:018/1/19- FAILED. DOES THE SURVEY SHOW THE EXISTING POOL
 AND DECK OR THE PROPOSED NEW POOL AND DECK?
  
 ANGELLA VANN
 561-822-1441
 [email protected]