Plan Review Details - Permit 19070245
Plan Review Stops For Permit 19070245
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-06 Cont ID  
Sent By rmcdouga Date 2019-09-06 Time 18:45 Rev Time 0.00
Received By rmcdouga Date 2019-09-06 Time 18:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-23 Cont ID  
Sent By jwitmer Date 2019-07-23 Time 15:51 Rev Time 0.00
Received By jwitmer Date 2019-07-23 Time 14:47 Sent To  
Notes
2019-07-23 15:51:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070245
 ADD: 1701 S. FLAGLER DR. SUITE: 407
 CONT: BENCHMARK PAINTING & CARPENTRY
 TEL: 908-514-3123
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY, JULY 23, 2019
 ACTION: DENIED
  
 1) A DESIGNER OF RECORD WILL BE REQUIRED FOR THE
 PURPOSES RELATING TO COMPLIANCE WITH WIND-RESISTANCE
 PROVISIONS OF THE CODE.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 107.3.4.2 CERTIFICATIONS BY
 CONTRACTORS AUTHORIZED UNDER THE PROVISIONS OF SECTION
 489.115 FLORIDA STATUTES, SHALL BE CONSIDERED
 EQUIVALENT TO SEALED PLANS AND SPECIFICATIONS
 BY A PERSON LICENSED UNDER CHAPTER 471, FLORIDA
 STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY LOCAL
 ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR PERMITTING
 PURPOSES RELATING TO COMPLIANCE WITH THE
 WIND-RESISTANCE PROVISIONS OF THE CODE OR ALTERNATE
 METHODOLOGIES APPROVED BY THE FLORIDA BUILDING
 COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. LOCAL
 ENFORCEMENT AGENCIES MAY RELY UPON SUCH CERTIFICATION
 BY CONTRACTORS THAT THE PLANS AND SPECIFICATIONS
 SUBMITTED CONFORM TO THE REQUIREMENTS OF THE CODE FOR
 WIND RESISTANCE. UPON GOOD CAUSE SHOWN, LOCAL
 GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT OR
 REJECT PLANS SEALED BY PERSONS LICENSED UNDER CHAPTERS
 471,481 OR 489, FLORIDA
 STATUTES.
  
 2) MISSING THE WIND DESIGN CRITERIA BY A DESIGN
 PROFESSIONAL. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 2.6TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2.7 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. ALL
 PRODUCT APPROVALS ARE IN VASD SUBMIT THE PRESSURES IN
 VASD.
  
 3) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
 (B) WINDOWS & MULLIONS.
  
 4) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-23 Cont ID  
Sent By jpearson Date 2019-09-23 Time 08:07 Rev Time 0.00
Received By jpearson Date 2019-09-23 Time 08:07 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-09-06 Cont ID  
Sent By jpearson Date 2019-09-06 Time 09:57 Rev Time 0.00
Received By jpearson Date 2019-09-06 Time 09:57 Sent To  
Notes
2019-09-06 09:57:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 (SIGNATURE BY CGC NOT ACCEPTABLE, MUST BE AN ELECTRICAL
 CONTRACTOR OR A DESIGN PROFESSIONAL. PROVIDE
 CORRECTION.)
 2. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-25 Cont ID  
Sent By jpearson Date 2019-07-25 Time 15:18 Rev Time 0.00
Received By jpearson Date 2019-07-25 Time 14:16 Sent To  
Notes
2019-07-25 14:59:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. IN EACH PLAN SET, THERE ARE TWO ELECTRICAL SHEETS,
 MARKED ELECTRICAL PLAN #1 AND ELECTRICAL PLAN #2. THESE
 SHEETS APPEAR TO BE IDENTICAL. PROVIDE CLARIFICATION OR
 REMOVE REDUNDANT SHEET. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-21 Cont ID  
Sent By pleduc Date 2019-08-21 Time   Rev Time 0.00
Received By pleduc Date 2019-08-21 Time 13:19 Sent To  
Notes
2019-08-21 13:21:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE INDICATIONS OF SMOKE ALARMS ON THE
 ELECTRICAL PLAN.
  
 PLEASE HAVE MANUFACTURERS SPECIFICATIONS SHEETS FOR
 FIRE INSPECTOR REVIEW SO THAT THE LOCATION(S) WILL BE
 CONFIIRMED .
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-10 Cont ID  
Sent By pleduc Date 2019-07-10 Time   Rev Time 0.00
Received By pleduc Date 2019-07-10 Time 14:23 Sent To  
Notes
2019-07-10 14:29:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE NO INDICATIONS OF SMOKE ALARMS ON THE
 ELECRICAL PLAN.
  
 WITH THE RELOCATION OF THE DOOR, THE RELOCATION OF THE
 SD MAY BE REQUIRED.
  
 PER NFPA 101, CH 31, EXISTING APARTMENT OCCUPANCIES
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
  
 31.3.4.5.2 SMOKE ALARMS REQUIRED BY 31.3.4.5.1 SHALL
 NOT BE REQUIRED TO
 BE PROVIDED WITH A SECONDARY (STANDBY) POWER SOURCE.
  
 CH 9
  
 9.6.2.10.4* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT
 BE
 INSTALLED WITHIN AN AREA OF EXCLUSION DETERMINED BY A
 10 FT (3.0 M)
 RADIAL DISTANCE ALONG A HORIZONTAL FLOW PATH FROM A
 STATIONARY OR
 FIXED COOKING APPLIANCE, UNLESS LISTED FOR INSTALLATION
 IN CLOSE
 PROXIMITY TO COOKING APPLIANCES. SMOKE ALARMS AND SMOKE
 DETECTORS INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT
 (6.1 M) ALONG A
 HORIZONTAL FLOW PATH FROM A STATIONARY OR FIXED COOKING
 APPLIANCE
 SHALL BE EQUIPPED WITH AN ALARM-SILENCING MEANS OR USE
 PHOTOELECTRIC DETECTION.
 EXCEPTION: SMOKE ALARMS OR SMOKE DETECTORS THAT USE
 PHOTOELECTRIC DETECTION SHALL BE PERMITTED FOR
 INSTALLATION AT A
 RADIAL DISTANCE GREATER THAN 6FT (1.8 M) FROM ANY
 STATIONARY OR
 FIXED COOKING APPLIANCE WHEN THE FOLLOWING CONDITIONS
 ARE MET:
 (1) THE KITCHEN OR COOKING AREA AND ADJACENT SPACES
 HAVE NO
 CLEAR INTERIOR PARTITIONS OR HEADERS
 (2) THE 10 FT (3.0 M) AREA OF EXCLUSION WOULD PROHIBIT
 THE
 PLACEMENT OF A SMOKE ALARM OR SMOKE DETECTOR REQUIRED
 BY
 OTHER SECTIONS OF THIS NFPA 72.
  
 9.6.2.10.5* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT
 BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 A DOOR TO A
 BATHROOM CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN
 CLOSE PROXIMITY TO SUCH LOCATIONS. [72:29.8.3.4 (6) ]
  
 9.6.2.10.6 SYSTEM SMOKE DETECTORS IN ACCORDANCE WITH
 NFPA 72,
 NATIONAL FIRE ALARM AND SIGNALING CODE, AND ARRANGED TO
 FUNCTION IN THE SAME MANNER AS SINGLE-STATION OR
 MULTIPLE-STATION
 SMOKE ALARMS SHALL BE PERMITTED IN LIEU OF SMOKE ALARMS
  
 PLEASE REVIEW AND ENSURE COMPLIANCE WITH THE CODE AND
 MANUFACTURE'S SPECIFICATIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-09-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-19 Time 13:45 Sent To  
Notes
2019-09-20 13:45:20RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-12 Cont ID  
Sent By shill Date 2019-09-12 Time 07:36 Rev Time 0.00
Received By shill Date 2019-08-19 Time 13:10 Sent To  
Notes
2019-08-20 13:10:59B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-05 Cont ID  
Sent By shill Date 2019-08-05 Time 08:28 Rev Time 0.00
Received By shill Date 2019-07-03 Time 13:26 Sent To  
Notes
2019-07-08 13:26:24B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-23 Cont ID  
Sent By jwitmer Date 2019-07-23 Time 15:51 Rev Time 0.00
Received By jwitmer Date 2019-07-23 Time 14:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-07-27 Cont ID  
Sent By cmontell Date 2019-07-27 Time 06:19 Rev Time 0.00
Received By cmontell Date 2019-07-27 Time 06:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By tklarge Date 2019-09-10 Time 10:07 Rev Time 0.00
Received By tklarge Date 2019-09-10 Time 10:07 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-26 Cont ID  
Sent By gjohnson Date 2019-07-26 Time 11:46 Rev Time 0.00
Received By gjohnson Date 2019-07-26 Time 09:42 Sent To  
Notes
2019-07-26 12:29:041ST REVIEW: 19070245
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. IN EACH PLAN SET, THERE ARE TWO PLUMBING SHEETS,
 MARKED PLUMBING PLAN #1 AND PLUMBING PLAN #2. THESE
 SHEETS APPEAR TO BE IDENTICAL. PROVIDE CLARIFICATION OR
 REMOVE REDUNDANT SHEET. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2019-09-12 Cont ID  
Sent By shill Date 2019-09-12 Time 07:36 Rev Time 0.00
Received By shill Date 2019-09-12 Time 07:36 Sent To  
Notes
2019-09-12 07:36:43INTERIOR RENOVATION (NO ZONING REVIEW REQUIRED)

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-22 Cont ID  
Sent By pgreilic Date 2019-07-22 Time 14:17 Rev Time 0.00
Received By pgreilic Date 2019-07-19 Time 14:51 Sent To  
Notes
2019-07-22 14:18:261.) PROVIDE HOA APPROVAL
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]