Plan Review Details - Permit 19071173
Plan Review Stops For Permit 19071173
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2019-10-30 Cont ID  
Sent By jgomez Date 2019-10-30 Time 13:44 Rev Time 0.00
Received By jgomez Date 2019-10-30 Time 13:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-08-27 Cont ID  
Sent By jgomez Date 2019-08-27 Time 14:51 Rev Time 0.00
Received By jgomez Date 2019-08-26 Time 18:02 Sent To  
Notes
2019-08-27 14:52:08FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-30 Cont ID  
Sent By jgomez Date 2019-10-30 Time 17:10 Rev Time 0.00
Received By jgomez Date 2019-10-30 Time 08:40 Sent To  
Notes
2019-10-30 17:11:14PROVISO:
 ARCHITECT SPECIFIED TYPE IIA CONSTRUCTION. STRUCTURAL
 COLUMN BY THE NEW SECURITY AREA NEEDS 1 HOUR FIRE
 PROTECTION. TABLE 601 FBC-BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-27 Cont ID  
Sent By pleduc Date 2019-08-27 Time 11:08 Rev Time 0.00
Received By jgomez Date 2019-08-23 Time 18:35 Sent To P
Notes
2019-08-23 18:36:13BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-BASED ON PLANS SUBMITTED THE SCOPE OF WORK IS NOT A
 LEVEL 1 ALTERATION. THIS IS A CHANGE OF OCCUPANCY (SEC.
 506 FBC-EXISTING BUILDING) AND ALTERATION LEVEL 2 (SEC.
 506 FBC-EXISTING BUILDING). PLANS SHOW EXISTING
 CLASSROOMS AND OFFICE SPACES TO BE CONVERTED TO A
 DIFFERENT USE. REVISE CODE INFORMATION ON SHEET A0.0.
  
 2- ARCHITECT NEEDS TO SPECIFY THE OCCUPANCY GROUP OF
 THE BUILDING AND CLASSIFY THE OCCUPANCY OF ALL THE
 PROPOSED SPACES AS REQUIRED BY SEC. 302.1 FBC-BUILDING.
 SPECIFY THE USE, NUMBER AND AGES OF CHILDREN IN THE
 TODDLER AREA AND CHECK IN AREA. WHO USES THE CHECK IN
 KIOSKS.
  
 3- ARCHITECT TO PROVIDE ALL THE MINIMUM PLAN REVIEW
 CRITERIA AS REQUIRED BY SEC. 107.3.5 CITY AMENDMENTS.
 SPECIFY TYPE OF CONSTRUCTION, RISK CATEGORY,
 SPRINKLERED OR NON-SPRINKLERED BUILDING, OCCUPANCY
 GROUP,
  
 4- THERE ARE SEVERAL BUILDINGS ON THIS PROPERTY.
 PROVIDE SITE PLAN/PLOT PLAN SHOWING THE BUILDING AND
 AREA OF WORK. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- PROVIDE LIFE-SAFETY PLANS SHOWING OCCUPANT LOAD
 (SEC. 1004.1.1 FBC-BUILDING), ALL EXIT SIGNS SEC.
 1013.1 FBC-BUILDING.
  
 6- EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS. SEC. 1016.2
 FBC-BUILDING. SEE NEW DOOR #100. REVISE OR SHOW HOW IT
 WILL BE ALLOWED TO PASS THRU THE DAY CARE AREA.
 NOTE: COORDINATE WITH TOTAL OCCUPANT LOAD REQUESTED ON
 ITEM #5 ABOVE IF DETERMINED THAT PASSING THRU THE NEW
 DAY CARE AREA FOR TODDLERS MAY BE ALLOWED.
  
 7- PLANS SHOW A 2 HOUR FIRE RATED CEILING SEPARATION
 ASSEMBLY UL DES U438 FOR NEW STORAGE ROOM. THIS NEW
 STORAGE ROOM IS LOCATED IN THE EXISTING SHAFT. THE
 SPECIFIED CEILING ASSEMBLY IS A WALL ASSEMBLY NOT A
 CEILING ASSEMBLY. NEED TO SPECIFY AN APPROVED
 HORIZONTAL ASSEMBLY ASSEMBLY COMPLYING WITH SEC.
 711.2.2 FBC AS REQUIRED BY SEC. 713.5 FBC.
  
 8- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR NEW
 STORAGE FLOOR FRAMING. SPECIFY ALL STRUCTURAL
 FASTENERS. SEC. 1604.1 FBC.
  
 9- PROVIDE DETAILS AND SPECIFICATIONS FOR ALL BUILT
 IN-ELEMENTS SHOWING COMPLIANCE WITH SEC. 904 FBC
 ACCESSIBILITY AS REQUIRED BY SEC. 227
 FBC-ACCESSIBILITY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-04 Cont ID  
Sent By jpearson Date 2019-11-04 Time 11:24 Rev Time 0.00
Received By jpearson Date 2019-11-04 Time 11:24 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-14 Cont ID  
Sent By jpearson Date 2019-08-14 Time 10:43 Rev Time 0.00
Received By jpearson Date 2019-08-14 Time 10:43 Sent To  
Notes
2019-08-14 10:43:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 4. PROVIDE TAMPER RESISTANT RECEPTACLES FOR ANY CHILD
 CARE AREAS. NEC 406.12(C)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-21 Cont ID  
Sent By pleduc Date 2019-10-21 Time   Rev Time 0.00
Received By pleduc Date 2019-10-21 Time 12:13 Sent To  
Notes
2019-10-21 12:18:28THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-31 Cont ID  
Sent By pleduc Date 2019-07-26 Time   Rev Time 0.00
Received By pleduc Date 2019-07-26 Time 15:32 Sent To B
Notes
2019-07-26 15:30:42FFPC: 1-14.1: FIRE SPRINKLER & FIRE ALARM CONTRACTORS
 SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL.
 FFPC: 1-14.4: APPROVAL BY THE AHJ SHALL NOT RELIEVE THE
 APPLICANT OF THE RESPONSIBILITY OF COMPLIANCE WITH THE
 CODE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-15 Time 14:44 Sent To  
Notes
2019-10-16 14:44:20B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-28 Cont ID  
Sent By tklarge Date 2019-08-28 Time 11:19 Rev Time 0.00
Received By tklarge Date 2019-07-23 Time 13:33 Sent To  
Notes
2019-07-24 13:33:30B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-08-23 Cont ID  
Sent By jgomez Date 2019-08-23 Time 18:36 Rev Time 0.00
Received By jgomez Date 2019-08-23 Time 18:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By hmoser Date 2019-10-23 Time 11:35 Rev Time 0.00
Received By hmoser Date 2019-10-23 Time 10:46 Sent To  
Notes
2019-10-23 11:35:07PASS PROVISO
 PROVIDE DUCT SIZE FOR NEW LINEAR IN EXISTING ELEVATOR
 LOBBY
 BEFOR FIRST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-22 Cont ID  
Sent By hmoser Date 2019-08-22 Time 10:01 Rev Time 0.00
Received By hmoser Date 2019-08-22 Time 09:41 Sent To  
Notes
2019-08-22 10:01:53PLAN DENIED
 1) PROVIDE MORE INFORMATION ON THE AIR CONDITIONING
 SYSTEM.
 DUCT SIZE ON THE NEW SUPPLY DUCT AND RETURN AIR, IF IT
 IS
 ABOVE CEILING RETURN PLEASE INDICATE ON PLAN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By gjohnson Date 2019-10-23 Time 15:50 Rev Time 0.00
Received By gjohnson Date 2019-10-23 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-08-28 Cont ID  
Sent By jgomez Date 2019-08-28 Time 11:19 Rev Time 0.00
Received By tklarge Date 2019-08-28 Time 06:36 Sent To  
Notes
***NONE***