| 2019-08-23 18:36:13 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1-BASED ON PLANS SUBMITTED THE SCOPE OF WORK IS NOT A |
| | LEVEL 1 ALTERATION. THIS IS A CHANGE OF OCCUPANCY (SEC. |
| | 506 FBC-EXISTING BUILDING) AND ALTERATION LEVEL 2 (SEC. |
| | 506 FBC-EXISTING BUILDING). PLANS SHOW EXISTING |
| | CLASSROOMS AND OFFICE SPACES TO BE CONVERTED TO A |
| | DIFFERENT USE. REVISE CODE INFORMATION ON SHEET A0.0. |
| | |
| | 2- ARCHITECT NEEDS TO SPECIFY THE OCCUPANCY GROUP OF |
| | THE BUILDING AND CLASSIFY THE OCCUPANCY OF ALL THE |
| | PROPOSED SPACES AS REQUIRED BY SEC. 302.1 FBC-BUILDING. |
| | SPECIFY THE USE, NUMBER AND AGES OF CHILDREN IN THE |
| | TODDLER AREA AND CHECK IN AREA. WHO USES THE CHECK IN |
| | KIOSKS. |
| | |
| | 3- ARCHITECT TO PROVIDE ALL THE MINIMUM PLAN REVIEW |
| | CRITERIA AS REQUIRED BY SEC. 107.3.5 CITY AMENDMENTS. |
| | SPECIFY TYPE OF CONSTRUCTION, RISK CATEGORY, |
| | SPRINKLERED OR NON-SPRINKLERED BUILDING, OCCUPANCY |
| | GROUP, |
| | |
| | 4- THERE ARE SEVERAL BUILDINGS ON THIS PROPERTY. |
| | PROVIDE SITE PLAN/PLOT PLAN SHOWING THE BUILDING AND |
| | AREA OF WORK. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- PROVIDE LIFE-SAFETY PLANS SHOWING OCCUPANT LOAD |
| | (SEC. 1004.1.1 FBC-BUILDING), ALL EXIT SIGNS SEC. |
| | 1013.1 FBC-BUILDING. |
| | |
| | 6- EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| | ADJOINING OR INTERVENING ROOMS OR AREAS. SEC. 1016.2 |
| | FBC-BUILDING. SEE NEW DOOR #100. REVISE OR SHOW HOW IT |
| | WILL BE ALLOWED TO PASS THRU THE DAY CARE AREA. |
| | NOTE: COORDINATE WITH TOTAL OCCUPANT LOAD REQUESTED ON |
| | ITEM #5 ABOVE IF DETERMINED THAT PASSING THRU THE NEW |
| | DAY CARE AREA FOR TODDLERS MAY BE ALLOWED. |
| | |
| | 7- PLANS SHOW A 2 HOUR FIRE RATED CEILING SEPARATION |
| | ASSEMBLY UL DES U438 FOR NEW STORAGE ROOM. THIS NEW |
| | STORAGE ROOM IS LOCATED IN THE EXISTING SHAFT. THE |
| | SPECIFIED CEILING ASSEMBLY IS A WALL ASSEMBLY NOT A |
| | CEILING ASSEMBLY. NEED TO SPECIFY AN APPROVED |
| | HORIZONTAL ASSEMBLY ASSEMBLY COMPLYING WITH SEC. |
| | 711.2.2 FBC AS REQUIRED BY SEC. 713.5 FBC. |
| | |
| | 8- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR NEW |
| | STORAGE FLOOR FRAMING. SPECIFY ALL STRUCTURAL |
| | FASTENERS. SEC. 1604.1 FBC. |
| | |
| | 9- PROVIDE DETAILS AND SPECIFICATIONS FOR ALL BUILT |
| | IN-ELEMENTS SHOWING COMPLIANCE WITH SEC. 904 FBC |
| | ACCESSIBILITY AS REQUIRED BY SEC. 227 |
| | FBC-ACCESSIBILITY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |