Plan Review Details - Permit 19071073
Plan Review Stops For Permit 19071073
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-17 Cont ID  
Sent By jgomez Date 2019-09-17 Time 08:54 Rev Time 0.00
Received By jgomez Date 2019-09-17 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-29 Cont ID  
Sent By jbrooks Date 2019-08-29 Time 08:54 Rev Time 0.00
Received By jbrooks Date 2019-08-29 Time 08:52 Sent To  
Notes
2019-08-29 08:52:56JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1.FBC B 107.2.1. PROVIDE TWO SETS OF FLOOR
 PLANS/BUILDING FOOT PRINT SHOWING LOCATION OF PROPOSED
 ACCORDION SHUTTERS TO BE INSTALLED AND CORRESPONDING
 WITH INSTALLATION SCHEDULE ALONG WITH DIMENSIONS OF
 EACH OPENING.
 2. FBC R 310.4. PLAN TO SHOW REQUIRED MEANS OF EGRESS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-23 Cont ID  
Sent By jbrooks Date 2019-07-23 Time 14:19 Rev Time 0.00
Received By jbrooks Date 2019-07-23 Time 14:19 Sent To  
Notes
2019-07-23 14:19:431. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-17 Cont ID  
Sent By jgomez Date 2019-09-17 Time 08:54 Rev Time 0.00
Received By jgomez Date 2019-09-17 Time 08:43 Sent To  
Notes
2019-09-17 08:44:10MET WITH CONTRACTOR TO GO OVER COMMENTS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-29 Cont ID  
Sent By jbrooks Date 2019-08-29 Time 08:53 Rev Time 0.00
Received By jbrooks Date 2019-08-27 Time 15:30 Sent To  
Notes
2019-08-27 15:30:26RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-23 Cont ID  
Sent By jbrooks Date 2019-07-23 Time 14:20 Rev Time 0.00
Received By jbrooks Date 2019-07-19 Time 15:49 Sent To  
Notes
***NONE***