Plan Review Details - Permit 19070457
Plan Review Stops For Permit 19070457
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-23 Cont ID  
Sent By pvalenti Date 2019-10-23 Time 11:36 Rev Time 0.00
Received By pvalenti Date 2019-10-23 Time 11:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 09:54 Rev Time 0.00
Received By shill Date 2019-07-19 Time 09:54 Sent To  
Notes
2019-07-19 11:31:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 3202, REVISE PLAN TO SHOW HEIGHT OF BOTTOM OF
 SIGN TO GRADE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-28 Cont ID  
Sent By jleahy Date 2019-10-09 Time 12:34 Rev Time 0.00
Received By jpearson Date 2019-10-09 Time 12:34 Sent To  
Notes
2019-10-28 10:56:59ELECTRICAL PORTION OF WALL SIGN APPROVED. PER LETTER IN
 FILE NET, THE ONLY BLADE SIGN WILL NOT BE ILLUMINATED.
  
  
2019-10-09 12:34:57LETTER TAKES OUT THE ELECTRIC TO SIGN JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-31 Cont ID  
Sent By fgiaquin Date 2019-07-31 Time 06:09 Rev Time 0.00
Received By fgiaquin Date 2019-07-31 Time 05:53 Sent To I
Notes
2019-07-31 06:09:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO DISCONNECT SHOWN CONFORMING TO DISCONNECT
 REQUIREMENTS OF NEC 600.6A1, ONLY A NOTE. SHOW
 DISCONNECT ON PLAN, MUST BE WITHIN SIGHT OF SIGN.
  
 2. NOTE ON PLAN ABOUT TIMECLOCK OR PHOTOCELL REFERENCES
 SFBC NOT FBC EC AND DOES NOT CONFORM TO ENERGY
 CONSERVATION STANDARDS OF FBC EC 405.2.5, ALL TIME
 SWITCHES MUST RETAIN TIME SETTING FOR MINIMUM OF 10
 HOURS FOLLOWING A LOSS OF POWER. PLEASE CORRECT NOTE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-23 Cont ID  
Sent By pvalenti Date 2019-10-23 Time 11:37 Rev Time 0.00
Received By pvalenti Date 2019-09-19 Time 13:37 Sent To  
Notes
2019-10-02 14:40:29ROUTED FROM ZONING TO PERMIT LIBRARIAN 10/2/19 EL
2019-09-20 13:38:04RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-31 Cont ID  
Sent By fgiaquin Date 2019-07-31 Time 06:09 Rev Time 0.00
Received By fgiaquin Date 2019-07-10 Time 13:54 Sent To  
Notes
2019-07-30 14:34:45ROUTED FROM ZONING TO PERMIT LIBRARIAN 7/30/19 EL
  
 ADDED SECOND ZONING STOP WITH UPDATED COMMENTS 7/30/19
 EL
2019-07-29 16:41:367/29 TO ZONING PER LIZ LEVESQUE REQUEST
  
2019-07-19 09:55:16TO ELEC
  
  
2019-07-12 10:56:35ROUTED FROM ZONING TO PERMIT LIBRARIAN 7/12/2019 EL
2019-07-11 13:55:02ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-10-02 Cont ID  
Sent By elevesqu Date 2019-10-02 Time 14:40 Rev Time 0.00
Received By elevesqu Date 2019-10-02 Time 14:23 Sent To E
Notes
2019-10-02 14:23:31EMAIELD GOPERMIT ON 10/2/2019 - INTERNAL ILLUMINATION
 NOT PERMITTED IN BLADE SIGN , STILL IN PACKET
  
 PASSED 10/2/19 - BLADE SIGN WILL NOT BE ILLUMINATED

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-30 Cont ID  
Sent By elevesqu Date 2019-07-30 Time 14:34 Rev Time 0.00
Received By elevesqu Date 2019-07-30 Time 14:33 Sent To E
Notes
2019-07-30 14:34:00WALL SIGN:
 PLEASE PROVIDE TOTLA VERTICAL DIMENSION OF SIGN,
 INCLUDING BACKING
  
 SIGN CANNOT PROJECT BEYOND THE CANOPY
  
 BLADE SIGN:
 INTERNAL ILLUMINATION NOT PERMITTED
 PLEASE DIMENSION VERTICAL CLEARANCE FROM SIDEWALK -
 MUST BE 8 FEET MINIMUM
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By EL 7/12 Date 2019-07-12 Time 10:56 Rev Time 0.00
Received By elevesqu Date 2019-07-12 Time 10:56 Sent To B
Notes
2019-07-12 10:56:08WALL SIGN:
 ALUMINUM FRAME BACKER PANEL CANNOT BE VISIBLE ABOVE
 LETTERS - THE SECOND SHEET FOR MOUNTED WALL SIGN SHOWS
 ALUMINUM FRAME TALLER THAN CHANNEL LETTERS
  
 CAN LETTERS BE MOUNTED LIKE PREVIOUS ULTIMA SIGN TO
 EXLCUDE USE OF ALUMINUM BACKER? PLEASE LOOK AT
 POSSIBITY TO REDUCE LOOK OF CABINET SIGN.
  
 BLADE SIGN:
 INTERNAL ILLUMINATION NOT PERMITTED
 PLEASE DIMENSION VERTICAL CLEARANCE FROM SIDEWALK -
 MUST BE 8 FEET MINIMUM
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  
  