Plan Review Details - Permit 19070834
Plan Review Stops For Permit 19070834
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2021-12-20 Cont ID  
Sent By cthroop Date 2021-12-20 Time 09:43 Rev Time 0.00
Received By cthroop Date 2021-12-20 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-12-13 Cont ID  
Sent By cthroop Date 2021-12-13 Time 13:26 Rev Time 0.00
Received By cthroop Date 2021-12-11 Time 12:05 Sent To  
Notes
2021-12-13 13:27:13DEFERRAL ON PLAN PAGE A-600: SUBMIT PRODUCT APPROVALS
 FOR ALL WINDOWS AND DOORS FOR REVIEW AND APPROVAL PRIOR
 TO INSTALLATION. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-10-21 Cont ID  
Sent By cthroop Date 2021-10-21 Time 11:37 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-03-29 Cont ID  
Sent By cthroop Date 2021-03-29 Time 14:53 Rev Time 0.00
Received By cthroop Date 2021-03-29 Time 11:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-16 Cont ID  
Sent By rmcdouga Date 2020-06-16 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2020-06-16 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-26 Cont ID  
Sent By cthroop Date 2019-10-26 Time 07:45 Rev Time 0.00
Received By cthroop Date 2019-10-26 Time 06:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By rmcdouga Date 2019-09-24 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2019-09-17 Time 18:10 Sent To I
Notes
2019-09-24 09:10:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND DESIGN INFORMATION ON SHEET CS-2 SPECIFIES
 ASCE 7-16 AND THE 2017 FBC REFERENCES ASCE 7-10. PLEASE
 REVISE THE PLANS TO SPECIFY ASCE 7-10. FBC-R CHAPTER 46
  
 2) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS AND
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC ENERGY
 CONSERVATION R401.2 & R403.7.1
  
 3) SPECIFY THE INSULATION TYPE AND R-VALUE ON THE PLANS
 FOR THE EXTERIOR ENVELOPE ( UNDER FLOOR, WALLS AND
 ATTICS/CEILINGS) INCLUDING THE LOFT AREA. FBC ENERGY
 CONSERVATION R402.1
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS, HARDI BOARD SIDING AND EXTERIOR DOOR TYPES.
 THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT
 APPROVAL WEBSITE.
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
 THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT APPROVAL
 WEBSITE.
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 5) FBC 107.3.5.3 ? INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 6) SHOW COMPLIANCE FOR ATTIC VENTILATION AS REQUIRED BY
 FBC-R806.
  
 7) SHOW COMPLIANCE WITH FBC-R807 FOR ATTIC ACCESS.
  
 8) SHOW COMPLIANCE WITH FBC-R408 FOR UNDER FLOOR
 VENTILATION.
  
 9) SHOW COMPLIANCE WITH FBC-R408.4 FOR ACCESS TO UNDER
 FLOOR SPACES.
  
 10) FBC-R310.1 THE GUEST BEDROOM WINDOWS DO NOT MEET
 THE REQUIREMENTS OF FBC R310 FOR EMERGENCY AND RESCUE
 OPENINGS. INDICATE THE EXISTING WINDOW'S TYPE AND THE
 NET CLEAR OPENING SIZE OF IT. PROVIDE CALCULATIONS TO
 SHOW THAT THE NET CLEAR OPENING DIMENSIONS OF THE
 EXISTING WINDOW ARE NOT BEING REDUCED BY MORE THAN
 5-PERCENT PER FBC EXISTING BUILDING SECTION 702.5.
  
 11) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 12) FBC-R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 13) SHOW COMPLIANCE WITH FBC - R301.2.1.2 FOR
 PROTECTION OF GLAZED OPENINGS. FBC - R 301.2.1.2 SUBMIT
 TWO COPIES OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR
 THE STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND
 PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE
 DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE
 FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER
 FROM THE INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK
 TO THE CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS
 MANY OF THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ (
 NOT REQUIRED IF LARGE MISSILE IMPACT WINDOWS ARE USED.)
  
