Plan Review Details - Permit 19070609
Plan Review Stops For Permit 19070609
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-16 Cont ID  
Sent By cthroop Date 2019-10-16 Time 12:43 Rev Time 0.00
Received By cthroop Date 2019-10-16 Time 12:43 Sent To  
Notes
2019-10-16 12:45:05PROVISO: REMOVE CABANA, PERGOLA/DECK & SPIRAL STAIRCASE
 FROM SUBMITTAL. THESE ITEMS WILL BE SUBMITTED AS A
 REVISION. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-15 Cont ID  
Sent By cthroop Date 2019-10-15 Time 11:41 Rev Time 0.00
Received By cthroop Date 2019-10-10 Time 11:46 Sent To  
Notes
2019-10-15 11:46:11BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 2. SPIRAL STAIRCASE SHOP DRAWINGS SHALL BE REVIEWED AND
 APPROVED BY A LICENSED FLORIDA DESIGN PROFESSIONAL.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 3. PROVIDE A ROOF FRAMING PLAN FOR THE CABANA.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-31 Cont ID  
Sent By cthroop Date 2019-07-31 Time 11:44 Rev Time 0.00
Received By cthroop Date 2019-07-31 Time 07:54 Sent To  
Notes
2019-07-31 12:56:37BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. INCORRECT CODE REFERENCE STATED IN NOTE #2 PLAN PAGE
 E-1.
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION.
  
 3. SCOPE OF WORK INCLUDES DEMO OF EXISTING CABANA. THIS
 WORK SHALL BE BY SEPERATE PERMIT.
 PLEASE SEE THE "DEMOLITION PERMIT APPLICATION
 CHECKLIST" WHICH YOU CAN FIND AT THE FOLLOWING WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 4. PROVIDE SITE PLAN.
  
 5. PROVIDE TWO COPIES OF A RECENT SURVEY.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By jpearson Date 2019-10-02 Time 08:25 Rev Time 0.00
Received By jpearson Date 2019-10-01 Time 13:02 Sent To  
Notes
2019-10-02 08:25:26PASSED WITH PROVISOS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-30 Cont ID  
Sent By jpearson Date 2019-07-30 Time 16:35 Rev Time 0.00
Received By jpearson Date 2019-07-30 Time 06:41 Sent To  
Notes
2019-07-30 15:53:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 2. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 3. NOTE 27 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 7. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6
 8. DETAIL FOR DISHWASHER / DISPOSAL DOES NOT PERMIT FOR
 GFCI PROTECTION OF DISHWASHER. PROVIDE GFCI PROTECTION
 FOR DISHWASHER. NEC 210.8(D); FBC RE E3902.10
 9. RECEPTACLE OUTLETS IN BATHROOMS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.1
 10. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 11. PLAN DOES NOT SHOW LOCATION OF PANEL B. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 12. PLAN DOES NOT SHOW LOCATION OF LAUNDRY CIRCUITS
 SHOWN IN PANEL SCHEDULEL. PROVIDE CORRECTION. WPB FBC
 107.2.1
 13. PLAN SHOWS WHAT APPEARS TO BE STANDARD RECESS
 LIGHTS IN CLOSET. PER CODE, LIGHTING WITH OPEN OR
 PARTIALLY ENCLOSED LAMPS AND PENDANT LUMINAIRES OR
 LAMPHOLDERS SHALL NOT BE PERMITTED IN CLOTHES CLOSETS.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 14. PLAN DOES NOT SHOW LOCATION OF AC EQUIPMENT.
 PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING
 OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER
 CODE. NEC 210.63; FBC RE E3901.12
 15. RECEPTACLES INSTALLED OUTDOORS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.3
 16. RISER DIAGRAM DOES NOT PROVIDE WIRE SIZE TO MDP
 FROM METER. PROVIDE CORRECTION. WPB FBC 107.2.1
 17. RISER DIAGRAM SHOWS 4 CONDUCTORS AND AN EQUIPMENT
 GROUND TO SUB-PANELS. IS THIS A 3 PHASE SYSTEM? LOAD
 CALCULATION AND PANEL SCHEDULES SHOW A SINGLE PHASE
 SERVICE. CORRECT DISCREPANCY. WPB FBC 107.2.1; NEC
 215.5
 18. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-10-09 Cont ID  
Sent By lcrespo Date 2019-10-09 Time 16:07 Rev Time 0.00
Received By lcrespo Date 2019-09-25 Time 16:08 Sent To M
Notes
2019-09-25 16:08:3610/09/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-31 Cont ID  
Sent By cthroop Date 2019-07-31 Time 13:24 Rev Time 0.00
Received By cthroop Date 2019-07-31 Time 09:39 Sent To  
Notes
2019-07-31 13:29:55GAS PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 1. GAS SHALL BE BY SEPERATE PERMIT.
  
 PROVIDE THE FOLLOWING INFORMATION FOR YOUR GAS PERMIT
 AND REVIEW.
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE
 USED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-RES. SEC.G2426 THROUGH G2439.
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FBC-RES. SEC.G2408.1.
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-16 Cont ID  
Sent By cthroop Date 2019-10-16 Time 13:36 Rev Time 0.00
Received By cthroop Date 2019-10-16 Time 12:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-15 Cont ID  
Sent By cthroop Date 2019-10-15 Time 12:06 Rev Time 0.00
Received By cthroop Date 2019-09-20 Time 15:08 Sent To  
Notes
2019-09-23 15:08:36R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-31 Cont ID  
Sent By cthroop Date 2019-07-31 Time 13:30 Rev Time 0.00
Received By cthroop Date 2019-07-12 Time 12:49 Sent To  
Notes
2019-07-15 12:49:15R05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By cmontell Date 2019-10-11 Time 15:05 Rev Time 0.00
Received By cmontell Date 2019-10-11 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-27 Cont ID  
Sent By cmontell Date 2019-07-27 Time 07:26 Rev Time 0.00
Received By cmontell Date 2019-07-27 Time 07:23 Sent To  
Notes
2019-07-27 07:25:50MECHANICAL PLAN REVIEW FAIL
  
 NEED MECHANICAL PLAN PER WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, 6TH EDITION (2017),
 CHAPTER 1, ADMINISTRATION, SEC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-25 Cont ID  
Sent By lcrespo Date 2019-09-25 Time 16:08 Rev Time 0.00
Received By lcrespo Date 2019-09-25 Time 16:08 Sent To  
Notes
2019-09-25 16:13:2709/25/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-31 Cont ID  
Sent By cthroop Date 2019-07-31 Time 13:21 Rev Time 0.00
Received By cthroop Date 2019-07-31 Time 07:54 Sent To  
Notes
2019-07-31 13:24:16PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 1. PLUMBING SUPPLY ISO SHOWS EXISTING WATER HEATER.
  
 2. PLAN PAGE P-2 SHOWS WATER HEATER DETAIL.
  
 IS THE WATER HEATER BEING REPLACED?
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-16 Cont ID  
Sent By rfalcone Date 2019-10-16 Time 13:23 Rev Time 0.00
Received By rfalcone Date 2019-10-16 Time 13:23 Sent To I
Notes
2019-10-16 13:25:22ONLY INTERIOR RENOVATIONS. RF
  
 PROVISO: REMOVE CABANA, PERGOLA/DECK & SPIRAL STAIRCASE
 FROM SUBMITTAL. THESE ITEMS WILL BE SUBMITTED AS A
 REVISION.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-09-27 Cont ID  
Sent By rfalcone Date 2019-09-27 Time 09:24 Rev Time 0.00
Received By rfalcone Date 2019-09-27 Time 09:24 Sent To I
Notes
2019-09-27 09:26:4109/27/19 FAILED.
  
 THE PERGOLA ACCESSORY STRUCTURE ON THE EASTERN PORTION
 OF THE SUBJECT PROPOERTY IS ENCROACHING THE REQUIRED 5
 FT SIDE SETBACK. PLEASE REVISE PLANS TO MEET CODE
 REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  