Plan Review Details - Permit 19070552
Plan Review Stops For Permit 19070552
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-26 Cont ID  
Sent By cthroop Date 2019-11-26 Time 06:56 Rev Time 0.00
Received By cthroop Date 2019-11-25 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 08:04 Rev Time 0.00
Received By cthroop Date 2019-08-13 Time 15:53 Sent To  
Notes
2019-08-14 08:08:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER OF RECORD TO SIGN AND SEAL PLANS.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND
 EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 YOU MAY CHOOSE TO DEFER THESE PRODUCT APPROVALS
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-01-06 Cont ID  
Sent By jleahy Date 2020-01-06 Time 12:23 Rev Time 0.00
Received By jleahy Date 2020-01-06 Time 12:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-12-30 Cont ID  
Sent By ppetty Date 2019-12-30 Time 11:02 Rev Time 0.00
Received By ppetty Date 2019-12-30 Time 11:01 Sent To P
Notes
2019-12-30 11:02:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.
 2.
 3.
 4. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, FEEDERS
 THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THIS PANEL. NEC 225.31, 225.32 250.32
 NEED METAL PIPE OR GROUND WIRE TO GARAGE
 5.
 6.
 7. SHOW LOCATION OF MINI-SPLIT UNIT ON ELECTRICAL PLAN.
 110.26 DISCONNECT BEHIND UNIT.OUTLET FOR UNIT MISSING
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-11-20 Cont ID  
Sent By ppetty Date 2019-11-20 Time 13:20 Rev Time 0.00
Received By ppetty Date 2019-11-20 Time 13:20 Sent To  
Notes
2019-11-20 13:20:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.
 2.
 3.
 4. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, FEEDERS
 THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THIS PANEL. NEC 225.31, 225.32 250.32
 NEED METAL PIPE OR GROUND WIRE TO GARAGE
 5.
 6.
 7. SHOW LOCATION OF MINI-SPLIT UNIT ON ELECTRICAL PLAN.
 110.26 DISCONNECT BEHIND UNIT.OUTLET FOR UNIT MISSING
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-07 Cont ID  
Sent By jpearson Date 2019-08-07 Time 10:32 Rev Time 0.00
Received By jpearson Date 2019-08-07 Time 08:37 Sent To  
Notes
2019-08-07 10:31:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30
 2. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, PROVIDE
 LOCATION OF PANEL TO CONFIRM CODE COMPLIANCE. PROVIDE
 PANEL SCHEDULE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 3. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, PROVIDE
 GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING
 OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT.
 NEC 250.32; FBC RE3607.3
 4. IF A PANEL IS TO BE INSTALLED IN THE GARAGE, FEEDERS
 THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THIS PANEL. NEC 225.31, 225.32
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 6. LOAD SCHEDULE INDICATES THAT THE BATHROOM RECEPTACLE
 WILL BE ON A 15 AMP CIRCUIT. A MINIMUM OF ONE 20 AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE
 E3703.4
 7. SHOW LOCATION OF MINI-SPLIT UNIT ON ELECTRICAL PLAN.
 PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING
 OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER
 CODE. NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 13:37 Rev Time 0.00
Received By gjohnson Date 2019-12-17 Time 14:17 Sent To  
Notes
2019-12-18 14:17:57RESUB ROUTED TO PPETTY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-27 Cont ID  
Sent By cpuell Date 2019-11-27 Time 15:33 Rev Time 0.00
Received By cpuell Date 2019-11-08 Time 16:29 Sent To  
Notes
2019-11-12 16:29:56R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 08:10 Rev Time 0.00
Received By cthroop Date 2019-07-11 Time 15:38 Sent To  
Notes
2019-07-12 15:38:46R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-11-26 Cont ID  
Sent By cthroop Date 2019-11-26 Time 06:55 Rev Time 0.00
Received By cthroop Date 2019-11-25 Time 15:37 Sent To  
Notes
2019-11-26 06:55:49MU-2019-028391-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 08:08 Rev Time 0.00
Received By cthroop Date 2019-08-13 Time 15:53 Sent To  
Notes
2019-08-14 08:10:00PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-11-26 Cont ID  
Sent By cthroop Date 2019-11-26 Time 07:34 Rev Time 0.00
Received By cthroop Date 2019-11-25 Time 15:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-08-09 Cont ID  
Sent By cmontell Date 2019-08-09 Time 14:40 Rev Time 0.00
Received By cmontell Date 2019-08-09 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-01-03 Cont ID  
Sent By gjohnson Date 2020-01-03 Time 13:36 Rev Time 0.00
Received By gjohnson Date 2020-01-03 Time 13:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-11-21 Cont ID  
Sent By gjohnson Date 2019-11-21 Time 17:27 Rev Time 0.00
Received By gjohnson Date 2019-11-21 Time 10:59 Sent To  
Notes
2019-11-21 18:15:262ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SIZING ON THE SANITARY ISOMETRIC IS NOT CODE
 COMPLIANT 3" IS REQUIRED TO THE WATER CLOSET THE ISO
 SHOWS 2" THEN REDUCES TO 11/2" THEN BACK UP TO 2" FOR
 THE VENT IT SHALL REMAIN 2" ALL THE WAY THRU THE ROOF
 11/4 SHALL NOT BE USED ON SANITARY ISOMETRIC PER FBC
 RES P2713.1 BATHTUB WASTE OUTLETS AND OVERFLOWS.
 BATHTUBS SHALL BE EQUIPPED WITH A WASTE OUTLET AND AN
 OVERFLOW OUTLET. THE OUTLETS SHALL BE CONNECTED TO
 WASTE TUBING OR PIPING NOT LESS THAN 11/2 INCHES (38
 MM) IN DIAMETER. THE WASTE OUTLET SHALL BE EQUIPPED
 WITH A WATER-TIGHT STOPPER.
 P2714.1 SINK WASTE OUTLETS. SINKS SHALL BE PROVIDED
 WITH WASTE OUTLETS NOT LESS THAN 11/2 INCHES (38 MM) IN
 DIAMETER. A STRAINER, CROSSBAR OR OTHER DEVICE SHALL BE
 PROVIDED TO RESTRICT THE CLEAR OPENING OF THE WASTE
 OUTLET.
 P3005.1.4
  
 2. PROVIDE DETAIL FOR SHOWER PAN SHOWING COMPLIANCE
 WITH FBC RES P2709.1, P2709.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-09 Cont ID  
Sent By abelisle Date 2019-08-09 Time 06:21 Rev Time 0.00
Received By abelisle Date 2019-08-08 Time 16:40 Sent To  
Notes
2019-08-09 06:24:488/9/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) SHOW LOCATION OF HOT WATER HEATER
  
 2) REVISE PLUMBING ISOMETRIC TO MEET MINIMUM FBC 2017
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-27 Cont ID  
Sent By awooten Date 2019-11-27 Time   Rev Time 0.00
Received By awooten Date 2019-11-27 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-26 Cont ID  
Sent By awooten Date 2019-07-26 Time   Rev Time  
Received By awooten Date 2019-07-26 Time   Sent To  
Notes
2019-07-26 11:09:52************ZONING REVIEW FAILED**********
  
 PROVIDE A COPY OF SURVEY.
  
 WITH CONVERSION OF GARAGE INTO A DEN, WHERE WILL THE
 REQUIRED PARKING BE LOCATED?
  
 ADDITIONAL COMMENTS MAY FOLLOW ADDITIONAL REVIEW.
  