Plan Review Details - Permit 19070147
Plan Review Stops For Permit 19070147
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-08-02 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-07-14 Cont ID  
Sent By rmcphers Date 2021-07-14 Time 11:10 Rev Time 0.00
Received By rmcphers Date 2021-07-14 Time 11:08 Sent To  
Notes
2021-07-14 11:10:28REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) BUILDING CODE VERSION SHOWN ON COVER PAGE (001
 CS-000) IS INCORRECT - SHOULD BE 2017 FBC
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS FOR THE
 NEW EXTERIOR DOORS. FBC WPB AMENDMENTS 107.3.4.1 (ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD IF THE PRODUCT
 APPROVAL NUMBERS ARE NOT LISTED ON THE DRAWINGS)
 3) DOOR PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY
 LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-03-24 Cont ID  
Sent By rmcphers Date 2020-03-24 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2020-03-24 Time 11:09 Sent To  
Notes
2020-03-24 11:58:34REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) BUILDING CODE VERSION SHOWN ON COVER PAGE (001
 CS-000) IS INCORRECT - SHOULD BE 2017 FBC
 2) PLEASE PROVIDE PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOORS. FBC WPB AMENDMENTS 107.3.4.1
 3) PLEASE PROVIDE THE FLOORING SYSTEM ACOUSTICAL
 TESTING REPORT FOR THE TILE FLOORING AND UNDERLAYMENT
 BEING USED IN THE UNITS TO COMPLY WITH FBC 1207.3 (IIC)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-02-05 Cont ID  
Sent By rmcphers Date 2020-02-05 Time 15:52 Rev Time 0.00
Received By rmcphers Date 2020-02-05 Time 12:11 Sent To  
Notes
2020-02-05 15:52:09REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - AS NOTED ON PREVIOUS REVIEW BY
 (DYLAN BATTLES)
 1) BUILDING CODE VERSION SHOWN ON COVER PAGE (001
 CS-000) IS INCORRECT - SHOULD BE 2017 FBC
 2) PLEASE PROVIDE PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOORS. FBC WPB AMENDMENTS 107.3.4.1
 3) PLEASE PROVIDE STAIRWAY RAILING DETAILS (SHOW
 ATTACHMENTS TO EXISTING STRUCTURE) TO COMPLY WITH FBC
 1014
 4) PLEASE PROVIDE THE FLOORING SYSTEM ACOUSTICAL
 TESTING REPORT FOR THE FLOORING AND UNDERLAYMENT BEING
 USED TO COMPLY WITH FBC 1207 (IIC) AND (STC)
 5) PLEASE ADD NOTE TO DRAWING SP-100 THAT PARKING LOT
 UPGRADES WILL BE DONE UNDER A SEPARATE BUILDING PERMIT.
 6) PLEASE SHOW THE ACCESSIBLE EATING AREAS IN THE
 HEARTH ROOM.
 7) - ADDED COMMENT - PLEASE PROVIDE A LETTER FROM THE
 CONTRACTOR STATING THAT THE PBC ASBESTOS REQUIREMENTS
 WILL BE FOLLOWED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-11-26 Cont ID  
Sent By dbattles Date 2019-11-26 Time 14:08 Rev Time 0.00
Received By dbattles Date 2019-11-26 Time 14:08 Sent To  
Notes
2019-11-26 14:13:212ND REVIEW NOVEMBER 26, 2019
  
 I SEE A COMMENT RESPONSE SHEET THAT STATES VARIOUS
 SHEETS REPLACED, BUT THEY WERE NOT UPLOADED INTO
 PROJECTDOX.
 PLEASE UPLOAD THE NEW SHEETS AND I CAN COMPLETE MY
 REVIEW.
  
  
  
  
 BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070147
 REVIEWED: AUGUST 12, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 107.5.3 FBC[AMENDED] CODE EDITION.
 PLEASE UPDATE SHEET CS-000 WHERE IS STATES FBC 2014 5TH
 EDITION TO READ FLORIDA BUILDING CODE 6TH EDITION
 (2017) AND AMENDMENTS ARE 2017 AS WELL.
  
 2) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 3) 501 FBC[EXISTING] IF WORK AREA PLEASE STATE THE
 LEVEL OF ALTERATION FOR WORK BEING PERFORMED.
 A) LEVEL 1 ALTERATION
 B) LEVEL 2 ALTERATION
 C) LEVEL 3 ALTERATION
  
 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 EXTERIOR DOORS AND SIDE PANELS AS APPLICABLE.
  
 4) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE RAILS
 ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED.
  
 5) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT
 FLOORING UNDERLAYMENT IS PROPOSED? IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS WILL BE
 REQUIRED:
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
 -THIS WOULD APPLY TO SECOND AND THIRD FLOORS IN THE
 SLEEPING UNITS ONLY.
  
 6) 806.1 FBC[B] GENERAL. COMBUSTIBLE DECORATIVE
 MATERIALS, OTHER THAN DECORATIVE VEGETATION, SHALL
 COMPLY WITH SECTIONS 806.2 THROUGH 806.8. [F] 806.2
 NONCOMBUSTIBLE MATERIALS. THE PERMISSIBLE AMOUNT OF
 NONCOMBUSTIBLE MATERIALS SHALL NOT BE LIMITED.
 -PROVISO: IF WINDOW TREATMENTS FALL UNDER 806.3 THEN
 SUBMIT REPORTS TO INSPECTOR PRIOR TO INSTALL.
  
 7) PLEASE ADD NOTE TO SHEET SP-100 THAT PARKING LOT
 UPGRADES WILL BE DONE UNDER SEPARATE PERMIT.
  
 8) 902.1 FBC[A]GENERAL. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. 902.3
 HEIGHT. THE TOPS OF DINING SURFACES AND WORK SURFACES
 SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 -PLEASE SHOW ACCESSIBLE EATING AREAS IN HEARTHROOM
  
 PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By dbattles Date 2019-08-12 Time 16:07 Rev Time 0.00
Received By dbattles Date 2019-08-09 Time 07:53 Sent To  
Notes
2019-08-12 16:09:53BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070147
 REVIEWED: AUGUST 12, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 107.5.3 FBC[AMENDED] CODE EDITION.
 PLEASE UPDATE SHEET CS-000 WHERE IS STATES FBC 2014 5TH
 EDITION TO READ FLORIDA BUILDING CODE 6TH EDITION
 (2017) AND AMENDMENTS ARE 2017 AS WELL.
  
 2) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 3) 501 FBC[EXISTING] IF WORK AREA PLEASE STATE THE
 LEVEL OF ALTERATION FOR WORK BEING PERFORMED.
 A) LEVEL 1 ALTERATION
 B) LEVEL 2 ALTERATION
 C) LEVEL 3 ALTERATION
  
 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 EXTERIOR DOORS AND SIDE PANELS AS APPLICABLE.
  
 4) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE RAILS
 ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED.
  
 5) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT
 FLOORING UNDERLAYMENT IS PROPOSED? IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS WILL BE
 REQUIRED:
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
 -THIS WOULD APPLY TO SECOND AND THIRD FLOORS IN THE
 SLEEPING UNITS ONLY.
  
 6) 806.1 FBC[B] GENERAL. COMBUSTIBLE DECORATIVE
 MATERIALS, OTHER THAN DECORATIVE VEGETATION, SHALL
 COMPLY WITH SECTIONS 806.2 THROUGH 806.8. [F] 806.2
 NONCOMBUSTIBLE MATERIALS. THE PERMISSIBLE AMOUNT OF
 NONCOMBUSTIBLE MATERIALS SHALL NOT BE LIMITED.
 -PROVISO: IF WINDOW TREATMENTS FALL UNDER 806.3 THEN
 SUBMIT REPORTS TO INSPECTOR PRIOR TO INSTALL.
  
 7) PLEASE ADD NOTE TO SHEET SP-100 THAT PARKING LOT
 UPGRADES WILL BE DONE UNDER SEPARATE PERMIT.
  
 8) 902.1 FBC[A]GENERAL. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. 902.3
 HEIGHT. THE TOPS OF DINING SURFACES AND WORK SURFACES
 SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 -PLEASE SHOW ACCESSIBLE EATING AREAS IN HEARTHROOM
  
 PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW EACH
 COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By jleahy Date 2019-09-27 Time 14:52 Rev Time 0.00
Received By jleahy Date 2019-09-27 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-08-13 Cont ID  
Sent By jpearson Date 2019-08-21 Time 14:02 Rev Time 0.00
Received By jpearson Date 2019-08-13 Time 14:02 Sent To  
Notes
2019-08-13 14:02:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN ONLY PROVIDED FOR FIRST FLOOR.
 PROVIDE ELECTRICAL PLAN OF ALL PROPOSED WORK FOR
 REVIEW, SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2021-07-16 Cont ID  
Sent By pleduc Date 2021-07-16 Time   Rev Time 0.00
Received By pleduc Date 2021-07-16 Time 13:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2021-06-22 Cont ID  
Sent By pleduc Date 2021-06-22 Time   Rev Time 0.00
Received By pleduc Date 2021-06-22 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-03-02 Cont ID  
Sent By pleduc Date 2020-03-02 Time   Rev Time 0.00
Received By pleduc Date 2020-03-02 Time 13:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-01-27 Cont ID  
Sent By pleduc Date 2020-01-27 Time   Rev Time 0.00
Received By pleduc Date 2020-01-27 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-11-06 Cont ID  
Sent By pleduc Date 2019-11-06 Time   Rev Time 0.00
Received By pleduc Date 2019-11-06 Time 10:22 Sent To  
Notes
2019-11-06 10:23:10FIRE COMMENTS NOT SPECIFICALLY ADDRESSED AND REINSERTED
 WITH ADDITIONAL COMMENTS BELOW:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 THERE IS INSUFFICIENT INFORMATION PROVIDED TO CONDUCT A
 DETAILED LIFE SAFETY REVIEW.
  
  
 1) SHEET A 101 - FIRE MISUNDERSTOOD THE WORDING OF THE
 # 26 NOTE - COMPLIED.
  
  
  
 2) NO LIFE SAFETY SHEETS - IS THE PROPOSED PROJECT
 BEING CONDUCTED WITH THE BUILDING OCCUPIED WITH GUESTS
 ON THE SAME OR ANY FLOORS.
  
 PLEASE CLARIFY AND PROVIDE DETAILS OF PHASING OR
 SEQUENCES OF WORK.
  
 NOT COMPLIED, PLEASE ADDRESS.
  
  
 2A) THERE ARE INDICATIONS OF FLOORS, WALLS, STAIRS,
 CEILINGS, BEING WORKED ON.
  
 HOW WILL EXITING AND MAINTNENCE FOR ALL LIFE SAFETY
 SYSTEM BEING ACCOMPLISHED WHILE BEING OCCUPIED?
  
 A DETAILED LIFE SAFETY PLAN FOR EACH FLOOR IS REQUIRED
 INDICATING HOW ALL LIFE SAFETY SYSTEMS, EXITS, TRAVEL
 DISTANCES, COMMON PATHS OT TRAVEL AND EXIT DISCHARGES
 WILL BE MAINTAINED.
  
  
 NOT COMPLIED, PLEASE ADDRESS
  
  
  
 3) FIRE ALARM AND FIRE SPRINKLER - THE PROPOSED WORK
 MAY AFFECT FA & FS EQUIPMENT, DEVICES, HEADS, FUNCTION,
 ETC.
  
 ANY WORK ON THE FA & FS SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIST AND SHOP DRAWINGS BY CERTIFIED
 CONTRACTORS.
  
 THE FA & FS SYSTEMS SHALL BE MAINTAINED THROUGHOUT DEMO
 AND CONSTRUCTION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE ON THE LIFE SAFETY PLAN SHEETS.
  
  
 NOT COMPLIED, PLEASE ADDRESS
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 NOT COMPLIED, PLEASE ADDRESS
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 STATEMENT RESUBMITTED
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-10 Cont ID  
Sent By pleduc Date 2019-07-10 Time   Rev Time 0.00
Received By pleduc Date 2019-07-10 Time 15:05 Sent To  
Notes
2019-08-12 09:58:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 THERE IS INSUFFICIENT INFORMATION PROVIDED TO CONDUCT A
 DETAILED LIFE SAFETY REVIEW.
  
  
 1) SHEET A 101 - THERE IS A CIRCLE 26 NOTE : INDICATING
 REPAIR/REPLACE STAIR WITH ADDITIONAL DOOR REPLCEMENT
 INFORMATION; HOWEVER, THE LOCATION OF THE CIRCLE 26 ON
 THE FLOOR LAYOUT IS AT A DOOR.
  
 PLEASE CLARIFY THE LOCATION AND MEANING OF CIRCLE 26
 NOTE. IS IT FOR A STAIR REPAIR/REPLACE OR A DOOR.
  
  
  
  
 2) NO LIFE SAFETY SHEETS - IS THE PROPOSED PROJECT
 BEING CONDUCTED WITH THE BUILDING OCCUPIED WITH GUESTS
 ON THE SAME OR ANY FLOORS.
  
 PLEASE CLARIFY AND PROVIDE DETAILS OF PHASING OR
 SEQUENCES OF WORK.
  
  
 2A) THERE ARE INDICATIONS OF FLOORS, WALLS, STAIRS,
 CEILINGS, BEING WORKED ON.
  
 HOW WILL EXITING AND MAINTNENCE FOR ALL LIFE SAFETY
 SYSTEM BEING ACCOMPLISHED WHILE BEING OCCUPIED?
  
 A DETAILED LIFE SAFETY PLAN FOR EACH FLOOR IS REQUIRED
 INDICATING HOW ALL LIFE SAFETY SYSTEMS, EXITS, TRAVEL
 DISTANCES, COMMON PATHS OT TRAVEL AND EXIT DISCHARGES
 WILL BE MAINTAINED.
  
  
  
  
 3) FIRE ALARM AND FIRE SPRINKLER - THE PROPOSED WORK
 MAY AFFECT FA & FS EQUIPMENT, DEVICES, HEADS, FUNCTION,
 ETC.
  
 ANY WORK ON THE FA & FS SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIST AND SHOP DRAWINGS BY CERTIFIED
 CONTRACTORS.
  
 THE FA & FS SYSTEMS SHALL BE MAINTAINED THROUGHOUT DEMO
 AND CONSTRUCTION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE ON THE LIFE SAFETY PLAN SHEETS.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-03-24 Cont ID  
Sent By jbaker Date 2020-03-24 Time 10:36 Rev Time 0.00
Received By shill Date 2020-03-24 Time 06:51 Sent To  
Notes
2020-03-24 10:37:05REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-02-17 Cont ID  
Sent By shill Date 2020-02-17 Time 17:34 Rev Time 0.00
Received By shill Date 2020-02-16 Time 07:40 Sent To  
Notes
2020-02-17 17:34:17SEE PLUMBING

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-12-02 Cont ID  
Sent By shill Date 2019-12-02 Time 12:11 Rev Time 0.00
Received By shill Date 2019-12-02 Time 12:11 Sent To  
Notes
2019-12-02 12:11:48GAS 2ND REVIEW**DENIED**
  
 YOUR RESPONSE TO THE COMMENTS BELOW ARE THAT NO NEW GAS
 WORK TO BE PERFORMED. PLEASE CLARIFY AS SHT. CS-000
 STILL IS SHOWING GAS FIRE PIT.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By shill Date 2019-08-19 Time 06:21 Rev Time 0.00
Received By shill Date 2019-08-13 Time 09:06 Sent To  
Notes
2019-08-19 06:21:56GAS 1ST REVIEW**DENIED**
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6
 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 . GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1,
  
 6. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37)
  
