| 2019-07-12 15:24:42 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 1901 |
| | REVIEWED: JULY 12, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH |
| | CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN |
| | ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL |
| | COST OF WORK. |
| | - THE VALUE SEEMS LOW FOR THE AMOUNT OF SLIDERS |
| | INSTALLED. WAS THIS INSTALLED BT A CONTRACTOR? |
| | - THE VALUE OF WORK SHOULD BE EQUAL TO WHAT A |
| | CONTRACTOR WOULD CHARGE FOR TIME, MATERIALS AND |
| | OVERHEAD. |
| | - IF THIS WAS OWNER BUILDER THAN AN OWNER BUILDER |
| | AFFIDAVIT NEEDS TO BE FILLED OUT AND SIGNED HERE AT THE |
| | BUIDING DEPARTMENT BY THE OWNER. |
| | THE FORM CAN BE DOWNLOADED FROM. HTTPS://WWW.WPB.ORG/DE |
| | PARTMENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FO |
| | RMS |
| | |
| | 2) 609.7.2.1 FBC[R] MASONRY, CONCRETE OR OTHER |
| | STRUCTURAL SUBSTRATE. WHERE THE WOOD SHIM OR BUCK |
| | THICKNESS IS LESS THAN 11/2 INCHES (38 MM), WINDOW AND |
| | GLASS DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE |
| | JAMB, OR BY JAMB CLIP AND ANCHORS SHALL BE EMBEDDED |
| | DIRECTLY INTO THE MASONRY, CONCRETE OR OTHER |
| | SUBSTANTIAL SUBSTRATE MATERIAL. ANCHORS SHALL |
| | ADEQUATELY TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME |
| | INTO THE ROUGH OPENING SUBSTRATE [SEE FIGURES |
| | R609.7.2(1) AND R6097.2(2)]. |
| | - PROVIDE WINDOW BUCK DETAIL. |
| | |
| | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| | FIXED WINDOWS ABOVE SLIDERS AND WINDOW MULL BETWEEN THE |
| | FIXED WINDOWS. |
| | - PLEASE PROVIDE TWO COPIES EACH NEW PRODUCT APPROVAL |
| | AND ONE COPY ADDITIONAL FOR PRODUCT APPROVALS ALREADY |
| | SUBMITTED AS ONLY ONE SET WAS TURNED IN WITH THE |
| | PERMIT. |
| | |
| | 4) DESIGN DATA: |
| | A. RISK CATEGORY = ___(II) |
| | B. EXPOSURE CATEGORY = ___(B,C OR D) |
| | C. BUILDING CLASSIFICATION = __________(ENCLOSED) |
| | D. MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE |
| | HEIGHT MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND |
| | ROOF PEAK, OR THE ROOF DECK ABOVE) |
| | E. WIND SPEED V ULT = _____(170) |
| | F. WIND SPEED V ASD = _____(132) |
| | COMPONANT & CLADDING: |
| | FBC TABLE 301.2(2) FBC[R] |
| | DESIGN PRESSURE = +___ & -___ |
| | 301.2(3) FBC[R] CHECK EXPOSURE AND M.R.H. TO DETERMINE |
| | IF ADJUSTMENT FACTOR NEEDED. |
| | MULTIPLE DESIGN PRESSURES BY THE ADJUSTMENT FACTOR IF < |
| | OR > 1.00 |
| | |
| | 5) 107.5.3 FBC[AMENDED] OPENING SCHEDULE: |
| | PROVIDE OPENEING SIZE AND PRESSURE ON EACH WINDOW/DOOR. |
| | INDICATE IF THE OPENING IS IN THE INTERIOR OR EXTERIOR |
| | ZONE. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |