Plan Review Details - Permit 19070778
Plan Review Stops For Permit 19070778
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By jleahy Date 2019-08-22 Time 15:22 Rev Time 0.00
Received By jleahy Date 2019-08-22 Time 15:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-08 Cont ID  
Sent By jleahy Date 2019-08-08 Time 10:24 Rev Time 0.00
Received By jleahy Date 2019-08-08 Time 10:24 Sent To  
Notes
2019-08-08 10:28:19FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SORRY TO KEEP FAILING BUT I'M NOT SURE IF YOU ARE DOING
 ONE DOOR TO ATM OR ALL THE DOORS SHOWN ON PLAN.
 PLEASE CHANGE THE DESCRIPTION IF IT IS MORE THAN ONE
 DOOR.
  
 DOOR CLOSER YOU SUBMITTED DOES NOT LOOK TO BE ELECTRIC.
  
 IF THERE ARE DOOR LOCKS INVOLVED I NEED THE CUT SHEETS
 ON THE LOCKS, AND CONTROLLER
  
 CALL ME OR EMAIL ME WHEN YOU RESUBMIT AND I WILL DO
 ASAP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-22 Cont ID  
Sent By jleahy Date 2019-07-22 Time 14:33 Rev Time 0.00
Received By jleahy Date 2019-07-22 Time 14:33 Sent To  
Notes
2019-07-22 14:34:33PLANS NOT SIGNED
  
 PLANS NOT READABLE
  
 CUT SHEETS FOR LOCKS AND CONTROLER

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-01 Cont ID  
Sent By pleduc Date 2019-08-01 Time   Rev Time 0.00
Received By pleduc Date 2019-08-01 Time 14:59 Sent To E
Notes
2019-08-01 15:01:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 ) DEVICES ON EGRESS DOORS SHALL COMPLY WITH NFPA 101,
 CH 7, MEANS OF EGRESS
  
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By pleduc Date 2019-07-18 Time   Rev Time 0.00
Received By pleduc Date 2019-07-18 Time 15:08 Sent To E
Notes
2019-07-18 15:17:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS ARE TOO SMALL AND UNREADIBLE. A
 DETAILED LIFE SAFETY CAN NOT BE CONDUCTED.
  
 PLEASE ENLARGE THE PLANS TO A READABLE SIZE I.E.
 24"X36"
  
  
  
 2) PLEASE PROVIDE MANUFACTURER SPECIFICATION SHEETS.
  
  
  
 3) ACCESS CONTROL SHALL COMPLY WITH NFPA 101, CH 7,
 MEANS OF EGRESS WHERE APPLICABLE.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By jleahy Date 2019-08-22 Time 15:34 Rev Time 0.00
Received By jleahy Date 2019-08-22 Time 15:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-08 Cont ID  
Sent By jleahy Date 2019-08-08 Time 10:28 Rev Time 0.00
Received By jleahy Date 2019-07-30 Time 13:28 Sent To  
Notes
2019-07-31 13:28:23RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-31 Cont ID  
Sent By lmarchan Date 2019-07-31 Time 13:27 Rev Time 0.00
Received By lmarchan Date 2019-07-16 Time 11:16 Sent To  
Notes
2019-07-17 11:16:21ROUTED TO FIRE INBOX