Plan Review Details - Permit 19070860
Plan Review Stops For Permit 19070860
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-15 Cont ID  
Sent By jbrooks Date 2019-08-15 Time 07:43 Rev Time 0.00
Received By jbrooks Date 2019-08-15 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-06 Cont ID  
Sent By jbrooks Date 2019-08-06 Time 12:59 Rev Time 0.00
Received By jbrooks Date 2019-08-06 Time 12:59 Sent To  
Notes
2019-08-06 13:00:46JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FBC B 107.2.1. PLEASE CLARIFY; SCOPE OF WORK ON
 DRAWINGS INDICATE NEW 1.5 HOUR FIRE RATED DOOR IN
 SERVICE LOBBY AT 1ST FLOOR THRU 10TH FLOOR, IS THIS A
 TYPICAL FLOOR PLAN FOR FLOORS ONE THROUGH TEN? IF NOT
 PROVIDE FOR EACH FLOOR.
 2. FBC EB 801.1 & 801.2 LEVEL 2 ALTERATIONS AS
 DESCRIBED IN SECTION 504 SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 8. IN ADDITION TO THE
 REQUIREMENTS OF THIS CHAPTER, ALL WORK SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 7. SUBMITTED DRAWINGS
 MUST SHOW COMPLIANCE WITH ALL APPLICABLE SECTIONS OF
 THIS CODE.
 3. FBC B 107.2.1 PROVIDE FRAMING DETAILS SUPPLIED FOR
 ALL NEW WALLS/CEILINGS/INFILL/SOFFITS. SHOW ANCHORAGE,
 BRACING AND BLOCKING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-25 Cont ID  
Sent By jbrooks Date 2019-07-25 Time 09:59 Rev Time 0.00
Received By jbrooks Date 2019-07-25 Time 09:59 Sent To  
Notes
2019-07-25 10:00:21JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 16-0330.11 HAS BEEN SUPERSEDED BY MIAMI-DADE COUNTY NOA
 NO. 17-0829.08 AND DOES NOT HAVE AN UL LISTED FIRE
 RATING. PROVIDE TWO SETS OF PRODUCT
 APPROVALS/SPECIFICATIONS FOR THE PROPOSED 1.5-HOUR FIRE
 RATED DOORS TO BE USED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-15 Cont ID  
Sent By jbrooks Date 2019-08-15 Time 07:44 Rev Time 0.00
Received By jbrooks Date 2019-08-12 Time 14:08 Sent To  
Notes
2019-08-13 14:08:40RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-06 Cont ID  
Sent By jbrooks Date 2019-08-06 Time 13:02 Rev Time 0.00
Received By jbrooks Date 2019-07-31 Time 15:00 Sent To  
Notes
2019-08-01 15:00:34RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-25 Cont ID  
Sent By jbrooks Date 2019-07-25 Time 10:00 Rev Time 0.00
Received By jbrooks Date 2019-07-17 Time 13:44 Sent To  
Notes
***NONE***