Plan Review Details - Permit 19070730
Plan Review Stops For Permit 19070730
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-08 Cont ID  
Sent By jbrooks Date 2019-08-08 Time 08:33 Rev Time 0.00
Received By jbrooks Date 2019-08-08 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-23 Cont ID  
Sent By jbrooks Date 2019-07-23 Time 14:09 Rev Time 0.00
Received By jbrooks Date 2019-07-23 Time 14:09 Sent To  
Notes
2019-07-23 14:10:11JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.FBC B 107.2.1. PLEASE CORRECT THE FOLLOWING; ON THE
 SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR
 ASSEMBLIES: COLUMN HEADING ?SHUTTER SPAN?; SEE TYPICAL
 (1) HV BLADE SHUTTER ELEVATION; SHEET 5 OF PRODUCT
 APPROVAL FL1850. COLUMN HEADING ?ANCHOR SPACING?;
 PROVIDE INFORMATION FROM PAGE 12 OF PRODUCT APPROVAL
 FL1850 TAPCON W/ADVANCED THREADFORM TECHNOLOGY REQUIRES
 A .9 FACTOR... COLUMN HEADING ?SHUTTER INSTALLED
 VERTICAL/HORIZONTAL?: ACCORDION SHUTTERS ARE INSTALLED
 VERTICALLY AS PER PRODUCT APPROVAL FL1580.
 2. FBC B 107.2.1. PLEASE VERIFY THE INFORMATION ON THE
 SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR
 ASSEMBLIES FOR PRODUCT APPROVAL FL11291. EXAMPLE: PAGE
 13 TABLE 4 CONCRETE ?? & 5/16? ELCO ULTRACON SPANS
 16?-0 < 16?-6? 40 (PSF) ANCHOR SPACING IS 9.0?. PLEASE
 NOTE SCREEN PANELS CAN BE MOUNTED VERTICALLY OR
 HORIZONTAL. PLEASE USED APPROPRIATE INSTALLATION METHOD
 AND SPAN.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-08 Cont ID  
Sent By jbrooks Date 2019-08-08 Time 08:34 Rev Time 0.00
Received By jbrooks Date 2019-08-05 Time 13:59 Sent To  
Notes
2019-08-06 13:59:38RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-23 Cont ID  
Sent By jbrooks Date 2019-07-23 Time 14:10 Rev Time 0.00
Received By jbrooks Date 2019-07-16 Time 09:54 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved