| 2019-08-05 09:32:02 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. |
| | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON |
| | THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING |
| | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR |
| | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 |
| | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. YOU HAVE |
| | ONLY SUBMITTED ONE SPECIFICATION SHEET FOR EACH |
| | REGULATOR. |
| | 2) THE APPLICATION NOTES THAT TIKKI TORCHES ARE TO BE |
| | INSTALLED YET THE TIKKI TORCHES ARE NOT SHOWN ON THE |
| | GAS DRAWING. THE TIKKI TORCHES SHALL BE SHOWN ON THE |
| | GAS DRAWING ALONG WITH THE LENGTH OF ALL PIPING AND THE |
| | PLAN SHALL CLEARLY SHOW THE LENGTH OF ALL CUT SECTIONS |
| | OF PIPE PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. |
| | OR 2017 FBC-R SEC. G2413.4.1, G2413.4.2. |
| | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED FOR |
| | THE TIKKI TORCHES AND THE SECOND MOUSQUITO TRAP AND ALL |
| | PIPE SIZES. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). |
| | 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| | SEC. G 2413.4.1, G2413.4.2. |
| | 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. |
| | 7) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS |
| | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | 8) THE PLAN NOTES THAT TWO MOSQUITO TRAPS WILL BE |
| | INSTALLED BUT ONLY ONE IS SHOWN ON THE GAS DRAWING AND |
| | NOTED ON THE PERMIT APPLICATION. CLARIFY. |
| | 9) SUBMIT A SURVEY/SITE PLAN SHOWING THE LOCATION OF |
| | THE MOSQUITO TRAPS AND ALSO THE TIKKI TORCHES.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 10) THE PLANS INDICATE AN EXISTING LP TANK AND CITY |
| | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. |
| | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE |
| | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE |
| | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. FGC SECS. 401.4, |
| | 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4, |
| | G2412.8, G2413.1, G2413.2, G2413.3. |
| | 11) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO ALL |
| | APPLIANCES. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD. |
| | 12) SHOW THE DISTANCE FROM THE GAS METER TO THE MOST |
| | REMOTE REGULATOR ON THE SYSTEM. |
| | 13) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE MP |
| | REGULATOR. 2017 FBC-FUEL GAS SEC. 410.2 (7). |
| | 14) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE |
| | REGULATORS DO NOT CORRELATE WITH THE REGULATORS NOTED |
| | ON THE GAS DRAWING. CLARIFY. |
| | 15) DOCUMENTS HAVE BEEN SUBMITTED FOR THE MAGNESIUM |
| | ANODE, ANCHORING OF THE UNDERGROUND LP TANK, AND TANK |
| | DATA SHEET. IF YOU ARE CONNECTING TO AN EXISTING LP |
| | TANK, WHY ARE THESE DOCUMENTS BEING SUBMITTED? CLARIFY. |
| | 16)THE DOCUMENTS THAT HAVE BEEN SUBMITTED FOR THE LP |
| | TANK ANCHORING BEAR A COPIED ENGINEER'S SIGNATURE AND |
| | SEAL. DOCUMENTS THAT ARE BEING SUBMITTED FOR PUBLIC |
| | RECORD MUST BEAR THE ORIGINAL SEAL AND SIGNATURE OF THE |
| | ENGINEER PER THE FL. ADMIN. CODE RULE 61G15-23.001. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |