| 2020-03-14 10:31:26 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1) 107.5.3 FBC[AMENDED]PLEASE REMOVE PLAN SHEETS A-1.0 |
| | TO A-4.1 FROM BOTH SETS AS THESE ARE FOR WORK THAT IS |
| | ISSUED UNDER SEPARATE PERMIT. |
| | |
| | 2ND REVIEW, PAGES NOT REMOVED. |
| | |
| | 2) 503.3 FBC[CE] BUILDING ENVELOPE. NEW BUILDING |
| | ENVELOPE ASSEMBLIES THAT ARE PART OF THE ALTERATION |
| | SHALL COMPLY WITH SECTIONS C402.1 THROUGH C402.5. |
| | -PROVIDE INSULATION TYPE AND LOCATION FOR THE NEWLY |
| | CREATED ROOF AREA. |
| | |
| | 2ND REVIEW, RESPONSE LETTER DOES NOT STATE WHERE THIS |
| | WAS REVISED ON THE PLAN AND I WAS UNABLE TO LOCATE IT; |
| | EITHER REVISE PLAN OR SEND ME AN EMAIL ADVISING ON |
| | WHICH PAGE IT CAN BE FOUND. |
| | |
| | 3) OK |
| | |
| | 4) 602.1 CONSTRUCTION CLASSIFICATION. |
| | -WHAT IS THE CONSTRUCTION TYPE FOR THE BUILDING? |
| | -WHAT IS THE HEIGHT OF ROOF MEMBERS FROM THE FLOOR? |
| | SEE TABLE 601 FOR CONSTRUCTION TYPES AND APPLICABLE |
| | EXEMPTIONS. |
| | |
| | 2ND REVIEW, UNABLE TO LOCATE THIS INFORMATION ON THE |
| | PLANS. |
| | |
| | 5) 107.5.3 FBC[AMENDED]PLEASE REVIEW MATERIALS FOR |
| | CONSTRUCTION TYPE FOR THE GABLE END WALLS AND ADD WHAT |
| | TYPE OF FINISH MATERIALS ARE BEING USED FOR WEATHER |
| | PROTECTION. ALSO, TYPE AND VALUE OF INSULATION TO BE |
| | USED. |
| | |
| | 2ND REVIEW, A NEW SHEET S-1.0 WAS PROVIDED, OLD PAGE IS |
| | STILL IN THE PACKAGE. REMOVE ALL SUPERSEDED PAGES, MARK |
| | VOID, FOLD AND KEEP IN THE SUBMITTAL BUT REMOVED FROM |
| | THE BOUND SET. ALL PAGES SHOULD BE IN THE ORDER OF THE |
| | INDEX. |
| | |
| | ARCHITECT'S RESPONSE LETTER STATES THAT THIS IS TYPE II |
| | BUILDING, STRUCTURAL DETAIL SHOWS CDX PLYWOOD |
| | SHEATHING. FBC B 603, PLEASE CORRELATE. |
| | |
| | 6) NEW COMMENT - ALL ARCHITECTURAL PAGES HAVE AN IMAGE |
| | OF THE ARCHITECT'S SIGNATURE. MY UNDERSTANDING IS THAT |
| | THE BOARD REQUIRES A WET SIGNATURE. EITHER SIGN ALL |
| | PAGES OR ADVISE VIA EMAIL THAT YOU DISAGREE; AN INQUIRY |
| | WILL BE SENT TO THE BOARD. |
| | |
| | 7. NEW COMMENT - THE VALUE APPEARS LOW. PROVIDE AN |
| | ITEMIZED COST BREAKDOWN INCLUDING QUANTITIES/SF/LF AS |
| | APPLICABLE. |
| | |
| | 8) THIS PERMIT WILL BE ISSUED WITH PROVISO: |
| | SUBMIT PRE-ENGINEERED STEEL TRUSSES TO INSPECTOR PRIOR |
| | TO INSTALLATION. POINT LOAD OF NEW HANGING FIXTURE TO |
| | BE INCLUDED IN THE SUBMITTAL. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | |