Plan Review Details - Permit 19071219
Plan Review Stops For Permit 19071219
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-08-13 Cont ID  
Sent By rmcdouga Date 2019-08-13 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2019-08-13 Time 08:07 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-25 Cont ID  
Sent By jleahy Date 2019-09-25 Time 16:10 Rev Time 0.00
Received By jleahy Date 2019-09-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-01 Cont ID  
Sent By fgiaquin Date 2019-08-01 Time 07:04 Rev Time 0.00
Received By fgiaquin Date 2019-08-01 Time 06:21 Sent To B
Notes
2019-08-01 07:04:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. $5000 VALUE FOR AMOUNT OF WORK SHOWN IS NOT
 POSSIBLE. RAISE VALUE OR VALUE WILL BE SET BY BUILDING
 OFFICIAL. VALUE TO INCLUDE ALL MATERIALS AND LABOR
 (INCLUDE GENERATOR) PER
  
 FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2. PROVIDE CUT SHEETS OF ALL EQUIPMENT FOR PRODUCT
 APPROVAL TO INCLUDE GENERATOR. FBC 107.2.1, NEC 90.7,
 110.2, 110.3B
  
 3. ONE-LINE DIAGRAM SHOWS 3-3/0 AND 1- #4 EQUIPMENT
 GROUND FROM METER-CAN TO SERVICE DISCONNECT, EQUIPMENT
 GROUND FROM METER-CAN TO SERVICE DISCONNECT IS NOT
 PERMITTED. EQUIPMENT GROUND ORIGINATES AT SERVICE
 DISCONNECTING MEANS. NEC 250.130A
  
 4. GROUNDING ELECTRODE SYSTEM IS SHOWN MAKING ITS
 ATTACHMENT TO THE GROUNDED CONDUCTOR (NEUTRAL) IN THE
 ATS WHICH IS DOWN STREAM FROM BOTH THE METER-CAN AND
 SERVICE DISCONNECTING MEANS, ATTACHMENT OF GROUNDING
 ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR IS NOT
 PERMITTED AFTER THE SERVICE DISCONNECTING MEANS.
 PROVIDE CORRECTION. NEC 250.24A1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-31 Cont ID  
Sent By cpuell Date 2019-08-13 Time 11:29 Rev Time 0.00
Received By pleduc Date 2019-07-31 Time 10:52 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-25 Cont ID  
Sent By jleahy Date 2019-09-25 Time 16:10 Rev Time 0.00
Received By jleahy Date 2019-09-17 Time 11:31 Sent To  
Notes
2019-09-18 11:31:43RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-13 Cont ID  
Sent By cpuell Date 2019-08-13 Time 11:29 Rev Time 0.00
Received By cpuell Date 2019-07-24 Time 13:10 Sent To FIRE
Notes
2019-07-25 13:10:35ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-18 Cont ID  
Sent By lcrespo Date 2019-09-18 Time 14:49 Rev Time 0.00
Received By lcrespo Date 2019-09-18 Time 14:49 Sent To  
Notes
2019-09-18 14:50:1209/18/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-02 Cont ID  
Sent By lcrespo Date 2019-08-02 Time 06:46 Rev Time 0.00
Received By lcrespo Date 2019-08-02 Time 06:46 Sent To  
Notes
2019-08-02 06:56:5008/02/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE, PROVIDE UL 142 RATING CERTIFICATE FOR DIESEL
 TANK, WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. PLEASE PROVIDE MANUFACTURES SPECIFICATION FOR DIESEL
 TANK, WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-08-13 Cont ID  
Sent By eschneid Date 2019-08-13 Time 11:10 Rev Time 0.25
Received By eschneid Date 2019-08-13 Time 11:06 Sent To PC
Notes
***NONE***