| 2019-07-24 16:53:11 | RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- THIS ROOFING WORK IS FOR ST. MARY'S HOSPITAL. |
| | HOSPITALS ARE ESSENTIAL FACILITIES. ENGINEER DOING THE |
| | RAS 117 CALCULATIONS NEED TO REVISE THE DESIGN CRITERIA |
| | ACCORDINGLY. ENGINEER TO SEE SEC. 1603.1.4, SEC. 1604.5 |
| | AND SEC. 1609.3 FBC-BUILDING AND REVISE DESIGN CRITERIA |
| | AND RAS 117 CALCULATIONS AS REQUIRED. |
| | |
| | 2- IT LOOKS LIKE THERE ARE SEVERAL BUILDINGS WHERE WORK |
| | IS GOING TO BE PERFORMED. THIS IS A VERY LARGE COMPLEX. |
| | IT IS NOT CLEAR WHICH BUILDINGS ARE INVOLVED. PROVIDE A |
| | PLOT PLAN SHOWING EACH BUILDING. AND PROVIDE A PERMIT |
| | APPLICATION FOR EACH BUILDING TO FACILITATE INSPECTIONS |
| | AND RECORD KEEPING. SEC. 105.1.1 CITY AMENDMENTS, SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- STEEL DECK NOA 15-0709.15 SUBMITTED: PROVIDE THE THE |
| | FIELD RESISTANCE TEST (TAS 105) AS REQUIRED BY THE |
| | STEEL DECK LIMITATIONS ON LAST PAGE OF THE NOA |
| | SUBMITTED. |
| | |
| | 4- WATERPROOFING NOA 18-0717.02: SELECTED ASSEMBLY ON |
| | PAGE 15 OF 25 IS LIMITED BY GENERAL LIMITATION #9. THE |
| | DESIGN PRESSURES FOR THIS SYSTEM ARE TOO LOW. THIS |
| | SYSTEM CAN NOT BE USED BECAUSE GENERAL LIMITATION #9 |
| | DOESN'T ALLOW ANY ENHANCEMENT. SEE GENERAL LIMITATION |
| | #9. REVISE AS REQUIRED. |
| | SEC. 1609.3 FBC-BUILDING |
| | |
| | 5- ALL THE NOA'S SUBMITTED ARE MISSING THE LAST PAGE. |
| | THIS PAGE CONTAINS ALL THE SYSTEMS LIMITATIONS AND |
| | GENERAL LIMITATIONS. PROVIDE COPIES OF THE LAST PAGE. |
| | FAC61G20-3.001 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |