Plan Review Details - Permit 19070371
Plan Review Stops For Permit 19070371
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-29 Cont ID  
Sent By dbattles Date 2019-07-29 Time 07:57 Rev Time 0.00
Received By dbattles Date 2019-07-29 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By dbattles Date 2019-07-17 Time 11:38 Rev Time 0.00
Received By dbattles Date 2019-07-17 Time 11:38 Sent To  
Notes
2019-07-17 11:39:33BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070371
 REVIEWED: JULY 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[R] = FBC RESIDENTIAL
  
 107.3.5 FBC[AMENDED]PLEASE PROVIDE IN-FILL DETAIL FOR
 WINDOW IN THE KITCHEN THAT WILL BECOME PART OF SOLID
 WALL BUILDING ENVELOPE.
  
 NOTES:
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-25 Cont ID  
Sent By ppetty Date 2019-07-25 Time 11:34 Rev Time 0.00
Received By ppetty Date 2019-07-25 Time 11:34 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By ppetty Date 2019-07-17 Time 09:34 Rev Time 0.00
Received By ppetty Date 2019-07-17 Time 09:34 Sent To B
Notes
2019-07-17 09:34:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-29 Cont ID  
Sent By dbattles Date 2019-07-29 Time 07:57 Rev Time 0.00
Received By dbattles Date 2019-07-23 Time 13:50 Sent To  
Notes
2019-07-24 13:50:14RESUB ROUTED TO PPETTY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-17 Cont ID  
Sent By dbattles Date 2019-07-17 Time 11:39 Rev Time 0.00
Received By dbattles Date 2019-07-09 Time 16:31 Sent To  
Notes
2019-07-10 16:31:47REVISION ROUTED TO PPETTY