 14) THE MASTER BATHROOM WINDOW IS REQUIRED TO COMPLY
 WITH FBC-R308.4.5 FOR SAFETY GLAZING. ( IMPACT WINDOWS
 MEET THE REQUIREMENTS)
  
 15) FBC-R317.1 (1) REQUIRES WOOD JOISTS CLOSER THAN 18"
 AND WOOD GIRDERS CLOSER THAN 12" TO THE EXPOSED GROUND
 IN CRAWL SPACES TO BE PROTECTED FROM DECAY. ON SHEET
 S-100 OF THE PLANS IT IS NOTED THAT THE FLOOR
 JOISTS/GIRDERS ARE TREATED. IN ORDER TO CLARIFY,
 SPECIFY THAT THE WOOD IS TO BE PRESERVATIVE-TREATED IN
 ACCORDANCE WITH AWPA U1.
  
 16) SHOW ON THE PLANS THAT THE LOFT AREAS COMPLY WITH
 FBC-R304 AND R305 FOR THE REQUIRED CEILING HEIGHT AND
 DIMENSIONS TO BE CONSIDERED HABITABLE SPACE.
  
 17) FBC-R311.3 REQUIRES LANDINGS AT EXTERIOR
 DOORS.THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF
 EACH EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE
 NOT LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE
 A DIMENSION OF NOT LESS THAN 36 INCHES (914 MM)
 MEASURED IN THE DIRECTION OF TRAVEL. THERE IS NO
 LANDING SHOWN ON THE PLANS AT THE PROPOSED MASTER
 BEDROOM SLIDING DOOR AND THE ONES AT THE DOORS ON EACH
 SIDE OF THE DWELLING ARE LESS THAN 36" WIDE FROM THE
 WALL TO THE GUARDS.
  
 18) PROVIDE INTERIOR STAIR DETAILS. SHOW COMPLIANCE
 WITH FBC-R 311.7.2 FOR MINIMUM HEADROOM OF 6'-8" AND
 R311.7.5 FOR STAIR TREADS AND RISERS.
  
 19) PROVIDE DETAILS THAT SHOW ALL CONNECTIONS TO
 PROVIDE A COMPLETE LOAD PATH FROM THE ROOF TO THE
 FOUNDATION. SPECIFY THE CONNECTORS/ANCHORS THAT WILL BE
 USED. FBC-R301.1
  
 20) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2019-08-25 20:07:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2021-12-13 Cont ID  
Sent By cthroop Date 2021-12-13 Time 09:34 Rev Time 0.00
Received By cthroop Date 2021-12-11 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2021-10-22 Cont ID  
Sent By cthroop Date 2021-10-22 Time 09:24 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:56 Sent To  
Notes
2021-10-22 09:27:29ELECTRICAL PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 5TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 COMMENTS FROM 4TH ELECTRICAL REVIEW HAVE NOT BEEN
 ADDRESSED
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ADDING A LOAD OF 27KW, PLEASE SUBMIT A LOAD CALCULATION
 TO SUPPORT THE LOAD. 215.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2021-03-26 Cont ID  
Sent By jleahy Date 2021-03-26 Time 16:08 Rev Time 0.00
Received By jleahy Date 2021-03-26 Time 12:59 Sent To  
Notes
2021-03-26 16:09:57FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ADD ING A LOAD OF 27KW, PLEASE SUBMIT A LOAD
 CALCULATION TO SUPPORT THE LOAD. 215.5

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-17 Cont ID  
Sent By jleahy Date 2020-06-17 Time 12:03 Rev Time 0.00
Received By jleahy Date 2020-06-17 Time 10:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-21 Cont ID  
Sent By fgiaquin Date 2019-10-21 Time 05:53 Rev Time 0.00
Received By fgiaquin Date 2019-10-21 Time 05:50 Sent To  
Notes
2019-10-21 05:53:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS BLURRED AND UNREADABLE. PLEASE
 SEE REQUIREMENTS BELOW FOR PLAN SUBMISSION PER FBC,
  
  
 THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE REVIEW
 THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-25 Cont ID  
Sent By fgiaquin Date 2019-08-25 Time 20:07 Rev Time 0.00
Received By fgiaquin Date 2019-08-25 Time 19:29 Sent To  
Notes
2019-09-17 18:15:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2021-12-13 Cont ID  
Sent By cthroop Date 2021-12-13 Time 10:57 Rev Time 0.00
Received By cthroop Date 2021-12-11 Time 10:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2021-10-22 Cont ID  
Sent By cthroop Date 2021-10-22 Time 17:04 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:56 Sent To  
Notes
2021-10-22 17:05:26FUEL GAS PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 5TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: COMMENTS FROM PREVIOUS REVIEW HAVE NOT BEEN
 ADDRESSED: SEE BELOW:
  
 GAS 1ST REVIEW**DENIED* DURING THE 1ST PLAN REVIEW
 THERE WAS NOTHING MENTIONED ABOUT GAS. WITH A NEW
 TANKLESS WATER HEATER BEING INSTALLED WHERE ONE WAS NOT
 EXISTING A GAS PERMIT IS REQUIRED AND THE FOLLOWING
 COMMENT WILL BE TO BE ADDRESSED.
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION FOR THE STOVE,
 FIREPLACE, AND DRYER IF THERE WILL BE GAS. FBC 107.3.5
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 9. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 10. 15) INDICATE ON THE PLAN IF THE TANKLESS WATER
 HEATER IS REPLACING AN EXISTING TANKLESS WATER HEATER
 OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR
 IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM?
 INDICATE ON THE APPLICATION IN THE DESCRIPTION OF WORK.
 11. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 12. 18) SHOW THE LOCATION OF ALL MP (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL
 GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 13. 19) THE PLANS INDICATE AN EXISTING GAS METER. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 14. 20) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
 TIM HUNT
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2021-03-24 Cont ID  
Sent By ccole Date 2021-03-24 Time 15:02 Rev Time 0.00
Received By ccole Date 2021-03-24 Time 14:36 Sent To  
Notes
2021-03-24 15:06:304TH REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 19070834
 3/24/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 1) P-101: THE REVISED PLAN SHOWS AN ELECTRIC
 TANKLESS WATER HEATER HOWEVER THE COMMENT RESPONSE
 LETTER INDICATES A GAS TANKLESS WATER HEATER WILL BE
 INSTALLED USING EXISTING GAS ON SITE. MANUFACTURER?S
 SPECIFICATIONS FOR A GAS TANKLESS WATER HEATER HAVE
 ALSO BEEN SUBMITTED. IN THE PREVIOUS LETTER DATED
 3/12/2020, IT WAS STATED THAT THERE WAS NO GAS ON SITE
 AND GAS REVIEW NOT APPLICABLE. PLEASE CLARIFY ON THE
 PLUMBING PLAN WHICH WATER HEATER IS TO BE INSTALLED AND
 PROVIDE THE CONDENSATE DISPOSAL PLAN AS PREVIOUSLY
 REQUESTED. PLEASE SEE PREVIOUS GAS REVIEW COMMENTS
 BELOW FROM PLUMBING/GAS PLANS EXAMINER TIM HUNT
 10/19/2020-
  
 GAS 1ST REVIEW**DENIED* DURING THE 1ST PLAN REVIEW
 THERE WAS NOTHING MENTIONED ABOUT GAS. WITH A NEW
 TANKLESS WATER HEATER BEING INSTALLED WHERE ONE WAS NOT
 EXISTING A GAS PERMIT IS REQUIRED AND THE FOLLOWING
 COMMENT WILL BE TO BE ADDRESSED.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL). WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION FOR THE STOVE,
 FIREPLACE, AND DRYER IF THERE WILL BE GAS. FBC 107.3.5.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 11. SUBMIT COPIES OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 12. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 13. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 14. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 TIM HUNT
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS ST.
 WEST PALM BEACH, FL. 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2020-06-18 Cont ID  
Sent By ccole Date 2020-06-18 Time 16:42 Rev Time 0.00
Received By ccole Date 2020-06-17 Time 15:10 Sent To  
Notes
2020-06-18 16:43:38GAS HAS BEEN REMOVED FROM THE PROJECT PER THE
 ARCHITECT'S RESPONSES TO 2ND REVIEW COMMENTS.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-10-28 Cont ID  
Sent By cthroop Date 2019-10-26 Time 07:13 Rev Time 0.00
Received By shill Date 2019-10-28 Time 08:09 Sent To  
Notes
2019-10-28 08:10:07GAS 1ST REVIEW**DENIED* DURING THE 1ST PLAN REVIEW
 THERE WAS NOTHING MENTIONED ABOUT GAS. WITH A NEW
 TANKLESS WATER HEATER BEING INSTALLED WHERE ONE WAS NOT
 EXISTING A GAS PERMIT IS REQUIRED AND THE FOLLOWING
 COMMENT WILL BE TO BE ADDRESSED.
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION FOR THE STOVE,
 FIREPLACE, AND DRYER IF THERE WILL BE GAS. FBC 107.3.5
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 9. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 10. 15) INDICATE ON THE PLAN IF THE TANKLESS WATER
 HEATER IS REPLACING AN EXISTING TANKLESS WATER HEATER
 OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR
 IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM?
 INDICATE ON THE APPLICATION IN THE DESCRIPTION OF WORK.
 11. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 12. 18) SHOW THE LOCATION OF ALL MP (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL
 GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 13. 19) THE PLANS INDICATE AN EXISTING GAS METER. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 14. 20) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
 TIM HUNT
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  
  
2019-10-26 07:14:18NO NOTES

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-10-25 Cont ID  
Sent By shill Date 2019-10-25 Time 06:32 Rev Time 0.00
Received By shill Date 2019-10-25 Time 06:32 Sent To  
Notes
2019-10-25 06:32:45SEE 2ND GAS REVIEW. NO GAS WAS SHOWN IN FIRST REVIEW
 CYCLE. A NEW TANKLESS WAS ADDED IN 2ND REVIEW.
 ELECTRICAL PLANS ARE NOT CLEAR ENOUGH TO DETERMINE IF
 THIS IS ELECTRICAL OR GAS, THEREFORE A GAS REVIEW IS
 DONE IN 2ND REVIEW CYCLE.
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2021-10-27 Cont ID  
Sent By fmittner Date 2021-10-27 Time 12:38 Rev Time 0.00
Received By fmittner Date 2021-10-27 Time 12:38 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2021-03-30 Cont ID  
Sent By fmittner Date 2021-03-30 Time 11:04 Rev Time 0.00
Received By fmittner Date 2021-03-30 Time 11:04 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2020-06-12 Cont ID  
Sent By fmittner Date 2020-06-12 Time 11:21 Rev Time 0.00
Received By fmittner Date 2020-06-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By fmittner Date 2019-10-23 Time 16:58 Rev Time 0.00
Received By fmittner Date 2019-10-23 Time 16:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By fmittner Date 2019-09-06 Time 14:04 Rev Time 0.00
Received By fmittner Date 2019-09-06 Time 14:04 Sent To  
Notes
2019-09-06 14:14:42PROPERTY LOCATED IN HISTORIC DISTRICT. STAFF HAS HAD
 MULTIPLE CONVERSATIONS WITH OWNER/ARCHITECTS REGARDING
 PROJECT BUT NO FORMAL COA WAS AUBMITTED/APPROVED. OF
 PARTICULAR NOTE IS TEH AHRDI-BOARD IS NOT PERMITTE DON
 CONTRIBUTING STRUCTURES. QUESTIONS, CONTACT: FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT (561)
 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-12-20 Cont ID  
Sent By lmarchan Date 2021-12-20 Time 11:32 Rev Time 0.00
Received By lmarchan Date 2021-12-17 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-12-13 Cont ID  
Sent By cthroop Date 2021-12-13 Time 13:27 Rev Time 0.00
Received By cthroop Date 2021-12-10 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-10-28 Cont ID  
Sent By lmarchan Date 2021-10-28 Time 07:55 Rev Time 0.00
Received By lmarchan Date 2021-10-05 Time 12:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-03-30 Cont ID  
Sent By cthroop Date 2021-03-30 Time 11:15 Rev Time 0.00
Received By cthroop Date 2021-03-17 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-06-18 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-03 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-26 Cont ID  
Sent By cthroop Date 2019-10-26 Time 07:45 Rev Time 0.00
Received By cthroop Date 2019-10-15 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-09-24 Cont ID  
Sent By rmcdouga Date 2019-09-24 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2019-08-21 Time 15:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By lmarchan Date 2021-12-22 Time 12:40 Rev Time 0.00
Received By lmarchan Date 2021-12-17 Time 16:18 Sent To  
Notes
2021-12-22 10:44:19RECEIPT MU-2021-059049 - $185.17 PAID
  
2021-12-17 16:18:5112/17/21 EMAILED IMPACT FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-09-17 Cont ID  
Sent By rmcdouga Date 2019-09-17 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2019-09-17 Time 18:10 Sent To  
Notes
2020-06-16 07:30:11IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2021-12-13 Cont ID  
Sent By cthroop Date 2021-12-13 Time 09:54 Rev Time 0.00
Received By cthroop Date 2021-12-11 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2021-10-21 Cont ID  
Sent By cthroop Date 2021-10-21 Time 11:09 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:57 Sent To  
Notes
2021-10-21 11:09:53SEE COMMENTS FROM 5TH MECH REVIEW.
  
 PLAN DENIED
 1) PROVIDE GRILL SIZE AND CFM ON ALL SUPPLY GRILLS.
 SECTION 107 FBC 2019.
 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN.
 PER SECTION 107 FBC 2019.
 3) REFER TO SECTION M1602 FBC 2019
 RESIDENTIAL CODE RETURN AIR.
 4) REFER TO SECTION M1305 APPLIANCE ACCESS
 2019 FBC RESIDENTIAL CODE
 5) REFER TO SECTION 1401.3 EQUIPMENT SIZING
 2019 FBC RESIDENTIAL CODE.
 6) PLEASE EXPLAIN WHAT TYPE OF AIR CONDITIONING WORK
 IS BEING DON ON THE SECOND FLOOR.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 516-805-6732
 FAX 561-805-6676
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2021-10-13 Cont ID  
Sent By hmoser Date 2021-10-13 Time 13:34 Rev Time 0.00
Received By hmoser Date 2021-10-13 Time 10:43 Sent To  
Notes
2021-10-13 13:34:32PLAN DENIED
 1) PROVIDE GRILL SIZE AND CFM ON ALL SUPPLY GRILLS.
 SECTION 107 FBC 2019.
 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN.
 PER SECTION 107 FBC 2019.
 3) REFER TO SECTION M1602 FBC 2019
 RESIDENTIAL CODE RETURN AIR.
 4) REFER TO SECTION M1305 APPLIANCE ACCESS
 2019 FBC RESIDENTIAL CODE
 5) REFER TO SECTION 1401.3 EQUIPMENT SIZING
 2019 FBC RESIDENTIAL CODE.
 6) PLEASE EXPLAIN WHAT TYPE OF AIR CONDITIONING WORK
 IS BEING DON ON THE SECOND FLOOR.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 516-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-03-29 Cont ID  
Sent By cthroop Date 2021-03-29 Time 14:53 Rev Time 0.00
Received By cthroop Date 2021-03-29 Time 11:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-06-15 Cont ID  
Sent By medwards Date 2020-06-12 Time 09:15 Rev Time 0.00
Received By medwards Date 2020-06-12 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-10-26 Cont ID  
Sent By cthroop Date 2019-10-26 Time 07:35 Rev Time 0.00
Received By cthroop Date 2019-10-26 Time 06:29 Sent To  
Notes
2019-10-26 07:45:12MECHANICAL PLAN REVIEW
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. TEXT ON PLAN PAGES M-101 & M-102 IS TOO BLURRY TO
 READ.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ARCHITECTS SIGNATURE AND SEAL ON PLAN PAGES M-101 &
 M-102 CAN NOT BE VERIFIED. PLAN IS ALSO SIGNED BY
 CONTRACTOR. ARCHITECT SHALL REMOVE SIG. & SEAL OR
 UPLOAD VALID DIGITAL SIG. & SEAL VIA PROJECT DOX.
 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-09-16 Cont ID  
Sent By cmontell Date 2019-09-16 Time 14:00 Rev Time 0.00
Received By cmontell Date 2019-09-16 Time 13:58 Sent To  
Notes
2019-09-16 14:00:03MECHANICAL PLAN REVIEW FAIL
  
 1 - CAN NOT READ PLAN
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 6 Status P Date 2021-12-13 Cont ID  
Sent By cthroop Date 2021-12-13 Time 10:57 Rev Time 0.00
Received By cthroop Date 2021-12-11 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2021-10-22 Cont ID  
Sent By cthroop Date 2021-10-22 Time 17:00 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:55 Sent To  
Notes
2021-10-22 17:04:01BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 5TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SHOWER PAN DETAIL. PREVIOUSLY REQUESTED
 UNDER 1ST PLUMBING REVIEW ON 9/6/2019.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-03-24 Cont ID  
Sent By ccole Date 2021-03-24 Time 14:35 Rev Time 0.00
Received By ccole Date 2021-03-24 Time 13:20 Sent To  
Notes
2021-03-24 14:35:314TH REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 19070834
 3/24/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-101: THE REVISED PLAN SHOWS AN ELECTRIC TANKLESS
 WATER HEATER HOWEVER THE COMMENT RESPONSE LETTER
 INDICATES A GAS TANKLESS WATER HEATER WILL BE INSTALLED
 USING EXISTING GAS ON SITE. MANUFACTURER?S
 SPECIFICATIONS FOR A GAS TANKLESS WATER HEATER HAVE
 ALSO BEEN SUBMITTED. IN THE PREVIOUS LETTER DATED
 3/12/2020, IT WAS STATED THAT THERE WAS NO GAS ON SITE
 AND GAS REVIEW NOT APPLICABLE. PLEASE CLARIFY ON THE
 PLUMBING PLAN WHICH WATER HEATER IS TO BE INSTALLED AND
 PROVIDE THE CONDENSATE DISPOSAL PLAN AS PREVIOUSLY
 REQUESTED. REFER TO GAS REVIEW COMMENTS FOR GAS WATER
 HEATER COMPLIANCE REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-06-18 Cont ID  
Sent By ccole Date 2020-06-18 Time 16:39 Rev Time 0.00
Received By ccole Date 2020-06-17 Time 15:10 Sent To  
Notes
2020-06-18 16:39:513RD REVIEW FBC-2017 RES.
 PERMIT- 19070834
 6/18/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW WATER
 HEATER ON THE PLAN- SECTION M2005.1 FBC RES. THIS NEW
 WATER HEATER IS ASSUMED TO BE ELECTRIC-FIRED PER THE
 ARCHITECT'S COMMENT RESPONSES. PROVIDE THE MAKE AND
 MODEL, GALLON CAPACITY, ELECTRICAL DATA, AND EFFICIENCY
 RATING IN THE SCHEDULE- SEE TABLE C404.2 FBC EC FOR
 MINIMUM EFFICIENCY RATING. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE UNIT- SECTION 107.2.1 WPB.
 2) PROVIDE A FRONT ELEVATION VIEW OF THE WATER HEATER
 IN THE CLOSET HOW ACCESS WILL BE PROVIDED, AND THE
 REQUIRED DRAIN PAN AND DRAIN PAN PIPE. SHOW THE DRAIN
 PAN PIPE RUN AND TERMINATION LOCATION- SEE SECTIONS
 P2801.5, P2801.6.1, P2801.6.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-10-25 Cont ID  
Sent By shill Date 2019-10-25 Time 06:31 Rev Time 0.00
Received By shill Date 2019-10-21 Time 11:35 Sent To  
Notes
2019-10-25 06:32:08PLUMBING 2ND REVIEW**DENIED**
  
 1)PROVIDE A SANITARY RISER DRAWING AND NOT A FLAT
 DRAWING. ALL NEW WORK INCLUDING THE MASTER SHOWER SHALL
 BE INCLUDED. FBC-PLB 107.3.5
 2) PROVIDE AN EXISTING FLOOR PLAN. SHOW THE LOCATION OF
 ALL EXISTING PLUMBING FIXTURES INCLUDING THE WATER
 HEATER. FBC 107.3.5
 3) PROVIDE STEAM UNIT RELIEF, PAN, AND PAN DRAIN
 DETAIL. FBC 107.2.1
 4) SHT. P102 CALLED THE LOFT PLUMBING DOES NOT SHOW ANY
 PLUMBING FIXTURES NOR IS THERE A GUT STACK ON THE FLAT
 DRAWING YOU PROVIDED. PLEASE CLARIFY. FBC 107.2.1
  
 TIM HUNT
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By thunt Date 2019-09-06 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2019-09-06 Time 09:25 Sent To  
Notes
2019-09-06 09:25:20PLUMBING 1ST REVIEW**DENIED**19070834
 1-SUB PLUMBING PERMIT REQUIRED. FBC 105.1
 2-PROVIDE LOCATION ON FLOOR PLAN OF WATER HEATER AND
 PROVIDE INSTALLATION MANUAL SHOWING IT MEETS FLORIDA
 ENERGY CODE. FBC 107.2.1
 3-PROVIDE A COMPLETE SANITARY ISOMETRIC DRAWING. FBC
 107.3.5
 4-PROVIDE SHOWER PAN DETAIL SHOWING THE 2% PRE-PITCH
 AND MATERIAL TO BE USED. FBC 107.2.1
 5-PROVIDE NOTE ON PLAN THE HAMMER ARRESTORS REQUIRED ON
 ALL QUICK CLOSING VALVES. FBC-PLB 604.9 AND WASHING
 MACHINE SHUT OFF VALVES ARE REQUIRED TO BE ACCESSIBLE.
 FBC-PLB606.3
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-10-21 Cont ID  
Sent By cthroop Date 2021-10-21 Time 11:37 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-10-26 Cont ID  
Sent By cthroop Date 2019-10-26 Time 06:42 Rev Time 0.00
Received By cthroop Date 2019-10-26 Time 06:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By rmcdouga Date 2019-09-24 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2019-09-24 Time 07:08 Sent To  
Notes
2019-09-24 07:12:41NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOFING
 MATERIALS. ASPHALT SHINGLES WERE SPECIFIED FOR SLOPED
 ROOF. NOTHING WAS SPECIFIED ON THE PLANS FOR THE FLAT
 ROOF.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-12-11 Cont ID  
Sent By cthroop Date 2021-12-11 Time 12:05 Rev Time 0.00
Received By cthroop Date 2021-12-11 Time 10:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-10-22 Cont ID  
Sent By cthroop Date 2021-10-22 Time 17:20 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-03-29 Cont ID  
Sent By cthroop Date 2021-03-29 Time 14:53 Rev Time 0.00
Received By cthroop Date 2021-03-29 Time 11:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-12 Cont ID  
Sent By medwards Date 2020-06-12 Time 09:26 Rev Time 0.00
Received By medwards Date 2020-06-12 Time 09:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By shill Date 2019-10-25 Time 06:37 Rev Time 0.00
Received By shill Date 2019-10-25 Time 06:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-09-24 Cont ID  
Sent By rmcdouga Date 2019-09-24 Time 07:12 Rev Time 0.00
Received By rmcdouga Date 2019-09-24 Time 07:12 Sent To  
Notes
2019-09-24 07:14:30DIGITAL SIGNATURES WILL NEED TO BE REVIEWED AND
 APPROVED WHEN ALL PLAN SHEETS HAVE BEEN CORRECTED.

Review Stop Z ZONING
Rev No 5 Status P Date 2021-10-27 Cont ID  
Sent By fmittner Date 2021-10-27 Time 12:38 Rev Time 0.00
Received By fmittner Date 2021-10-27 Time 12:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2021-03-30 Cont ID  
Sent By fmittner Date 2021-03-30 Time 11:03 Rev Time 0.00
Received By fmittner Date 2021-03-30 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-06-12 Cont ID  
Sent By fmittner Date 2020-06-12 Time 11:21 Rev Time 0.00
Received By fmittner Date 2020-06-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By fmittner Date 2019-10-23 Time 16:58 Rev Time 0.00
Received By fmittner Date 2019-10-23 Time 16:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-06 Cont ID  
Sent By fmittner Date 2019-09-06 Time 14:14 Rev Time 0.00
Received By fmittner Date 2019-09-06 Time 14:14 Sent To  
Notes
2019-09-06 14:16:50SUBMIT SURVEY AND SITE PLAN, SHOW LOT COVERAGE AND
 SETBACKS.


Account Summary | Usage Policy | Privacy Policy