Plan Review Details - Permit 19070494
Plan Review Stops For Permit 19070494
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By jwitmer Date 2019-10-22 Time 11:03 Rev Time 0.00
Received By jwitmer Date 2019-10-21 Time 10:59 Sent To  
Notes
2019-10-22 11:03:482017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070494
 ADD: 1921 S DIXIE HWY.
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 22, 2019
 ACTION: BUILDING PROVISO
  
 1A) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 1B) DEFERRED SUBMITTAL: 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS/ STOREFRONT SYSTEMS.
  
 1C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 JAMES A. WITMER BN, PX, CBO / SENIOR COMMERCIAL
 COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By jwitmer Date 2019-08-19 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2019-08-13 Time 12:10 Sent To  
Notes
2019-08-19 07:29:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070494
 ADD: 1921 S DIXIE HWY.
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 13, 2019
 ACTION: DENIED
  
 1) THE LS-1.1 FIRST FLOOR LIFE SAFETY SHEET:
 1A) THE CODE DATA HAS REQUIREMENTS FOR TABLE 601 FOR
 BUILDING ELEMENTS BUT NOT FOR:
  
 1A)(1) MISSING THE REQUIREMENTS FROM THE 2017 FBC-B
 TABLE 602 THE FIRE RESISTANCE REQUIREMENTS FOR EXTERIOR
 WALLS BASED ON FIRE SEPARATION DISTANCE.
  
 1A)(2) THE SURVEY INDICATES THIS IS A 2 STORY BUILDING
 PLEASE ALSO CONSIDER THE REQUIREMENTS FOR FIRE
 RESISTANCE RATING REQUIREMENTS FOR HORIZONTAL
 ASSEMBLIES BETWEEN FIRE AREAS, TABLE 707.3.10 OF THE
 2017 FBC-B. PLEASE PROVIDE WHAT OCCUPANCY IS ON THE 2ND
 FLOOR TO KNOW WHAT THE FIRE RESISTANCE RATING SHOULD
 BE? ON THE LIFE SAFETY SHEET THE CODE DATA STATES THE
 BUILDING IS A ONE STORY, IF SO THEN PLEASE UPDATE THE
 SURVEY. DISCREPANCY IN DOCUMENTS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1B) OCCUPANT LOADS BUSINESS & MERCANTILE IN BOTH CASES
 THE OCCUPANT LOAD WAS ROUNDED UP TO THE NEXT WHOLE
 NUMBER, THE OCCUPANT LOAD IS ROUNDED DOWN, AND THERE
 ARE NO PARTS OF OCCUPANTS. THE OCCUPANT LOAD IS ALWAYS
 ROUNDED DOWN TO THE NEXT WHOLE NUMBER TABLE 1004.1.2 OF
 THE 2017 FBC AND BUILDING OFFICIALS INFORMAL
 INTERPRETATION.
  
 1C) THE LIFE SAFETY SHEET UNDER THE HEADING OF OCCUPANT
 LOAD THE TOTAL OCCUPANT LOAD STATED IS 84 REQUIRING 2
 EXIT DOORS. THE BUILDING IS STATED AS BEING FIRE
 SPRINKLERED ALLOWING THE 2 EXITS TO BE AT LEAST 1/3 THE
 OVERALL DISTANCE APART. THE OVERALL DIAGONAL DISTANCE
 IS STATED ON THE PLANS AS 121 FEET. IN THE 2017 FBC-B
 SECTION 1007.1.1 EXCEPTION 2 ALLOWS WHEN 2 EXITS ARE
 REQUIRED FOR FULLY SPRINKLERED BUILDINGS THE SEPARATION
 DISTANCE CAN BE REDUCED TO 1/3RD OF THE LENGTH OF THE
 OVERALL DIAGONAL DISTANCE. THE MINIMUM OVERALL 1/3RD
 THE DIAGONAL DISTANCE APART FOR EXITS IS 40.333 FEET
 APART. PLEASE NOTE NEITHER OF THESE EXITS MEET THAT
 REQUIREMENT AS SHOWN THEY ARE 32.5 FEET AND 33.5 FEET
 APART AS SHOWN ON THE PLAN. THIS IS NOT TRUE. IN
 MEASURING THE DISTANCE BETWEEN THE EXITS, YOU DO NOT
 CUT THAT DISTANCE IN 1/3RD. PLEASE PROVIDE THE ACTUAL
 DISTANCE THE EXITS ARE SEPARATED, THIS IS THE DISTANCE
 THAT NEEDS TO BE SHOWN AND THAT DISTANCE WILL BE OVER
 40.333 FEET APART. CORRECT PLANS PLEASE SHOWING CODE
 COMPLIANCE.
  
 1D) THE LOWER LEFT SIDE OF THE SHEET THE COMMON PATH OF
 TRAVEL IS SHOWN AS 27.66 FEET. COMMON PATH OF TRAVEL
 FOR THIS AREA IS APPROXIMATELY 69 FEET. IT IS TAKEN IN
 THE MOST REMOTE POINT IN THE OFFICE AND MEASURED AT ONE
 FOOT OFF THE WALL OR TWO FEET OFF THE WALL TO THE POINT
 WHERE YOU HAVE A CHOICE OF 2 EGRESS PATHS. SEE IN THE
 2017 FBC-B SECTION 1006.2.1 AND TABLE 1006.2.1. PLEASE
 UPDATE THE TRAVEL DISTANCE FOR THE COMMON PATH OF
 TRAVEL.
  
 2) SHEET A1-1.5 1ST FLOOR CEILING PLAN SHOWS AN EXPOSED
 CEILING IN MANY PORTIONS OF THE BUILDING. WHEREAS THE
 SURVEY INDICATES THIS TO BE A 2 STORY BUILDING.
 RESTATED FROM COMMENT 1A)(2). HOW WILL THE REQUIREMENTS
 FOR FIRE RESISTANCE RATING REQUIREMENTS FOR HORIZONTAL
 ASSEMBLIES BETWEEN FIRE AREAS, TABLE 707.3.10 OF THE
 2017 FBC-B. PLEASE PROVIDE WHAT OCCUPANCY IS ON THE 2ND
 FLOOR TO KNOW WHAT THE FIRE RESISTANCE RATING SHOULD
 BE? ON THE LIFE SAFETY SHEET THE CODE DATA STATES THE
 BUILDING IS A ONE STORY, IF SO THEN PLEASE UPDATE THE
 SURVEY. DISCREPANCY IN DOCUMENTS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET A9.02 ACCESSIBLE RESTROOMS:
 3A) THE DETAIL # 7 SHOWS THE GRAB BAR BEING MEASURED
 FROM THE FLOOR TO THE CENTERLINE OF THE GRAB BAR.
 PLEASE NOTE THEE MEASUREMENT IS TO BE TAKEN FROM THE
 TOP OF THE GRASPING SURFACE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 3B) THE DETAIL # 7 SHOWS THE TOILET PAPER HOLDER
 VERTICAL DIMENSION BUT NOT THE HORIZONTAL DIMENSION
 FROM THE FRONT OF THE WATER CLOSET. TOILET PAPER
 DISPENSERS. 604.7 DISPENSERS. TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS. DISPENSERS SHALL NOT BE OF A
 TYPE THAT CONTROLS DELIVERY OR THAT DOES NOT ALLOW
 CONTINUOUS PAPER FLOW.
  
  
 3C) MEN?S RESTROOM DETAIL # 6 SHOWS A HEIGHT OF 39
 INCHES TO WHAT APPEARS TO BE A SHELF BELOW THE EDGE LIT
 MIRROR, PLEASE BE AWARE THAT MIRRORS ARE TO BE LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) THE STRUCTURAL SHEETS SHOW THE USE OF STEEL COLUMNS,
 BEAMS AND ROOF DECKING. PLEASE SHOW COMPLIANCE WITH
 WELDED AND BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 5) SHEET A3.02, A7.03 BOTH SHOW NEW EXTERIOR DOORS, AND
 MULLIONS, PLEASE PROVIDE COMPLIANCE WITH:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
 (B) WINDOWS & MULLIONS.
 (C) PANEL WALLS: STOREFRONTS SYSTEMS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 6) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-10 Cont ID  
Sent By fgiaquin Date 2019-10-10 Time 06:50 Rev Time 0.00
Received By fgiaquin Date 2019-10-04 Time 06:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2019-08-11 Time   Rev Time 0.00
Received By fgiaquin Date 2019-08-02 Time 07:12 Sent To  
Notes
2019-08-11 10:51:49FG PASS ON 8-3-19.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-03 Cont ID  
Sent By pleduc Date 2019-10-03 Time   Rev Time 0.00
Received By pleduc Date 2019-10-03 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By pleduc Date 2019-07-15 Time   Rev Time 0.00
Received By pleduc Date 2019-07-15 Time 11:22 Sent To  
Notes
2019-07-15 12:43:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.1 - THERE APPEARS TO BE A NEW 1-HOUR WALL
 IS INDICATED WITHIN THE CENTER AREA OF THE BUILDING;
 HOWEVER THERE IS AN OPEN AREA AT THE FRONT DESK AREA.
  
 THERE IS NO NET FIRE SEPARATION FOR THIS NEW 1 HOUR
 WALL AND I'M NOT SURE OF THE DESING ATTEMPT.
  
 IS THIS A MIXED, SEPARATED OR NONSEPARATED OCCUPANCY?
  
 PER NFPA 101, CH 6, OCCUPANCY CLSSIFICATION
  
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE
 RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR
 1-HOUR FIRE
 RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF
 CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE
 REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED
 TO LESS THAN 1
 HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE
 DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES.
 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL,
 HORIZONTAL, OR
 BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED
 TO PROVIDE
 COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE
 BUILDING.
 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING
 SHALL COMPLY
 WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN.
  
 PLEASE CLARIFY AND CORRECT ACCORDINGLY.
  
  
  
 2) SHEET LS 1.1 - THERE IS AN ASSEMBLY AREA INDICATED
 WITH TWO EXITS; ONE AT THE FRONT DOOR AND ONE THROUGH
 THE STORAGE AREA. THE ASSEMBY AREA EXIT CAN NOT PASS
 THROUGH A HIGHER HAZARD AREA, LIKE STORAGE.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PER NFPA 101, CH 13 NEW ASSEMBLY OCCUPANCIES
  
 12.2.5.2 ACCESS THROUGH HAZARDOUS AREAS. MEANS OF
 EGRESS
 FROM A ROOM OR SPACE FOR ASSEMBLY PURPOSES SHALL NOT BE
 PERMITTED THROUGH KITCHENS, STOREROOMS, RESTROOMS,
 CLOSETS,
 PLATFORMS, STAGES, PROJECTION ROOMS, OR HAZARDOUS AREAS
 AS
 DESCRIBED IN 12.3.2.
  
 ADDITIONALLY, THE REAR EXIT CANNOT BE USED AS THE 2ND
 EXIT FROM THE ASSEMBLY SPACE DUE TO THE REMOTENSS CODE
 BELOW.
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAILS AND FIRE CODE REFERENCES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-10-08 Cont ID  
Sent By fmittner Date 2019-10-08 Time 15:19 Rev Time 0.00
Received By fmittner Date 2019-10-08 Time 15:19 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-07-18 Cont ID  
Sent By fmittner Date 2019-07-18 Time 16:45 Rev Time 0.00
Received By fmittner Date 2019-07-18 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-10-22 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-02 Time 10:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-08-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-07-12 Time 11:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-08-19 Cont ID  
Sent By jwitmer Date 2019-08-19 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2019-08-13 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-08 Cont ID  
Sent By ccole Date 2019-10-08 Time 12:44 Rev Time 0.00
Received By ccole Date 2019-10-08 Time 09:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By pvalenti Date 2019-08-13 Time 08:54 Rev Time 0.00
Received By ccole Date 2019-08-13 Time 08:54 Sent To  
Notes
2019-08-13 08:56:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070494
 8/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1.1: THE PLAN APPEARS TO SHOW AIR BEING
 RETURNED FROM THE TOILET ROOMS TO RTU-1 WHICH IS
 PROHIBITED- 601.5 FBC M.
 2) M1.1.1: THE 30X12 TRANSFER GRILL RETURNING AIR VIA
 THE CORRIDOR IS PROHIBITED PER SECTION 601.2 FBC M.
 3) A.1.2.1.: 42? HIGH GUARD RAILS SHALL BE INSTALLED
 ALONG THE ROOF EDGES BY THE NEW RTU?S UNLESS THERE IS
 AN EXISTING 42? HIGH PARAPET WALL- SEE SECTION 304.11
 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-10-03 Cont ID  
Sent By jesmith Date 2019-10-03 Time 15:09 Rev Time 0.00
Received By jesmith Date   Time   Sent To  
Notes
2019-10-03 15:09:06PLUMBING COMMENTS: APPROVED
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By jesmith Date 2019-08-13 Time 12:02 Rev Time 0.00
Received By jesmith Date 2019-08-13 Time 08:52 Sent To  
Notes
2019-08-13 12:02:24ODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. DISHWASHER
  
 A. P1.1.2/P2.1.1/A1.1.1
  
 1)PLUMBING DRAWINGS INDICATE THE DISHWASHER IS LOCATED
 UNDER THE ISLAND BAR/COUNTER. ARCHITECTURAL DRAWING
 A1.1.1 SHOWS THE DISHWASHER ADJACENT TO THE SINK.
 P1.1.2 SANITARY ISO AND FLOOR PLAN SHOW DISHWASHER
 DISCHARGING TO A FLOOR SINK. P2.1.1 PLUMBING FIXTURE
 CONNECTION SCHEDULE CALLS TO COMPLY WITH FBC PL 802.1.6
 OR 802.1.7. PLEASE NOTE THAT IF DISCHARGING TO A FLOOR
 SINK PER 802.1.7, THAT THE FLOOR SINK SHALL NOT BE
 INSTALLED IN A CONCEALED PLACE BUT MUST HAVE READY
 ACCESS PER FBC PL 802.3. COMPLIANCE WITH FBC PL 802.1.6
 ALLOWS FOR A SIMPLE UNDER THE COUNTER CONNECTION TO THE
 SINK WASTE SO LONG AS THE DISHWASHER IS ADJACENT TO THE
 SINK AS NOTED ON A1.1.1 AND THE REQUIREMENTS OF 802.1.6
 ARE MET. PER WPB FBC 107.2.1, PLEASE CLARIFY WHICH
 INDIRECT WASTE METHOD IS TO BE USED ON BOTH THE
 SCHEDULE AND THE SANITARY PIPING DRAWINGS AS WELL AS
 THE ACTUAL LOCATION OF THE DISHWASHER.
  
  
 2. ICEMAKER
  
 A. PER FBC PL 608.2 AND 608.3, PROVIDE A BACKFLOW
 PREVENTER IN THE WATER SUPPLY TO THE ICE MAKER AND
 INDICATE ON THE WATER RISER AND SPECIFY IN THE PLUMBING
 FIXTURE CONNECTION SCHEDULE.
  
  
 3. RE: P2.1.1
  
 A.GENERAL PLUMBING NOTES
  
 1) DOMESTIC WATER PIPING NOTE 4; AMEND NOTE TO READ
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 AND
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED AND WHERE SHOWN ON THE WATER RISER DIAGRAM.
 2) DOMESTIC WATER PIPING NOTE 13 CALLS FOR A PRESSURE
 AND TEMPERATURE RELIEF VALVE FOR ALL WATER HEATERS
 (TANK-TYPE AND TANKLESS) AND AN EXPANSION TANK AS
 REQUIRED. PER WPB FBC107.2.1, CLARIFY WHETHER OR NOT
 ONE OR BOTH OF THESE ITEMS ARE REQUIRED FOR THE
 SCHEDULED TANKLESS WATER HEATER(S) AND IF THEY ARE
 REQUIRED THEN INCLUDE THEM IN THE ELECTRIC TANKLESS
 WATER HEATER DETAIL. ADDITIONALLY, IF THE RELIEF VALVE
 IS REQUIRED THEN PROVIDE FOR THE DISCHARGE OF SAID
 VALVE IN ACCORDANCE WITH FBC PL 504.6.
 3) DO YOU REQUIRE AN EMERGENCY PAN FOR THE TANKLESS
 WATER HEATER AS STATED IN NOTE 12? IF SO THEN PROVIDE A
 DETAIL SHOWING COMPLIANCE WITH FBC PL 504.7.1 AND
 504.7.2. IF NOT THEN REMOVE THE NOTE.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19070494 1921 S DIXIE HWY
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By jwitmer Date 2019-10-22 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2019-10-22 Time   Sent To  
Notes
2019-10-22 11:07:00ALL PLANS ELECTRONICALLY SIGNED AND SEALED. JW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By rmcdouga Date 2019-08-26 Time 10:59 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2019-08-19 07:35:38ARCHITECTURAL SHEETS ARE NOT ELECTRONICALLY SIGNED AND
 SEALED. ARCHITECT DIGITAL SIGNING & SEALING PLANS.
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-08 Cont ID  
Sent By fmittner Date 2019-10-08 Time 15:20 Rev Time 0.00
Received By fmittner Date 2019-10-08 Time 15:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-18 Cont ID  
Sent By fmittner Date 2019-07-18 Time 16:45 Rev Time 0.00
Received By fmittner Date 2019-07-18 Time 16:45 Sent To  
Notes
***NONE***