Plan Review Details - Permit 19070270
Plan Review Stops For Permit 19070270
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-07-12 Cont ID  
Sent By jleahy Date 2019-07-12 Time 11:33 Rev Time 0.00
Received By jleahy Date 2019-07-12 Time 11:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-12 Cont ID  
Sent By jleahy Date 2019-07-12 Time 11:33 Rev Time 0.00
Received By jleahy Date 2019-07-12 Time 11:33 Sent To Z
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-07-18 Cont ID  
Sent By abelisle Date 2019-07-18 Time 14:56 Rev Time 0.00
Received By abelisle Date 2019-07-18 Time 14:56 Sent To I
Notes
2019-07-18 14:55:377/18/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 1) CONTRACTOR CAME IN AND CLARIFIED PREVOUS COMMENTS,
 NO OPENINGS NEAR GENERATOR
  
 SENT TO PROCESSING
  
 ATELYO BELISLE
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By abelisle Date 2019-07-16 Time 06:38 Rev Time 0.00
Received By abelisle Date 2019-07-09 Time 06:41 Sent To Z
Notes
2019-07-09 07:00:337/9/19 DENIED
 THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?) FROM
 THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE, EXHAUST
 SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS OTHERWISE
 STATED IN THE MANUFACTURES SPECIFICATION INSTRUCTIONS.
  
 A PORTION OF SHEET 8 IS ILLEGIBLE. SUBMIT TWO COPIES OF
 CLEAR AND LEGIBLE PLANS FOR REVIEW. WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) ARE
 NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471. SUBMIT ORRIGINAL
 COPIES
  
 SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE, SURVEY INDICATES A
 DIFFERENT LENGTH OF GAS LINE FROM TANK TO GENERATOR.
 PLEASE CLARIFY PER 2017 FBC FUEL GAS, SECS. 402.4.1,
 402.4.2
  
 CLARIFY BTU LOAD, SPECS SHOW 127K BTU @ FULL LOAD.
 PLANS CALL FOR 330K BTU. PLEASE CLARIFY
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-17 Cont ID  
Sent By ajones Date 2019-07-17 Time 16:15 Rev Time 0.00
Received By ajones Date 2019-07-05 Time 12:57 Sent To  
Notes
2019-07-08 12:58:02ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-17 Cont ID  
Sent By ajones Date 2019-07-17 Time 16:14 Rev Time 0.00
Received By ajones Date 2019-07-17 Time 16:14 Sent To PC
Notes
***NONE***