Plan Review Details - Permit 19070496
Plan Review Stops For Permit 19070496
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-07-15 Cont ID  
Sent By rmcdouga Date 2019-07-15 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2019-07-15 Time 07:11 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-04 Cont ID  
Sent By cpuell Date 2019-08-04 Time 11:14 Rev Time 0.00
Received By cpuell Date 2019-08-01 Time 14:02 Sent To  
Notes
2019-08-02 14:02:42RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-15 Cont ID  
Sent By rmcdouga Date 2019-07-15 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2019-07-11 Time 15:57 Sent To  
Notes
2019-07-12 15:57:29ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-04 Cont ID  
Sent By abelisle Date 2019-08-04 Time 05:57 Rev Time 0.00
Received By abelisle Date 2019-08-04 Time 05:57 Sent To I
Notes
2019-08-04 08:52:048/4/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 ATELYO BELISLE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-13 Cont ID  
Sent By abelisle Date 2019-07-13 Time 07:02 Rev Time 0.00
Received By abelisle Date 2019-07-13 Time 04:56 Sent To  
Notes
2019-07-13 05:07:597/13/19 DENIED
  
 PLUMBING SHALL BE INSTALLED BY A LICENSED PLUMBING
 CONTRACTOR PER WEST PALM BEACH AMENDMENTS TO FBC 2017
 105.1
  
 THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 PLEASE
 PROVIDE SCOPE OF WORK TO BE DONE
  
 THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING ON-SITE
 BUILT-UP SHOWER RECEPTORS SHALL BE LINED WITH ONE OF
 THE FOLLOWING MATERIALS:
  
 1. SHEET LEAD.
 2. SHEET COPPER.
 3. PLASTIC LINER MATERIAL THAT COMPLIES WITH ASTM D4068
 OR ASTM D4551.
 4. HOT MOPPING IN ACCORDANCE WITH SECTION P2709.2.3.
 5. SHEET-APPLIED LOAD-BEARING, BONDED WATERPROOF
 MEMBRANES THAT COMPLY WITH ANSI A118.10.
  
 THE LINING MATERIAL SHALL EXTEND NOT LESS THAN 2 INCHES
 (51 MM) BEYOND OR AROUND THE ROUGH JAMBS AND NOT LESS
 THAN 2 INCHES (51 MM) ABOVE FINISHED THRESHOLDS.
 SHEET-APPLIED LOAD-BEARING, BONDED WATERPROOF MEMBRANES
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 NOTE: SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN
 PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING
 AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION
 PLACE SOME PEA GRAVEL OVER WEEP HOLES SO THE MORTAR
 DOES
 NOT COVER THEM PER MANUFACTURES SPECIFICATIONS.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
  
  