Plan Review Details - Permit 19070773
Plan Review Stops For Permit 19070773
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-24 Cont ID  
Sent By lmarchan Date 2020-04-24 Time 11:00 Rev Time 0.00
Received By lmarchan Date 2020-04-21 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-10 Cont ID  
Sent By lmarchan Date 2020-04-10 Time 08:36 Rev Time 0.00
Received By lmarchan Date 2020-04-03 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-09 Cont ID  
Sent By pvalenti Date 2019-08-09 Time 15:05 Rev Time 0.00
Received By pvalenti Date 2019-07-16 Time 15:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-04-24 Cont ID  
Sent By medwards Date 2020-04-24 Time 10:54 Rev Time 0.00
Received By medwards Date 2020-04-24 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-04-07 Cont ID  
Sent By ccole Date 2020-04-07 Time 16:24 Rev Time 0.00
Received By medwards Date 2020-04-07 Time 16:24 Sent To  
Notes
2020-04-07 16:25:38REVIEW FBC-2017 MECHANICAL
 PERMIT- 19070773
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-401: NOTES 3 & 4 APPEAR TO IDENTIFY THE EF-2
 ON REVISION 8. REVISION 9 HAS THE SAME NOTES 3 & 4
 POINTING AT 2 CIRCLES, PLEASE CLARIFY REVISION 9
 DRAWINGS. FBC WPB 107.2.1
 2) SHEET M-401: NOTE 19 IS FOR AN EXHAUST FAN IN THE
 GENERATOR ROOM, NOTE 1 IS FOR A LOUVER IN THE WALL OF
 THE GENERATOR ROOM. THIS LOUVER SHOWS THE AIR BEING
 EXHAUSTED OUT. WOULD THIS NOT BE AN INTAKE FOR THE ROOM
 AND EXHAUST FAN? FBC WPB 107.2.1
 3) SHEET M-401: PLEASE SPEC OUT THE LOUVER THAT THE
 EXHAUST FAN DUCT (NOTE 20) IS CONNECTED TO. FBC WPB
 107.2.1
 4) SHEET M-401: NOTES 14 & 15 ARE NEW. PLEASE SUBMIT A
 DRAWING SHOWING THIS COMPLETE PIPING SYSTEM INCLUDING
 WHERE IT ORIGINATES FROM. FBC WPB 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-09 Cont ID  
Sent By ccole Date 2019-08-09 Time 15:01 Rev Time 0.00
Received By ccole Date 2019-08-09 Time 14:59 Sent To  
Notes
2019-08-09 15:02:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070773
 8/9/2019
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-101, 102, 103, & 104: THERE ARE MISSING
 FIRE DAMPERS WHERE DUCTS ARE PENETRATING THE FIRE-RATED
 MECHANICAL ROOM/CORRIDOR WALLS. THERE ARE ONLY
 MOTORIZED DAMPER SYMBOLS AT THESE LOCATIONS.
 2) M-401: THE GENERATOR ROOM MAKEUP AIR OPENING IS
 MISLABELED AS AN EXHAUST OUTLET- SEE NOTE #5.
 3) THE EXHAUST DUCT FROM THE TANK ROOM THAT IS
 PENETRATING THE FIRE-RATED GARAGE WALL AND RUNNING
 THROUGH THE GARAGE MUST BE HOUSED IN A FIRE- RATED
 ENCLOSURE FROM THE POINT OF PENETRATION TO THE OUTLET-
 SECTION 510.7.3 FB C M.
  
 510.7.3 WALL ASSEMBLIES.
 HAZARDOUS EXHAUST DUCT SYSTEMS THAT PENETRATE
 FIRE-RESISTANCE-RATED WALL ASSEMBLIES SHALL BE ENCLOSED
 IN FIRE-RESISTANCE-RATED CONSTRUCTION FROM THE POINT OF
 PENETRATION TO THE OUTLET TERMINAL, EXCEPT WHERE THE
 INTERIOR OF THE DUCT IS EQUIPPED WITH AN APPROVED
 AUTOMATIC FIRE SUPPRESSION SYSTEM. DUCTS SHALL BE
 ENCLOSED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING REQUIREMENTS FOR SHAFT CONSTRUCTION AND SUCH
 ENCLOSURE SHALL HAVE A MINIMUM FIRE-RESISTANCE RATING
 OF NOT LESS THAN THE HIGHEST FIRE-RESISTANCE-RATED WALL
 ASSEMBLY PENETRATED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-04-24 Cont ID  
Sent By medwards Date 2020-04-24 Time 10:57 Rev Time 0.00
Received By medwards Date 2020-04-24 Time 10:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By medwards Date 2020-04-10 Time 07:25 Rev Time 0.00
Received By medwards Date 2020-04-10 Time 07:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-08-09 Cont ID  
Sent By pvalenti Date 2019-08-09 Time 15:03 Rev Time 0.00
Received By pvalenti Date 2019-08-09 Time 15:03 Sent To  
Notes
2019-08-09 15:05:03PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURES APPROVED FOR THIS REVIEW ONLY.