| Plan Review Stops For Permit 19070551 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-09-26 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-09-26 |
Time |
12:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-08-26 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-08-26 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-09-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-09-26 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-09-26 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2019-09-26 12:34:07 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PROVISO! | | | | | | SPACE AVOCE THE METER AND DISCONNECT IN THE ELECTRICAL | | | ROOM IS DEDICATED SPACE. F/A PANEL CANNOT BE INSTALLED | | | IN THE LOCATION SHOWN ON DRAWINGS. | | | 110.26(E)(1)(A) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-08-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-08-23 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-08-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-08-08 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-09-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-09-26 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-09-17 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-09-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-09-05 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-08-06 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-08-26 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-08-26 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2019-08-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-16 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-08-16 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2019-08-16 15:36:37 | MECHANICAL REVIEW | | | | | | APPROVED PER CHRIS COLE (REMOTELY) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-09-26 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-09-26 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-09-26 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2019-09-26 09:18:11 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | 1. PLUMBING PROVISO: PER WPB FBC 107.2.1 AND WPB FBC | | | 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL, AS AN | | | ADDENDUM TO A4.21, AN 8-1/2 INCH X 11 INCH SKETCH OF | | | DETAIL 3/A4.21 NOTING IN ADDITION TO THE CLEAR FLOOR | | | SPACE, THE REQUIRED TURNING SPACE TO COMPLY WITH FBC | | | ACC 304. THE DOCUMENTS SHALL BE SUBMITTED AS A | | | SUPPORTING DOCUMENT WITH REQUIRED ARCHITECTS DIGITAL | | | SIGNATURE, APPROVED AND ON SITE PRIOR TO FINAL | | | INSPECTION. SEE RED LINED COMMENTS ON PLAN SHEETS A4.21 | | | AND TP4. PROCEED AT YOUR OWN RISK. | | | 2. VALVING ARRANGEMENT AT SINK SHALL COMPLY WITH THE | | | MINIMUM REQUIREMENTS OF FBC PL 606.1. SEE REDLINED | | | COMMENTS ON PLAN SHEET TP4. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-09-05 |
|
|
Cont ID |
|
| Sent By |
Tim Hunt |
Date |
2019-09-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-09-26 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2019-09-05 17:16:36 | PLUMBING 1ST REVIEW**DENIED** | | | 1-PLUMBING SUB PERMIT APPLICATION REQUIRED. FBC 107.1 | | | 2-SHT. A0.04 LIST 1 OF THE TOILET DISPENSER DETAILS | | | SHOWING THE MEASUREMENT (7?-9?) TO THE FRONT EDGE AND | | | NOT THE CENTER. FBC-ACC 604.7 | | | 3-SHT. A0.12 NOTE #18 UNDER ACCESSIBILITY CALLS FOR THE | | | TOILET DISPENSER MOUNTING AS 12? FROM THE LIP OF TOILET | | | AND NOT 7?-9? AS REQUIRED IN FBC-ACC 604.7 | | | 4-SHT. A0.12 NOTE #21 UNDER ACCESSIBILITY CALLS FOR THE | | | GRAB BAR MOUNTING ABOVE THE FLOOR AND NOT TO THE TOP OF | | | THE GRIPPING SURFACE. FBC-ACC 606.5 | | | 5-SHT. A0.12 NOTE #25 CALLS TO INSULATE THE HOT WATER | | | LINE AND DRAIN LINE. THE COLD LINE IS ALSO REQUIRED. | | | FBC-ACC 606.5 | | | 6-TANKLESS WATER HEATER MUST BE CAPABLE OF PRODUCING A | | | HEAT RISE TO PRODUCE HOT WATER (MIN 110F) WITH 2.2 GPM | | | AND NOT THE .5GPM AS CALLED OUT. THIS WATER HEATER IS | | | DESIGNED FOR BATHROOM LAVATORIES WHERE .5 GPM IS | | | ACCEPTABLE. PLEASE PROVIDE A WATER HEATER THAT MEETS | | | FBC-PLB 604.3, 607.1 | | | 7-PROVIDE SHUT OFF VALVES AT THE COLD WATER DOWN FEED | | | AND THE HOT WATER HEATER INLET. FBC-PLB 606.1 | | | 8) SHOW ON PLAN THE CLEAR FLOOR SPACE IN FRONT OF THE | | | SINK. FBC-ACC 606 | | | 9) ADD HAMMER ARRESTORS OR PROVIDE NOTE THAT HAMMER | | | ARRESTORS ARE TO BE USED ON ALL QUICK CLOSING VALVES. | | | FBC-PLB 604.9 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH ( CGA SOLUTIONS) | | | [email protected] | | | 561-248-2703 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-09-26 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-09-26 |
Time |
12:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-09-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-09-05 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-09-05 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2019-09-05 17:19:52 | SIGNATURES WILL BE REVIEWED WHEN NEW SHEETS ARE | | | APPROVED. | | 2019-08-26 09:33:59 | ARCHITECTURAL SHEETS SIGNED AND SEALED ELECTRONICALLY. | | | JW 8/26/2019 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2019-08-29 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-08-29 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-08-29 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|