Plan Review Details - Permit 19070733
Plan Review Stops For Permit 19070733
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-02 Cont ID  
Sent By dbattles Date 2019-08-02 Time 15:55 Rev Time 0.00
Received By dbattles Date 2019-08-02 Time 15:59 Sent To  
Notes
2019-08-02 15:55:40BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070733
 REVIEWED: AUGUST 2, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
  
 107.5.3 FBC[AMENDED]PLEASE PROVIDE STANDARD FENCE
 DETAILS TO INCLUDE HEIGHT, POST SPACING, GATE POSTS AND
 CONNECTION TO GROUND.
  
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2019-07-19 Cont ID  
Sent By rrossano Date 2019-07-19 Time   Rev Time 0.00
Received By rrossano Date 2019-07-19 Time   Sent To FIRE
Notes
2019-07-19 07:30:00PASSED WITH PROVISOS:
  
 PLEASE ADDRESS ZONING COMMENTS.
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. MORE INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-22 Cont ID  
Sent By pleduc Date 2019-07-22 Time   Rev Time 0.00
Received By pleduc Date 2019-07-22 Time 10:47 Sent To B
Notes
2019-07-22 10:56:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE APPLICATION INDICATES "CONSTRUCTION TRAILER
 TEMPORARY FENCE"
  
 THERE IS NO CLEAR INDICATION OF THE LOCATION OF THE
 TRAILER.
  
 PLEASE REVIEW AND CLARFY THE INTENT OF THE APPLICATION;
 IF FOR A TRAILER AND FENCE, PLEASE PROVIDE EXACT
 LOCATION OF THE CONSTRUCTION TRAILER WITH DIMENSIONS TO
 PROPERTY LINES, NEIGHBOR BUILDINGS, PROPOSED BUILDING,
 ETC.
  
  
  
 2) THERE IS A GATE INDICATED IN THE MIDDLE OF THE
 VACANT FIELD. THERE IS NO FD ACCESS ROAD INTO THE
 PROPSED FENCED SITE.
  
 PER NFPA 1
  
 18.2.3 FIRE DEPARTMENT ACCESS ROADS.
 18.2.3.1 REQUIRED ACCESS.
 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL
 BE PROVIDED
 FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING
 HEREAFTER
 CONSTRUCTED OR RELOCATED.
 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST
 OF ROADWAYS, FIRE
 LANES, PARKING LOT LANES, OR A COMBINATION THEREOF.
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) THERE ARE NO DIMENSIONS INDICATED FOR THE GATE.
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) KNOX PADLOCKS ARE RECOMMENDED FOR EACH TO BE USED IN
 CONJUCTION WITH YOUR LOCKS SO YOUR LOCK OR CHAIN WILL
 NOT BE CUT IN THE EVENT OF NEEDED EMERGENCY INCIDENT
 ACCESS.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-02 Cont ID  
Sent By dbattles Date 2019-08-02 Time 15:55 Rev Time 0.00
Received By dbattles Date 2019-07-16 Time 11:18 Sent To  
Notes
2019-07-17 11:18:15ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By jroach Date 2019-07-18 Time 10:02 Rev Time 0.00
Received By jroach Date 2019-07-18 Time 10:02 Sent To ENG
Notes
2019-07-18 10:02:46ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.18.2019
 PERMIT NO.: 19070731
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE LOCATION OF THE PROPOSED CONSTRUCTION FENCE IS
 SHOWN ON A PROPERTY OWNED BY VERDEX CENTREPARK LLC; THE
 PERMIT APPLICATION INDICATES AND IS SIGNED BY THE OWNER
 OR AGENT OF CENTREPARK VENTURE PARTNERS LLC. THE PERMIT
 APPLICATION NEEDS TO BE SIGNED BY THE APPROPRIATE
 PROPERTY OWNER, OR AGREEMENTS FROM THE OTHER PROPERTY
 OWNER MAY NEED TO BE PROVIDED.
  
 2. PLEASE CLARIFY THE PURPOSE OF THIS CONSTRUCTION
 FENCE; IS THIS ASSOCIATED WITH THE RESIDENTIAL
 DEVELOPMENT PROPOSED AT 1500 CENTREPARK BOULEVARD?
  
 3. PURSUANT TO SEC. 94-316(D)(2)C.5. OF THE CITY?S
 ZONING AND LAND DEVELOPMENT REGULATIONS, DETAILS
 REGARDING THE SCREENING SHALL BE PROVIDED. SCREENING
 SHALL BE SUBSTANTIAL ENOUGH TO AVOID RIPS AND TEARS AND
 SHALL HAVE NO LESS THAN 85% OPACITY.
  
 4. THE LOCATION OF THE PROPOSED CONSTRUCTION FENCE
 EXTENDS INTO A UTILITY EASEMENT. AS SUCH, EASEMENT
 CONSENT SHALL BE OBTAINED FROM THE CITY?S PUBLIC
 UTILITIES DEPARTMENT, AS WELL AS ALL OF THE OTHER
 UTILITY COMPANIES (COMCAST, FP&L, FLORIDA PUBLIC
 UTILITIES ? GAS, AND AT&T).
  
 THE FOLLOWING ARE PROVIDED FOR INFORMATIONAL PURPOSES
 ONLY:
  
 A. TEMPORARY CONSTRUCTION FENCES MAY NOT BE ERECTED
 UNTIL A DEMOLITION PERMIT OR BUILDING PERMIT FOR THE
 LAND DISTURBING CONSTRUCTION OR LAND DEVELOPMENT
 ACTIVITIES HAS BEEN ISSUED, AND NO MORE THAN TEN DAYS
 PRIOR TO THE COMMENCEMENT OF LAND DISTURBING
 CONSTRUCTION OR LAND DEVELOPMENT ACTIVITIES. IF LAND
 DISTURBING CONSTRUCTION OR LAND DEVELOPMENT ACTIVITIES
 DO NOT COMMENCE WITHIN TEN DAYS OF FENCE INSTALLATION,
 THEN, WITHIN 15 DAYS OF THE TEN-DAY PERIOD, THE FENCE
 SHALL BE REMOVED AND THE SITE SHALL BE TILLED AND
 PLANTED WITH GROUND COVER TO INCLUDE SODDING OR SEEDING
 WHICH SHALL HAVE IRRIGATION AND SHALL BE MAINTAINED IN
 ACCORDANCE WITH SECTIONS 74-2 AND 94-446 OF THIS CODE.
  
 B. IN THE EVENT THAT THE DEMOLITION PERMIT OR BUILDING
 PERMIT EXPIRES, ALL TEMPORARY CONSTRUCTION FENCES SHALL
 BE REMOVED WITHIN TEN DAYS OF THE PERMIT EXPIRATION
 DATE, AND WITHIN 15 DAYS OF REMOVAL OF THE FENCES, THE
 SITE SHALL BE BROUGHT TO GRADE, TILLED AND PLANTED WITH
 GROUND COVER TO INCLUDE SODDING OR SEEDING WHICH SHALL
 HAVE IRRIGATION AND SHALL BE MAINTAINED IN ACCORDANCE
 WITH SECTION 74-2 AND 94-446 OF THIS CODE. ALL
 TEMPORARY CONSTRUCTION FENCING SHALL BE MAINTAINED IN A
 SATISFACTORY MANNER BY THE PERMITTEE OR LANDOWNER,
 DURING THE ENTIRE PERIOD OF THE LAND DISTURBING
 CONSTRUCTION AND LAND DEVELOPMENT ACTIVITIES, TO ENSURE
 ADEQUATE PERFORMANCE, TO PREVENT NUISANCE CONDITIONS
 AND TO MAINTAIN THE PUBLIC HEALTH, SAFETY AND WELFARE.
  
 C. TEMPORARY CONSTRUCTION FENCES SHALL BE INSTALLED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE AND
 OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA)
 STANDARDS.
  
 D. ALL TEMPORARY CONSTRUCTION FENCING SHALL BE
 MAINTAINED IN A SATISFACTORY MANNER BY THE PERMITTEE OR
 LANDOWNER, DURING THE ENTIRE PERIOD OF THE LAND
 DISTURBING CONSTRUCTION AND LAND DEVELOPMENT
 ACTIVITIES, TO ENSURE ADEQUATE PERFORMANCE, TO PREVENT
 NUISANCE CONDITIONS AND TO MAINTAIN THE PUBLIC HEALTH,
 SAFETY AND WELFARE.
  
 E. GATES SHALL BE CHAINED AND LOCKED WITH A LOCK
 SUBSTANTIAL ENOUGH TO ENSURE CLOSURE AND SECURITY WHEN
 WORKERS ARE NOT ON THE JOB SITE.
  
 F. SCREENING GRAPHICS (IF ANY) SHALL BE APPROVED WITH
 THE SUBMITTAL OF A SEPARATE PERMIT APPLICATION PURSUANT
 TO THE PROVISIONS OF CHAPTER 94, ARTICLE XIII, SIGN
 REGULATIONS, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS OF THIS CODE.
  
 G. ALL WIND SCREENING MATERIALS SHALL BE REMOVED UPON
 THE ISSUANCE OF A HURRICANE WARNING FOR AN AREA
 INCLUDING THE CITY. SCREENING MATERIALS SHALL BE
 REINSTALLED NOT MORE THAN TEN DAYS AFTER THE HURRICANE
 THREAT HAS ENDED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved