| Plan Review Stops For Permit 19070181 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-12 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-12 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-12 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-12 |
Time |
11:35 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
N |
Date |
2019-08-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-08-23 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-08-23 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-08-08 |
Time |
05:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-08-08 |
Time |
04:30 |
Sent To |
|
|
| Notes |
| 2019-08-08 04:51:07 | 1) THE GAS DRAWING THAT HAS BEEN SUBMITTED NOTES ALL | | | PIPING TO BE 1/2" GALVANIZED YET YOU HAVE SUBMITTED A | | | SIZING TABLE FOR POLYETHYLENE PIPE. CLARIFY. SUBMIT TWO | | | COPIES OF THE APPLICABLE GAS SIZING TABLES FOR THIS | | | INSTALLATION. 2ND REQUEST. | | | 2) YOU HAVE SUBMITTED ONE SHEET OF THE MANUFACTURER'S | | | SPECIFICATIONS AND NOTHING ELSE FOR THE REGULATORS. | | | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE PRESSURE REGULATORS. REGULATORS | | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | | APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON THE | | | SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING | | | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR | | | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. 2ND REQUEST. | | | 3) SINCE THIS SYSTEM IS BEING INCREASED TO A 2 PSI | | | SYSTEM, PRESSURE REGULATORS ARE REQUIRED AT EACH | | | APPLIANCE. SHOW THE LOOCATION OF EACH REGULATOR ON THE | | | GAS DRAWING. | | | 4) WHERE CCONNECTED TO RIDGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP | | | REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017 | | | FBC-FUEL GAS SEC. 410.2 (7). | | | | | | NOTE: DO NOT RESUBMIT THESE PLANS UNTIL YOU CONTACT | | | THIS REVIEWER TO DISCUSS THESE COMMENTS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-08-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-08-02 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-08-02 |
Time |
06:10 |
Sent To |
|
|
| Notes |
| 2019-08-02 07:00:59 | 1) THE GAS DRAWING THAT HAS BEEN SUBMITTED NOTES ALL | | | PIPING TO BE 1/2" GALVANIZED YET YOU HAVE SUBMITTED A | | | SIZING TABLE FOR POLYETHYLENE PIPE. CLARIFY. SUBMIT TWO | | | COPIES OF THE APPLICABLE GAS SIZING TABLES FOR THIS | | | INSTALLATION. | | | 2) YOU HAVE SUBMITTED TWO SHEETS OF THE MANUFACTURER'S | | | SPECIFICATIONS AND NOTHING ELSE FOR THE REGULATORS. | | | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE PRESSURE REGULATORS. REGULATORS | | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | | APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON THE | | | SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING | | | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR | | | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-07-13 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2019-07-13 |
Time |
05:14 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2019-07-13 |
Time |
05:13 |
Sent To |
|
|
| Notes |
| 2019-07-13 05:55:11 | 7/13/19 DENIED | | | | | | SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE | | | APPLIANCE. COMPLY WITH 2017 FBC FUEL GAS TABLE 402.4 | | | (28) OR 2017 FBC FUEL GAS RES.TABLE G2413.4 (12) | | | SCHEDULE 40 METALLIC PIPE FOR THE PROPER PIPE SIZE AND | | | BTU LOAD. | | | | | | PLEASE INDICATE THE BTU LOAD FOR THE OPTIONAL POOL | | | HEATER AND GRILL. | | | | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-08-08 |
Time |
05:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-08-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2019-08-07 14:07:07 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-08-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-08-02 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-07-18 |
Time |
11:26 |
Sent To |
I |
|
| Notes |
| 2019-07-19 11:26:27 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-07-16 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-07-16 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-07-05 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2019-07-08 12:59:25 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
pgreilic |
Date |
2019-07-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2019-07-09 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2019-07-09 15:35:13 | 1.) LANDSCAPE SCREENING REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|