Plan Review Details - Permit 19070414
Plan Review Stops For Permit 19070414
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-12-16 Cont ID  
Sent By jwitmer Date 2019-12-16 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2019-12-16 Time 08:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-09 Cont ID  
Sent By jwitmer Date 2019-09-09 Time 15:52 Rev Time 0.00
Received By jwitmer Date 2019-09-09 Time 11:10 Sent To  
Notes
2019-09-09 15:52:192017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070414
 ADD: 1609 S DIXIE HWY. 1ST FLOOR ONLY
 CONT: MARION CONSTRUCTION INC.
 TEL: 561-659-5292
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT. 10, 2019
 ACTION: DENIED
  
 1A-C) COMPLIED
  
 1D) DENIED. THE REQUIRED HORIZONTAL OCCUPANCY
 SEPARATION IS ASSUMED BE IN PLACE. THE CONTRACTOR SHALL
 VERIFY THE TYPE OF MATERIALS THE FLOOR ASSEMBLY IS MADE
 OF AND REPORT BACK TO THE ARCHITECT OF RECORD HIS
 FINDINGS. HE WILL VERIFY THE TYPE OF MATERIALS FOR THE
 SLAB AND THICKNESS OF THE SLAB FOR THE FIRE RATED FLOOR
 ASSEMBLY. THE FLOOR ASSEMBLY SHALL COMPLY WITH TABLE
 722.2.2.1 FOR A 3 HR FIRE RATING AND REPORT TO THE
 DESIGNER OF RECORD HIS FINDINGS. THE CONTRACTOR SHALL
 MAKE ALL NECESSARY REPAIRS AND AUGMENTATIONS TO IT AS
 NEEDED TO SATISFY THE BUILDING DEPARTMENT AND COMPLY
 WITH REQUIRED CODE SECTION 2017 FBC-B TABLE 707.3.10
 FIRE RATING OF HORIZONTAL ASSEMBLIES BETWEEN FLOORS.
 IN THE CITIES DIGITAL RECORDS PERMIT 01081470 WAS FOR
 STRUCTURAL REPAIRS TO THE 2ND FLOOR CONCRETE DECK,
 CONCRETE GIRDERS WITH ADDITIONAL STEEL COLUMNS AND
 BEAMS. FLOOR FRAMING AND CONSTRUCTION IS CONSISTENT
 WITH BUILDING TYPE II-B CONSTRUCTION.
  
 2017 FBC-B SECTION 707.3.10 AND TABLE 707.3.10 FIRE
 AREAS. FIRE-RESISTANCE RATING REQUIREMENTS FOR
 HORIZONTAL ASSEMBLIES BETWEEN FIRE AREAS. A S1
 OCCUPANCY WILL REQUIRE 3 HOUR FIRE BARRIER WHEREAS S2,
 M, & B ALL REQUIRE A 2 HOUR FIRE BARRIER.
 THE OTHER ISSUE IS HOW ARE YOU GOING TO GET THE 3 HOUR
 FIRE RESISTANCE RATING FOR THE STEEL COLUMNS AND BEAMS.
 TABLE 601 DOES NOT REQUIRE THE FIRE RATING BUT TABLE
 707.3.10 HORIZONTAL ASSEMBLIES BETWEEN FIRE AREAS WILL
 FOR THE SUPPORT OF THE 2ND FLOOR.
  
 1E) COMPLIED.
  
 1F) 2ND REQUEST. THE GETTING A UNITY OF TITLE AT TIME
 OF C. O. IS NOT GOING TO WORK. THIS PROJECT IS NOT A
 CHANGE OF OCCUPANCY SO THERE WILL BE NO C.O ISSUED. THE
 CONTRACTOR CAN REQUEST A CERTIFICATE OF COMPLETION, BUT
 IT IS NOT REQUIRED. THE OTHER ISSUE WITH WAITING UNTIL
 THE END OF THE JOB. WE ARE ALLOWING A NON-CONFORMITY TO
 INCREASE WITH THE NEW OPENINGS IN THE NORTH WALL.
  
 2017 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 1ST ROUND OF COMMENTS. PLEASE NOTE THE SUBMITTED SITE
 PLAN A-000 SHOWS THE BUILDING AND LOT TO THE NORTH AS
 ONE LARGE LOT WHEREAS THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE SHOWS THE PARKING LOT WITH A SEPARATE
 PCN: 74-43-43-28-02-000-0120. WITHOUT A UNITY OF TITLE
 THE NORTH WALL OF THE BUILDING WOULD NEED TO BE FIRE
 RATED PER FBC-B TABLE 602 AND TABLE 705.8 MAXIMUM AREA
 OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION WOULD NOT
 ALLOW ANY OPENINGS.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS OR
 NO ALLOWABLE OPENINGS ON THE NORTH SIDE OF THE
 BUILDING. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
  
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 1G) BUILDING PROVISO/ UNDER SEPARATE PERMIT. THE
 COVERSHEET SHOWS AN ACCESSIBLE PARKING SPACE AND ACCESS
 AISLE, PLEASE SEE THE 2017 FBC-ACCESSIBILITY CODE
 502.3.3 MARKING. ACCESS AISLES SHALL BE MARKED SO AS TO
 DISCOURAGE PARKING IN THEM.
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA LAW,
 S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF
 ACCESS AISLES.
 THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDES A DOUBLE LINED PARKING STALL DETAIL.
  
 2-3) COMPLIED.
  
 4) BUILDING PROVISO/ DEFERRED SUBMITTAL. THE DESIGNER
 OF RECORD HAS ELECTED TO DEFER THE WINDOW AND DOOR
 PRODUCT APPROVALS UNTIL AFTER PERMIT ISSUANCE.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
  
 5) BUILDING PROVISO/ DEFERRED SUBMITTAL. IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-30 Cont ID  
Sent By jwitmer Date 2019-07-30 Time 14:48 Rev Time 0.00
Received By jwitmer Date 2019-07-30 Time 09:35 Sent To  
Notes
2019-07-30 14:48:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070414
 ADD: 1609 S DIXIE HWY. 1ST FLOOR ONLY
 CONT: MARION CONSTRUCTION INC.
 TEL: 561-659-5292
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 30, 2019
 ACTION: DENIED
  
 1) A000 THE COVER PAGE:
  
 1A) THE CONSTRUCTION TYPE IS GIVEN AS BUILDING
 CONSTRUCTION TYPE V. IN THE 2017 FBC-B YOU HAVE TYPE
 V-A AND V-B TYPE CONSTRUCTION. THE LAST TIME THE CODE
 LISTED A TYPE V IS UNDER THE 2001 FBC-B (UNPROTECTED).
 IF USING THE 2001 TYPE V UNDER THE 2017 FBC-B THIS
 TRANSLATES INTO A BUILDING CONSTRUCTION TYPE IIIB.
 PLEASE PROVIDE ADDITIONAL INFORMATION AS THE PROPOSED
 CONSTRUCTION TYPE. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1B) THE WAREHOUSE SQUARE FOOTAGE OF 3,894 SQ. FT.
 STATES ONLY A S OCCUPANCY. PLEASE DECLARE IF THIS IS TO
 BE CONSIDERED A S1 OR S2 OCCUPANCY.
 PLEASE NOTE UNDER THE EXISTING BUILDING CODE 904.1.3.
 WORK AREAS SHALL BE PROVIDED WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING WHERE ANY OF THE FOLLOWING
 CONDITIONS EXIST:
 (3) A GROUP S-1 OCCUPANCY USED FOR THE STORAGE OF
 UPHOLSTERED FURNITURE OR MATTRESSES EXCEEDS 2,500
 SQUARE FEET.
  
 1C) THE PLANS ARE SILENT AS TO WHAT TYPE OF OCCUPANCY
 IS TO BE ON THE 2ND FLOOR, NOT PART OF THIS PROJECT BUT
 WHEN DECLARING A BUILDING TYPE OF VB AND
 NON-SPRINKLERED THE S1 OCCUPANCY CAN ONLY BE ON THE 1ST
 FLOOR. PLEASE REVIEW TABLE 504.4.
  
 1D) THE COVERSHEET IS SILENT AS TO THE HORIZONTAL
 OCCUPANCY SEPARATION BETWEEN THE 1ST FLOOR CEILING /
 2ND FLOOR ASSEMBLY AND REQUIRED FIRE RATING.
  
 2017 FBC-EXISTING BUILDING CODE SECTION 803.6
 FIRE-RESISTANCE RATINGS. WHERE APPROVED BY THE CODE
 OFFICIAL, BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR
 903.3.1.2 OF THE FLORIDA BUILDING CODE, BUILDING HAS
 BEEN ADDED, AND THE BUILDING IS NOW SPRINKLERED
 THROUGHOUT, THE REQUIRED FIRE-RESISTANCE RATINGS OF
 BUILDING ELEMENTS AND MATERIALS SHALL BE PERMITTED TO
 MEET THE REQUIREMENTS OF THE CURRENT BUILDING CODE. THE
 BUILDING IS REQUIRED TO MEET THE OTHER APPLICABLE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 PLANS, INVESTIGATION AND EVALUATION REPORTS, AND OTHER
 DATA SHALL BE SUBMITTED INDICATING WHICH BUILDING
 ELEMENTS AND MATERIALS THE APPLICANT IS REQUESTING THE
 CODE OFFICIAL TO REVIEW AND APPROVE FOR DETERMINATION
 OF APPLYING THE CURRENT BUILDING CODE FIRE-RESISTANCE
 RATINGS. ANY SPECIAL CONSTRUCTION FEATURES, INCLUDING
 FIRE-RESISTANCE-RATED ASSEMBLIES AND SMOKE-RESISTIVE
 ASSEMBLIES, CONDITIONS OF OCCUPANCY, MEANS OF-EGRESS
 CONDITIONS, FIRE CODE DEFICIENCIES, APPROVED
 MODIFICATIONS OR APPROVED ALTERNATIVE MATERIALS, DESIGN
 AND METHODS OF CONSTRUCTION, AND EQUIPMENT APPLYING TO
 THE BUILDING THAT IMPACT REQUIRED FIRE-RESISTANCE
 RATINGS SHALL BE IDENTIFIED IN THE EVALUATION REPORTS
 SUBMITTED.
  
 2017 FBC-B SECTION 707.3.10 AND TABLE 707.3.10 FIRE
 AREAS. FIRE-RESISTANCE RATING REQUIREMENTS FOR
 HORIZONTAL ASSEMBLIES BETWEEN FIRE AREAS. A S1
 OCCUPANCY WILL REQUIRE 3 HOUR FIRE BARRIER WHERE AS S2,
 M, & B ALL REQUIRE A 2 HOUR FIRE BARRIER.
  
 1E) THE COVERSHEET, A100 PHASING PLAN NOR A105 THE LIFE
 SAFETY PLAN INDICATE THE OCCUPANCY OF THE WAREHOUSE,
 EITHER A S1 OR S2. WITHOUT THIS INFORMATION WE CAN NOT
 DETERMINE IF OCCUPANCY SEPARATION IS REQUIRED PER TABLE
 508.4 OF THE 2017 FBC-B OR IF THE DESIGNER OF RECORD
 HAS DESIGNED THIS AS NON-SEPARATED PER 508.3?
  
 1F) PLEASE NOTE THE SUBMITTED SITE PLAN A-000 SHOWS THE
 BUILDING AND LOT TO THE NORTH AS ONE LARGE LOT WHEREAS
 THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE SHOWS
 THE PARKING LOT WITH A SEPARATE PCN:
 74-43-43-28-02-000-0120. WITHOUT A UNITY OF TITLE THE
 NORTH WALL OF THE BUILDING WOULD NEED TO BE FIRE RATED
 PER FBC-B TABLE 602 AND TABLE 705.8 MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION WOULD NOT
 ALLOW ANY OPENINGS.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS OR
 NO ALLOWABLE OPENINGS ON THE NORTH SIDE OF THE
 BUILDING. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
  
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 1G) THE COVERSHEET SHOWS AN ACCESSIBLE PARKING SPACE
 AND ACCESS AISLE, PLEASE SEE THE 2017 FBC-ACCESSIBILITY
 CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE MARKED SO
 AS TO DISCOURAGE PARKING IN THEM.
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
  
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA LAW,
 S.553.5041(5)(C)1., REQUIRES DIAGONAL STRIPING OF
 ACCESS AISLES.
 THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDES A DOUBLE LINED PARKING STALL DETAIL.
  
 2) SHEET A101:
  
 2A) THIS SHEET NOR THE LIFE SAFETY SHEET A105 PROVIDE
 WHAT FIRE RATING IS ON THE STAIRWELL SHAFTS? PLEASE SEE
 SECTION 2017 FBC-B SECTION 713.4. FIR RESISTANCE
 RATING.
  
 2B) THE SOUTH STAIR FROM THE 2ND FLOOR ENDS GOING INTO
 THE EXIT PASSAGE WAY, A CONTINUATION OF THE EXIT, A ONE
 HOUR FIRE RATED EXIT PASSAGE WAY (SEE 2017 FBC-B
 SECTIONS 1024.1 & 1024.3). ALSO SEE UNDER THE:
  
 2017 EXISTING BUILDING CODE SECTION 805.3.1 MINIMUM
 NUMBER. EVERY STORY UTILIZED FOR HUMAN OCCUPANCY ON
 WHICH THERE IS A WORK AREA THAT INCLUDES EXITS OR
 CORRIDORS SHARED BY MORE THAN ONE TENANT (SUITES 1 & 2)
 WITHIN THE WORK AREA SHALL BE PROVIDED WITH THE MINIMUM
 NUMBER OF EXITS BASED ON THE OCCUPANCY AND THE OCCUPANT
 LOAD IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2D) PLEASE REVIEW THE NORTH CORRIDOR USED BY (SUITES 3
 & 4) WILL ALSO NEED TO SHOW COMPLIANCE WITH:
 2017 EXISTING BUILDING CODE SECTION 805.3.1 MINIMUM
 NUMBER. EVERY STORY UTILIZED FOR HUMAN OCCUPANCY ON
 WHICH THERE IS A WORK AREA THAT INCLUDES EXITS OR
 CORRIDORS SHARED BY MORE THAN ONE TENANT (SUITES 1 & 2)
 WITHIN THE WORK AREA SHALL BE PROVIDED WITH THE MINIMUM
 NUMBER OF EXITS BASED ON THE OCCUPANCY AND THE OCCUPANT
 LOAD IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2017 FBC-TABLE 1020.1 CORRIDOR FIRE RESISTANCE RATING.
 FOR M, B, & S OCCUPANCIES WHEN A COMBINED OCCUPANT LOAD
 OF THE SUITES IS GREATER THAN 30 AND A NON-SPRINKLERED
 BUILDING THEN THE CORRIDOR NEEDS TO BE 1 HOUR FIRE
 RATING.
  
 2E) NONE OF THE DOORS (DOOR SCHEDULE A103/ DOORS 103,
 107, 111, 115, 120 & 132) THAT LEAD INTO THE EXIT
 PASSAGE WAY ON THE SOUTH SIDE OF THE BUILDING OR THE
 FIRE RATED CORRIDOR ON THE NORTH SIDE OF THE BUILDING
 SHOW A FIRE RATING REQUIRED BY FBC-B TABLE 716.5 FOR
 EXIT PASSAGE WAYS AND CORRIDORS.
  
 2F) SHEET A101 SHOWS VARIOUS WALL IDENTIFICATION TAGS,
 WALL TYPES A, B, C & D BUT NOT ALL WALLS IN THE EXIT
 PASSAGE WAY NOR EXIT ACCESS CORRIDOR ON THE NORTH SIDE
 ARE IDENTIFIED. ONE SECTION OF WALL BETWEEN THE
 WAREHOUSE AND STORAGE ROOM ARE IDENTIFIED, PLEASE
 PROVIDE WALL MARKERS IDENTIFYING RATED WALLS. 2017
 FBC-B TABLE 1020.1.
  
 3) SHEET S-3.00 PROVIDES THE COMPONENTS AND CLADDING
 PRESSURE CHART IN VASD. THANK YOU ALL PRODUCT APPROVALS
 ARE IN VASD. THERE IS NO WIND DESIGN CRITERIA FOR THE
 PRESSURE CHART. ALL OF THE STATED NEGATIVE PRESSURES
 ARE 2 TO 3 LBS. LIGHT OF WHAT ARE CHARTS ARE READING.
 AT WHAT MEAN ROOF HEIGHT ARE YOU TAKING THE PRESSURES
 FROM?
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 4) NOTICE ONLY, NO ACTION TO BE TAKEN. THE DESIGNER OF
 RECORD HAS ELECTED TO DEFER THE WINDOW AND DOOR PRODUCT
 APPROVALS UNTIL AFTER PERMIT ISSUANCE.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
  
 5) NOTICE ONLY, NO ACTION TO BE TAKEN AT THIS TIME.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-12 Cont ID  
Sent By jpearson Date 2019-09-12 Time 09:43 Rev Time 0.00
Received By jpearson Date 2019-09-12 Time 08:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-14 Cont ID  
Sent By jpearson Date 2019-07-14 Time 14:16 Rev Time 0.00
Received By jpearson Date 2019-07-14 Time 13:49 Sent To  
Notes
2019-07-14 14:09:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 2. IS THERE ANY LOAD BEING ADDED? PROVIDE ACCURATE LOAD
 CALCULATION FOR SERVICE, INCLUDE EXISTING AND NEW LOADS
 TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30
 3. EACH PANEL SHOWS A 1/0 CONDUCTOR FEEDING A 200 AMP
 PANEL. IS THIS CONDUCTOR PROTECTED FOR OVERCURRENT
 PROTECTION AT THE PROPER SIZE? PROVIDE CLARIFICATION
 AND/OR CORRECTIONS AS NEEDED. NEC 240.4, 310.15(B)(16);
 WPB FBC 107.2.1
 4. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-12-13 Cont ID  
Sent By pleduc Date 2019-12-13 Time   Rev Time 0.00
Received By pleduc Date 2019-12-13 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-22 Cont ID  
Sent By pleduc Date 2019-08-22 Time   Rev Time 0.00
Received By pleduc Date 2019-08-22 Time 12:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By pleduc Date 2019-07-15 Time   Rev Time 0.00
Received By pleduc Date 2019-07-15 Time 14:10 Sent To  
Notes
2019-07-15 14:35:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 100 - THE OCCUPANCY IS INDICATED AS
 MERCANTILE AND STORAGE; HOWEVER, IT IS NOT INDICATED AS
 MIXED, SEPARATED OR NON-SEPARATED.
  
 PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION
  
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE
 RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR
 1-HOUR FIRE
 RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF
 CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE
 REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED
 TO LESS THAN 1
 HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE
 DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES.
 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL,
 HORIZONTAL, OR
 BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED
 TO PROVIDE
 COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE
 BUILDING.
 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING
 SHALL COMPLY
 WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN.
  
 PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION PER THE
 ABOVE.
  
  
  
 2) SHEET A 100 - THERE APPEARS TO BE A SEPARATION WALL
 BETWEEN THE MERCANTILE AND WAREHOUSE/STORAGE.
  
 THERE IS NO FIRE RATING OF THE EXISTING WALL.
  
 PLEASE PROVIDE THIS FIRE RATING PER # 1 ABOVE OR
 JUSTIFY WITH SPECIFIC DETAIL AND CODE REFERENCES.
  
  
  
 3) SHEET A 101 - DOOR 130 IS INDICATED WITHIN THE
 SEPARATION WALL; BUT THE DOOR SCHEDULE ON SHEET A 103
 INDICATES A 1 HOUR FIRE RATED DOOR.
  
 THE REQUIRED SEPARATION PER # 1 ABOVE IS 2 HOUR.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAIL AND CODE REFERENCES.
  
  
  
  
 4) SHEET A 101 - THE SMALL STORAGE ROOM HAS A WALL
 IN-FILL SEPARATING IT FORM THE WAREHOUSE WITH A C
 CALL-OUT. SHEET A 103 INDICATED THE C CALL-OUT AS 1
 HOUR.
  
 THE REQUIRED SEPARATION PER # 1 ABOVE IS 2 HOUR.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAIL AND CODE REFERENCES.
  
  
  
 5) SHEET A 103 - THE IS NO DOOR EXIT HARDWARE INDICATED
 ON THE DOOR SCHEDULE.
  
 PLEASE PROVIDE EXIT DOOR HARDWARE PER NFPA 101, CH 7,
 MEANS OF EGRESS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL
 BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF
 OPERATION AND THAT IS READILY OPERATED UNDER ALL
 LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE
 LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR
 OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF
 WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS
 OTHERWISE
 SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR
 7.2.1.5.10.6.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status N Date 2019-12-16 Cont ID  
Sent By   Date 2019-12-16 Time   Rev Time 0.00
Received By   Date 2019-12-16 Time   Sent To  
Notes
2019-12-16 10:02:20NO NEW PLANS, JUST 8X11 UNITY OF TITLE, AND
 CALCULATIONS. J. W.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By fmittner Date 2019-08-30 Time 15:47 Rev Time 0.00
Received By fmittner Date 2019-08-30 Time 15:47 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By fmittner Date 2019-07-18 Time 16:25 Rev Time 0.00
Received By fmittner Date 2019-07-18 Time 16:25 Sent To  
Notes
2019-07-18 16:27:02THIS IS A HISTORIC PROPERTY. EXTERIOR MODIFICATIONS FOR
 WINDOWS AND DOORS REQUIRES SUBMITTAL OF COA. QUESTIONS,
 CONTACT: FRIEDERIKE MITTNER 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-12-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-04 Time 14:45 Sent To  
Notes
2019-12-05 14:45:22C11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-09-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-08-20 Time 15:44 Sent To  
Notes
2019-08-20 15:44:16C06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-06 Cont ID  
Sent By cmontell Date 2019-08-06 Time 13:02 Rev Time 0.00
Received By cmontell Date 2019-08-06 Time 13:02 Sent To  
Notes
2019-08-05 08:30:38TO CM DESK
  
2019-07-11 15:34:03C06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-30 Cont ID  
Sent By jwitmer Date 2019-07-30 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2019-07-30 Time 09:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By cmontell Date 2019-08-27 Time 14:45 Rev Time 0.00
Received By cmontell Date 2019-08-27 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-06 Cont ID  
Sent By cmontell Date 2019-08-06 Time 13:01 Rev Time 0.00
Received By cmontell Date 2019-08-06 Time 12:57 Sent To I
Notes
2019-08-06 13:01:37MECHANICAL PLAN REVIEW FAIL
  
 1 - PLEASE SHOW OUTDOOR AIR FLOW RATES 2017 FLORIDA
 BUILDING CODE - MECHANICAL, SIXTH EDITION TABLE
 403.3.1.1
  
 2 - NOTE AIR INTAKE OPENINGS SHALL COMPLY WITH 2017
 FLORIDA BUILDING CODE - MECHANICAL, SIXTH EDITION 401.4
 INTAKE OPENING LOCATION.
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By gjohnson Date 2019-09-10 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2019-09-10 Time 10:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-14 Cont ID  
Sent By abelisle Date 2019-07-14 Time 06:52 Rev Time  
Received By abelisle Date   Time   Sent To  
Notes
2019-07-14 09:05:327/14/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) PLUMBING RISER DIAGRAM REQUIRED FOR SANITARY AND
 WATER. WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
  
 3) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS ON THE CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 4) TEMPERED WATER REQUIRED AND DETAILS OF A TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 FBC P
 607.1.2 TEMPERED WATER TEMPERATURE CONTROL.
  
 5) DRINKING FOUNTAIN MISSING ON FLOOR PLAN A101
  
 6) MINIMUM 1 SERVICE SINK REQUIRED AND NOT INCLUDED IN
 THE SUBMITED PLANS, PLEASE INDICATE THE LOCATION OF THE
 SERVICE SINK
  
 7) 2" DRAIN LINE SHOWN ON PAGE P201, PLEASE CLARIFY
 WHAT THIS DRAIN LINE WILL BE USED FOR
  
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop Z ZONING
Rev No 2 Status N Date 2019-12-16 Cont ID  
Sent By   Date 2019-12-16 Time   Rev Time 0.00
Received By   Date 2019-12-16 Time   Sent To  
Notes
2019-12-16 10:03:48SEE ZONING COMMENTS FROM ROUND 1.

Review Stop Z ZONING
Rev No 1 Status N Date 2019-07-18 Cont ID  
Sent By fmittner Date 2019-07-18 Time 16:27 Rev Time 0.00
Received By fmittner Date 2019-07-18 Time 16:27 Sent To  
Notes
2019-07-18 16:27:50PHASE 1 PERMIT DEPICTS INTERIOR WORK. PHASE 2 PARKIGN
 LOT REQUIRES ZONING REVIEW.