| Plan Review Stops For Permit 19070457 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-10-23 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-10-23 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-10-23 |
Time |
11:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-07-19 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-07-19 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2019-07-19 11:31:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 3202, REVISE PLAN TO SHOW HEIGHT OF BOTTOM OF | | | SIGN TO GRADE. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-10-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-10-09 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-10-09 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2019-10-28 10:56:59 | ELECTRICAL PORTION OF WALL SIGN APPROVED. PER LETTER IN | | | FILE NET, THE ONLY BLADE SIGN WILL NOT BE ILLUMINATED. | | | | | | | | 2019-10-09 12:34:57 | LETTER TAKES OUT THE ELECTRIC TO SIGN JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-07-31 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-07-31 |
Time |
06:09 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-07-31 |
Time |
05:53 |
Sent To |
I |
|
| Notes |
| 2019-07-31 06:09:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO DISCONNECT SHOWN CONFORMING TO DISCONNECT | | | REQUIREMENTS OF NEC 600.6A1, ONLY A NOTE. SHOW | | | DISCONNECT ON PLAN, MUST BE WITHIN SIGHT OF SIGN. | | | | | | 2. NOTE ON PLAN ABOUT TIMECLOCK OR PHOTOCELL REFERENCES | | | SFBC NOT FBC EC AND DOES NOT CONFORM TO ENERGY | | | CONSERVATION STANDARDS OF FBC EC 405.2.5, ALL TIME | | | SWITCHES MUST RETAIN TIME SETTING FOR MINIMUM OF 10 | | | HOURS FOLLOWING A LOSS OF POWER. PLEASE CORRECT NOTE. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-10-23 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-10-23 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-09-19 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2019-10-02 14:40:29 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 10/2/19 EL | | 2019-09-20 13:38:04 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-07-31 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-07-31 |
Time |
06:09 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-07-10 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2019-07-30 14:34:45 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 7/30/19 EL | | | | | | ADDED SECOND ZONING STOP WITH UPDATED COMMENTS 7/30/19 | | | EL | | 2019-07-29 16:41:36 | 7/29 TO ZONING PER LIZ LEVESQUE REQUEST | | | | | 2019-07-19 09:55:16 | TO ELEC | | | | | | | | 2019-07-12 10:56:35 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 7/12/2019 EL | | 2019-07-11 13:55:02 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-10-02 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2019-10-02 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-10-02 |
Time |
14:23 |
Sent To |
E |
|
| Notes |
| 2019-10-02 14:23:31 | EMAIELD GOPERMIT ON 10/2/2019 - INTERNAL ILLUMINATION | | | NOT PERMITTED IN BLADE SIGN , STILL IN PACKET | | | | | | PASSED 10/2/19 - BLADE SIGN WILL NOT BE ILLUMINATED |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-07-30 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2019-07-30 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-07-30 |
Time |
14:33 |
Sent To |
E |
|
| Notes |
| 2019-07-30 14:34:00 | WALL SIGN: | | | PLEASE PROVIDE TOTLA VERTICAL DIMENSION OF SIGN, | | | INCLUDING BACKING | | | | | | SIGN CANNOT PROJECT BEYOND THE CANOPY | | | | | | BLADE SIGN: | | | INTERNAL ILLUMINATION NOT PERMITTED | | | PLEASE DIMENSION VERTICAL CLEARANCE FROM SIDEWALK - | | | MUST BE 8 FEET MINIMUM | | | | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | [email protected] | | | 561 822 1426 | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
EL 7/12 |
Date |
2019-07-12 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-07-12 |
Time |
10:56 |
Sent To |
B |
|
| Notes |
| 2019-07-12 10:56:08 | WALL SIGN: | | | ALUMINUM FRAME BACKER PANEL CANNOT BE VISIBLE ABOVE | | | LETTERS - THE SECOND SHEET FOR MOUNTED WALL SIGN SHOWS | | | ALUMINUM FRAME TALLER THAN CHANNEL LETTERS | | | | | | CAN LETTERS BE MOUNTED LIKE PREVIOUS ULTIMA SIGN TO | | | EXLCUDE USE OF ALUMINUM BACKER? PLEASE LOOK AT | | | POSSIBITY TO REDUCE LOOK OF CABINET SIGN. | | | | | | BLADE SIGN: | | | INTERNAL ILLUMINATION NOT PERMITTED | | | PLEASE DIMENSION VERTICAL CLEARANCE FROM SIDEWALK - | | | MUST BE 8 FEET MINIMUM | | | | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | [email protected] | | | 561 822 1426 | | | | | | | | | |
|
|