Plan Review Details - Permit 19070310
Plan Review Stops For Permit 19070310
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 07:35 Rev Time 0.00
Received By shill Date 2019-07-19 Time 07:35 Sent To  
Notes
2019-07-19 07:37:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. INCORRECT BUILDING CODE REFERENCE, REVISE ID2,
 FS553.
  
 2. INCORRECT LEVEL OF ALTERATION, SEE FBC EB 504. THIS
 IS A RECONFIGURATION OF SPACE; STRUCTURAL VS NON
 STRUCTURAL IS NOT APPLICABLE.
  
 3. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected]. IF THE
 MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST
 REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE
 SUBMITTED WHEN RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By jleahy Date 2019-07-19 Time 11:30 Rev Time 0.00
Received By jleahy Date 2019-07-19 Time 11:30 Sent To  
Notes
2019-07-19 11:01:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT "KITCHENS,
 LAUNDRY ROOMS", FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION.
 NEC 210.12; FBC RE3902.16
  
 E3902.7 SINK RECEPTACLES. 125-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE RECEPTACLES THAT ARE LOCATED WITHIN 6
 FEET (1829 MM) OF THE OUTSIDE EDGE OF A SINK SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL
  
 E3902.8 BATHTUB OR SHOWER STALL RECEPTACLES. 125-VOLT,
 SINGLE PHASE, 15- AND 20-AMPERE RECEPTACLES THAT ARE
 LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE EDGE OF
 A BATHTUB OR SHOWER STALL SHALL HAVE GROUND-FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(8)]
  
 E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
  
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
  
 607.1.1RECEPTACLES. REPLACEMENT OF ELECTRICAL
 RECEPTACLES SHALL COMPLY WITH THE APPLICABLE
 REQUIREMENTS OF SECTION 406.4(D) OF NFPA 70
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-10 Cont ID  
Sent By pleduc Date 2019-07-10 Time   Rev Time 0.00
Received By pleduc Date 2019-07-10 Time 11:12 Sent To  
Notes
2019-07-10 11:22:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET ID 0 - THERE IS NO REFERENCE TO COMPLIANCE
 WITH THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROJECT SHALL COMPLY WITH THE 6TH EDITION OF THE
 FFPC
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET ID 0 - UNER THE ELECTRICAL NOTES THERE IS AN
 INCORRECT EDITION REFERENCE.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
  
 3) THERE ARE INDICATIONS OF FIRE SPRINKLER
 MODIFICATIONS.
  
 ANY WORK ON THE FIRE SPRINKLER OR FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-19 Cont ID  
Sent By jleahy Date 2019-07-19 Time 11:30 Rev Time 0.00
Received By jleahy Date 2019-07-08 Time 14:56 Sent To  
Notes
2019-07-09 14:56:51B02