| 2019-08-07 09:41:43 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19071032 |
| | ADD: 1014 N. OLIVE AVE. |
| | CONT: OCEAN ONE MARINE |
| | TEL: 561-315-4916 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 07/2019 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS ARE PAPER AND HAVE AN ELECTRONIC |
| | SIGNATURE AND SEAL BY ALLEN WIEDER P. E. |
| | 61G15-23.003 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) THE COVERSHEET HAS A SITE PLAN THAT IS IN 1 INCH = |
| | 20 FEET. THIS IS A SMALLER SCALE THAN ALLOWED BY THE |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.3 |
| | QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE. PLEASE CORRECT. |
| | 3) WITHIN THIS PLAN THERE IS NO CODE ANALYSIS & MINIMUM |
| | BUILDING TYPE: |
| | 3A) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP |
| | |
| | 3B) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE SECTION 504.3, TABLE 504.4 & TABLE 506.2). |
| | |
| | 3C) WITH THE CLOSENESS OF THE 2 BUILDINGS IS THERE AN |
| | ASSUMED PROPERTY LINE BETWEEN THE 2 BUILDINGS OR ARE |
| | YOU CONSIDERING THIS AS ONE BUILDING ON THE SAME LOT IN |
| | ACCORDANCE WITH 2017 FBC-B 503.1.2. PLEASE ALSO PROVIDE |
| | THE TOTAL SQ. FT. OF AREA FOR EACH BUILDING. |
| | ASSUMED PROPERTY LINE FBC-B 503.1.2. |
| | RATED EXTERIOR WALLS FBC-B TABLE 602 |
| | ALLOWABLE AREA OPENINGS IN FIRE RATED EXTERIOR WALLS |
| | TABLE 705.8. |
| | |
| | 3D) IS THERE A CHANGE OF OCCUPANCY FOR BOTH AND OR |
| | EITHER BUILDING? 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. CHAPTER 10 OF THE 2017 EXISTING BUILDING |
| | CODE. |
| | |
| | 3D) TO WHICH DESIGN CRITERIA WERE THE PLANS DEVELOPED |
| | UNDER THE 2017 FLORIDA BUILDING CODE EXISTING BUILDING |
| | CODE THE PLANS SHALL COMPLY WITH ONE OF THE METHODS |
| | LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| | BY THE DESIGN PROFESSIONAL. |
| | |
| | 4) WITHIN THIS PLAN SET THERE IS NO REFERENCE TO A LIFE |
| | SAFETY PLAN SHOWING COMPLIANCE WITH: |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | LIFE SAFETY PLAN: |
| | OCCUPANCY TYPE |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | |
| | 5) THE SITE PLAN DOES NOT SHOW: |
| | 5A) ACCESSIBLE PARKING SPACE. 2017 FBC-ACCESSIBILITY |
| | CODE TABLE 208.2. |
| | |
| | 5B) THE PLANS DO NOT STATE THE USAGE FOR THIS PROJECT, |
| | IF THE USAGE IS GOING TO BE ASSOCIATED WITH |
| | REHABILITATION AND OR OUTPATIENT THERAPY THEN SHOW |
| | COMPLIANCE WITH: |
| | 2017 ACCESS. CODE SECTION 208.2.2 REHABILITATION |
| | FACILITIES AND OUTPATIENT PHYSICAL THERAPY FACILITIES. |
| | TWENTY PERCENT OF PATIENT AND VISITOR PARKING SPACES |
| | PROVIDED TO SERVE REHABILITATION FACILITIES |
| | SPECIALIZING IN TREATING CONDITIONS THAT AFFECT |
| | MOBILITY AND OUTPATIENT PHYSICAL THERAPY FACILITIES |
| | SHALL COMPLY WITH 502. |
| | |
| | 5C) PLEASE SHOW COMPLIANCE WITH ACCESSIBLE PARKING |
| | SPACE & ACCESS AISLE SIZE IN ACCORDANCE WITH ACCESS. |
| | CODE 502.2. & 502.3. |
| | |
| | 5D) CITY ACCESSIBLE PARKING STANDARD. AN ACCESSIBLE |
| | PARKING SPACE AND ACCESS AISLE, PLEASE SEE THE 2017 |
| | FBC-ACCESSIBILITY CODE 502.3.3 MARKING. ACCESS AISLES |
| | SHALL BE MARKED SO AS TO DISCOURAGE PARKING IN THEM. |
| | THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO |
| | DESIGNATE IT AS A NO-PARKING ZONE. |
| | |
| | ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF |
| | MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY |
| | BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| | BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE |
| | TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT |
| | THE AISLE BE CLEARLY MARKED. FLORIDA |
| | LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF |
| | ACCESS AISLES. |
| | THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485 |
| | PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING |
| | STALL DETAIL. |
| | |
| | 5E) PLEASE PROVIDE COMPLIANCE WITH THE 2017 FBC-ACCESS. |
| | CODE SECTION: |
| | 206.2.2 WITHIN A SITE. AT LEAST ONE ACCESSIBLE ROUTE |
| | SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE |
| | FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES |
| | THAT ARE ON THE SAME SITE. |
| | |
| | 6) FLOOR PLAN SHEET A-2: |
| | 6A) THE FLOOR PLAN BLDG. # 1 THE WEST BUILDING SHOWS 3 |
| | SETS OF STAIRS TO GAIN ENTRY INTO THIS BUILDING, THIS |
| | BUILDING HAS NO ACCESSIBLE EGRESS. SHOW HOW AN |
| | ACCESSIBLE EGRESS WILL BE COMPLIED WITH FOR THIS |
| | BUILDING. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 6B) THERE ARE 2 EXISTING RESTROOMS IN BLDG. # 1 (WEST |
| | BLDG.) NEITHER IS DESIGNATED AS AN ACCESSIBLE RESTROOM. |
| | RESTROOM # 2 DOES SHOW GRAB BARS AT THE WATER CLOSET |
| | (ASSUMED TO BE THE ACCESSIBLE RESTROOM). PLEASE |
| | ACKNOWLEDGE. RESTROOM IS NOT DIMENSIONED ON SHEET A2 OR |
| | RESTROOM ELEVATIONS A6, CANNOT DETERMINE THE EXACT SIZE |
| | AND ACCESSIBILITY REQUIREMENTS. |
| | |
| | 6C) EXISTING RESTROOM # 2 IN THE WEST BUILDING THE LAV |
| | IS IN THE CLEAR FLOOR SPACE REQUIRED FOR THE |
| | WATERCLOSET. |
| | 2017 ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A |
| | WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM |
| | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES |
| | (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL. |
| | |
| | 2017 ACCESS. CODE 604.3.2 OVERLAP. THE REQUIRED |
| | CLEARANCE AROUND THE WATER CLOSET SHALL BE PERMITTED TO |
| | OVERLAP THE WATER CLOSET, ASSOCIATED GRAB BARS, |
| | DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS, |
| | SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND |
| | CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE TURNING |
| | SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE |
| | LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 6D) SHEET A6 RESTROOM 2 ELEVATION 12 DEPICTS THE LAV |
| | AND MIRROR ABOVE. THERE IS NO DIMENSION TO THE BOTTOM |
| | REFLECTIVE SURFACE OF THE MIRROR SHOWING COMPLIANCE |
| | WITH: |
| | 2017 ACCESS. CODE SECTION CODE 603.3 MIRRORS. MIRRORS |
| | LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| | INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 6E) THERE IS NO ROOM IDENTIFICATION TAGS GIVEN TO THE |
| | ROOMS TO IDENTIFY PROBLEM AREAS WITH THE ROOMS (3 |
| | OFFICES). 107.2.1.2. THERE IS NO FURNITURE PLAN |
| | PROVIDED AS WELL. |
| | |
| | 6F) SHEET A2 THERE ARE NO DOOR IDENTIFICATION TAGS |
| | IDENTIFYING NEW / OLD DOORS, SIZE OF DOORS NOR DOOR |
| | SCHEDULE FOUND. 2017 FBC-B 1010.1.1 DOOR SIZE. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6G) THE FLOOR PLAN SHEET A2 INDICATES ELEVATIONS FOR |
| | KITCHEN ON SHEET A-6 DETAILS 1-4. DETAIL # 1 INDICATES |
| | THE COUNTER TOP/ SINK HEIGHT FROM FINISH FLOOR IS 36 |
| | INCHES TALL. PLEASE PROVIDE COMPLIANCE WITH: |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 6H) THE FLOOR PLAN DOES NOT SHOW IF THE KITCHEN SINK IS |
| | TO BE A FORWARD APPROACH OR SIDE APPROACH SEE: |
| | ACCESS. CODE SECTION 606.2 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| | FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. IF A FORWARD APPROACH IS TO |
| | BE USED THE N SHOW THE REMOVAL OF THE CLEAR FLOOR |
| | SPACE, TOE KICK AND DOORS. |
| | EXCEPTION: |
| | 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| | PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| | TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| | BARS. |
| | |
| | 6I) NOT USED. |
| | |
| | 7) SHEET A2 BUILDING # 2 THE EAST BUILDING: |
| | 7A) PLEASE SHOW WHICH DOORWAY IS THE MAIN ENTRY AND AN |
| | ACCESSIBLE EGRESS INTO THIS BUILDING? SHOW HOW AN |
| | ACCESSIBLE EGRESS WILL BE COMPLIED WITH FOR THIS |
| | BUILDING. |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 7B) SHEET A2 BUILDING # 2 SHOWS AN ACCESSIBLE BATHROOM |
| | AND PROPOSED SHOWER STALL. THE SIZE OF THE PROPOSED |
| | SHOWER STALL IS 3 FEET X 4 FEET IN LENGTH. PLEASE SEE |
| | THE 2017 ACCESS. CODE FOR THE MINIMUM SIZE OF SHOWER |
| | STALLS. ACCESS. CODE 608.2. |
| | 608.2.1 TRANSFER STALLS ? MINIMUM STALL SIZE OF 36 |
| | INCHES X 36 INCHES. |
| | 608.2.2. STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS 36 |
| | INCHES X 60 INCHES AND SHALL HAVE A 60 INCHES WIDE |
| | MINIMUM ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. |
| | NOT THE END OF A SHOWER STALL, THIS IS AN ACCESSIBLE |
| | SHOWER STALL. |
| | |
| | 7C) SHEET A6 DETAIL 13 THE ACCESSIBLE ROLL-IN SHOWER |
| | SHOWS A CURB AT THE ENTRY. ROLL-IN SHOWERS HAVE NO |
| | CURBS, THEY ARE ROLL-IN TYPE SHOWERS. PLEASE REDESIGN |
| | THE SHOWER TO COMPLY WITH ALL OF THE REQUIREMENTS FOUND |
| | FOR ACCESSIBLE ROLL-IN SHOWERS ACCESS. CODE 608.2.2 OR |
| | 608.2.3. |
| | |
| | 7D) THERE IS NO ROOM IDENTIFICATION TAGS GIVEN TO THE |
| | ROOMS TO IDENTIFY PROBLEM AREAS WITH THE ROOMS (3 |
| | OFFICES). 107.2.1.2. THERE IS NO FURNITURE PLAN |
| | PROVIDED AS WELL. |
| | |
| | 7E) SHEET A2 THERE ARE NO DOOR IDENTIFICATION TAGS |
| | IDENTIFYING NEW / OLD DOORS, SIZE OF DOORS NOR DOOR |
| | SCHEDULE FOUND. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. 2017 FBC-B 1010.1.1 DOOR SIZE. |
| | |
| | 7F) THE FLOOR PLAN SHOWS THE ACCESSIBLE BATHROOM, SHEET |
| | A6 DETAIL 14 SHOWS THE LAV AND MIRROR. |
| | THERE IS NO DIMENSION TO THE BOTTOM REFLECTIVE SURFACE |
| | OF THE MIRROR SHOWING COMPLIANCE WITH: |
| | 2017 ACCESS. CODE SECTION CODE 603.3 MIRRORS. MIRRORS |
| | LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| | INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 8) THERE IS NO REFLECTIVE CEILING PLAN WITH THE |
| | EXCEPTION OF SHEET A-5 AN ELECTRICAL OUTLET AND CEILING |
| | FIXTURE PLAN. PLEASE PROVIDE COMPLIANCE WITH: 2017 |
| | FBC-B: |
| | |
| | 8A) 1209.2 ATTIC SPACES. AN OPENING NOT LESS THAN 20 |
| | INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE |
| | PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF |
| | OVER 30 INCHES (762 MM). CLEAR HEADROOM OF NOT LESS |
| | THAN 30 INCHES (762 MM) SHALL BE PROVIDED IN THE ATTIC |
| | SPACE AT OR ABOVE THE ACCESS OPENING. |
| | |
| | |
| | 8B) 1209.3 MECHANICAL APPLIANCES. ACCESS TO MECHANICAL |
| | APPLIANCES INSTALLED IN UNDER-FLOOR AREAS, IN ATTIC |
| | SPACES AND ON ROOFS OR ELEVATED STRUCTURES SHALL BE IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL. |
| | |
| | 9) PLEASE CORRECT THE PAGE NUMBERING, THERE ARE 2 |
| | SHEETS IDENTIFIED AS S-3 AND NO SHEET S-4. TYPO. |
| | |
| | 10) INFORMATIONAL: THE PRESSURES (IN VASD) FOUND ON |
| | SHEET S-3 FOR COMPONENTS AND CLADDING ARE GOOD FOR ALL |
| | PRESSURE ZONES 1-5. THE PRODUCT APPROVALS FOR |
| | COMPONENTS AND CLADDING CAN BE DEFERRED BY EITHER THE |
| | CONTRACTOR OR THE DESIGNER OF RECORD. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE 107.3.4.2 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 11A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS. |
| | (B) WINDOWS & MULLIONS. |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS. |
| | |
| | 11B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 12) PLEASE NOTE THERE ARE WELDED AND BOLTED CONNECTIONS |
| | WITH-IN THE PROJECT. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION. IN |
| | ACCORDANCE WITH THE AMERICAN WELDING SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING / 2017 FBC-B 2204.2 BOLTING. |
| | FOR FURTHER QUESTIONS ABOUT THIS COMMENT, PLEASE |
| | CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD AT |
| | 561-805-6666. |
| | |
| | 13) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| | BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| | APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| | THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| | WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| | PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| | THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |