Plan Review Details - Permit 19070284
Plan Review Stops For Permit 19070284
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-10-01 Cont ID  
Sent By dbattles Date 2019-10-01 Time 10:08 Rev Time 0.00
Received By dbattles Date 2019-10-01 Time 10:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-09 Cont ID  
Sent By dbattles Date 2019-09-09 Time 10:55 Rev Time 0.00
Received By dbattles Date 2019-09-09 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-13 Cont ID  
Sent By dbattles Date 2019-08-13 Time 07:44 Rev Time 0.00
Received By dbattles Date 2019-08-13 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-07-22 Cont ID  
Sent By dbattles Date 2019-07-22 Time 13:39 Rev Time 0.00
Received By dbattles Date 2019-07-22 Time 13:39 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-09-27 Cont ID  
Sent By jleahy Date 2019-09-27 Time 16:17 Rev Time 0.00
Received By jleahy Date 2019-09-27 Time 15:19 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-09-09 Cont ID  
Sent By fgiaquin Date 2019-09-09 Time 06:07 Rev Time 0.00
Received By fgiaquin Date 2019-09-09 Time 05:50 Sent To B
Notes
2019-09-09 06:07:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SIGNATURE ON ALL PLANS IS STILL A COPY. SEE PREVIOUS
 PLAN REVIEW COMMENTS ABOUT REQUIRED SIGNATURES AND
 SEALS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By fgiaquin Date 2019-08-12 Time 06:11 Rev Time 0.00
Received By fgiaquin Date 2019-08-12 Time 05:49 Sent To B
Notes
2019-08-12 06:11:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SIGNATURES ON DESIGN PROFESSIONAL'S SEALS ARE NOT
 ORIGINAL WET SIGNATURES, THEY ARE COPIES. PLEASE SEE
 REQUIREMENTS BELOW FOR SIGNATURES AND SEALS:
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-25 Cont ID  
Sent By fgiaquin Date 2019-07-25 Time 06:09 Rev Time 0.00
Received By fgiaquin Date 2019-07-25 Time 05:46 Sent To I
Notes
2019-07-25 06:09:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SOLAR PANELS NOT LISTED BY A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL) SUCH AS UL, CSA, INTEREK,
 ETC. VDE IS NOT A NRTL NEC 90.7, 110.2, 110.3B FBC
 107.2.1
  
 2. TWO SEPARATE PLANS PROVIDED. ONE IS SIGNED AND
 SEALED BY AN ENGINEER AND THE OTHER IS NOT SIGNED BY
 ANYONE??? PLEASE ADVISE WHY?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-10-01 Cont ID  
Sent By dbattles Date 2019-10-01 Time 10:08 Rev Time 0.00
Received By dbattles Date 2019-09-18 Time 14:30 Sent To  
Notes
2019-09-19 14:30:31RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-09 Cont ID  
Sent By dbattles Date 2019-09-09 Time 10:55 Rev Time 0.00
Received By dbattles Date 2019-08-22 Time 11:58 Sent To  
Notes
2019-08-22 11:58:49RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-13 Cont ID  
Sent By dbattles Date 2019-08-13 Time 07:44 Rev Time 0.00
Received By dbattles Date 2019-08-05 Time 13:56 Sent To  
Notes
2019-08-06 13:56:59RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-25 Cont ID  
Sent By fgiaquin Date 2019-07-25 Time 06:10 Rev Time 0.00
Received By fgiaquin Date 2019-07-08 Time 14:04 Sent To  
Notes
2019-07-09 14:05:02ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2019-09-25 Time   Rev Time 0.00
Received By pgreilic Date 2019-09-25 Time 09:20 Sent To E
Notes
2019-09-25 09:20:361.) PROVIDE WRITTEN RESPONSES TO EACH COMMENT
 SPECIFICALLY ADDRESSING COMMENTS FROM FIRST REVIEW
 2.) PROVIDE DOCUMENTATION OF POA APPROVAL
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2019-08-27 Time   Rev Time 0.00
Received By pgreilic Date 2019-08-27 Time 11:35 Sent To E
Notes
2019-08-27 11:35:581.) PROVIDE WRITTEN RESPONSES TO EACH COMMENT
 SPECIFICALLY ADDRESSING COMMENTS FROM FIRST REVIEW
 2.) PROVIDE DOCUMENTATION OF POA APPROVAL
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2019-08-08 Time   Rev Time 0.00
Received By pgreilic Date 2019-08-08 Time 10:50 Sent To E
Notes
2019-08-08 10:51:521.) PROVIDE WRITTEN RESPONSES TO EACH COMMENT
 SPECIFICALLY ADDRESSING COMMENTS FROM FIRST REVIEW
 2.) PROVIDE DOCUMENTATION OF POA APPROVAL
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2019-07-10 Time   Rev Time 0.00
Received By pgreilic Date 2019-07-10 Time 13:05 Sent To B
Notes
2019-07-10 13:08:00SEC 94-309 MISCELLANEOUS SUPPLEMENTAL DISTRICT
 REGULATIONS
  
 (4) ROOFTOP SYSTEMS.
  
 A. SLOPED ROOFS?HEIGHT . ON SLOPED ROOFS, THE HIGHEST
 POINT OF THE SOLAR COLLECTORS SHALL NOT EXCEED THE
 HIGHEST ROOFTOP PEAK AND MUST BE INSTALLED PARALLEL TO
 THE ROOF SURFACES TO WHICH THEY ARE ATTACHED PROVIDED
 SUCH LOCATION DOES NOT IMPAIR THE EFFECTIVE OPERATION
 OF THE SOLAR COLLECTORS. SOLAR COLLECTORS MAY BE
 MOUNTED UP TO ONE FOOT ABOVE ROOF SURFACES TO WHICH
 THEY ARE ATTACHED.
  
 B. FLAT ROOFS?HEIGHT . ON FLAT ROOFS, THE HIGHEST POINT
 OF THE SYSTEM SHALL BE PERMITTED TO EXCEED THE
 DISTRICT'S HEIGHT LIMIT BY A MAXIMUM OF SIX FEET ABOVE
 THE ROOFTOP TO WHICH IT IS ATTACHED.
  
  
 ---PROVIDE ELEVATIONS OR OTHERWISE INDICATE ON THE
 PLANS THAT THE PROPOSED SYSTEM COMPLIES WITH THE
 REFERENCED CODE SECTION----
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]