 7. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4
  
 8. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3
  
 9. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1
  
 10. SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-07-15 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-14 Cont ID  
Sent By rmcphers Date 2021-07-14 Time 11:10 Rev Time 0.00
Received By rmcphers Date 2021-06-21 Time 16:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-03-24 Cont ID  
Sent By rmcphers Date 2020-03-24 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2020-02-26 Time 10:47 Sent To  
Notes
2020-03-24 12:36:34E MAIL SENT TO PERMIT LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-17 Cont ID  
Sent By shill Date 2020-02-17 Time 17:35 Rev Time 0.00
Received By shill Date 2020-01-24 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-12-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-05 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-19 Cont ID  
Sent By shill Date 2019-08-19 Time 06:22 Rev Time 0.00
Received By shill Date 2019-07-05 Time 08:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-08-12 Cont ID  
Sent By dbattles Date 2019-08-12 Time 16:08 Rev Time 0.00
Received By dbattles Date 2019-08-12 Time 16:08 Sent To  
Notes
2019-08-12 16:09:03NO CHANGE IN AREA OR OCCUPANCY.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-02-13 Cont ID  
Sent By ccole Date 2020-02-13 Time 14:57 Rev Time 0.00
Received By ccole Date 2020-02-13 Time 14:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-12-03 Cont ID  
Sent By ccole Date 2019-12-03 Time 10:51 Rev Time 0.00
Received By ccole Date 2019-12-03 Time 10:03 Sent To  
Notes
2019-12-03 10:57:502ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19070147
 12/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PREVIOUS 1ST REVIEW COMMENTS HAVE BEEN ADDRESSED
 HOWEVER THERE ARE SIGNATURE ISSUES: A) THE MEP SHEETS
 DO NOT BEAR THE ELECTRONIC SIGNATURE AND SEAL OF THE
 ENGINEEER AS REQUIRED BY FL. STATUTE 471.025 AND
 SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. B)
 THE NEW M101, M103, AND M600 PLAN SHEETS MUST HAVE
 THRIRD PARTY ELECTRONIC SIGNATURE AND SEAL
 VERIFICATION. FL. ENGINEERS ARE NOT PERMITTED TO
 SELF-CERTIFY PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-14 Cont ID  
Sent By pvalenti Date 2019-08-14 Time 07:36 Rev Time 0.00
Received By ccole Date 2019-08-14 Time 07:35 Sent To  
Notes
2019-08-16 15:41:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070147
 8/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS MEP- 102, 103, & 104: PROVIDE EXHAUST FAN
 EQUIPMENT SCHEDULES, AND SHOW NEW EXHAUST DUCT RUNS
 WHERE TOILET ROOMS HAVE BEEN RELOCATED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2019-08-14 07:36:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070147
 8/14/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS ONLY ONE MEP PLAN SHEET FOR THIS ENTIRE
 PROJECT THAT IS INDICATING ONLY THE REPLACEMENT OF A
 CEILING EXHAUST FAN ON LEVEL 1. PLEASE PROVIDE COMPLETE
 MECHANICAL DEMOLITION AND NEW WORK PLANS FOR EACH LEVEL
 AND GUESTROOM INCLUDING ITEMIZED SCOPE OF WORK OUTLINES
 WITH CORRELATING DETAILS, SPECIFICATIONS, AND EQUIPMENT
 SCHEDULES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-03-24 Cont ID  
Sent By jbaker Date 2020-03-24 Time 10:35 Rev Time 0.00
Received By shill Date 2020-03-24 Time 06:49 Sent To  
Notes
2020-03-24 06:49:26REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-02-17 Cont ID  
Sent By shill Date 2020-02-17 Time 17:34 Rev Time 0.00
Received By shill Date 2020-02-16 Time 07:40 Sent To  
Notes
2020-02-17 17:34:59PLUMBING 3RD REVIEW**DENIED**
 PLEASE RESPOND TO ALL COMMENTS. YOU CALL OUT SHT.
 CS-000 AND A-100 IN YOUR RESPONSE TO COMMENTS BUT NO
 NEW SHEETS SUBMITTED. SEE 1ST REVIEW COMMENTS BELOW.
 YOU CALL OUT R1 BUT THIS IS AN RESIDENCE INN EXTENDED
 STAY WHICH WOULD MAKE IT AN R-2.
  
 PLANS THAT ARE DENIED 3 OR MORE TIMES FOR THE SAME
 COMMENTS NOT BEING ADDRESSED ARE SUBJECT TO A 4X PLAN
 REVIEW FEE PER F.S 553.80 (2) (B)
 1) SHT. CS-000 STATES BUILDING WAS CONSTRUCTED IN 1998.
 BUILDING BUILT AFTER MARCH 13, 1991 SHOULD HAVE BEEN
 CONSTRUCTED AND APPEARS BY EXISTING BATHROOM FIXTURE
 LAY OUT TO HAVE BEEN UNDER THE FAIR HOUSING MANUAL
 (FHA). THE NEW PROPOSED RENOVATIONS SHALL ALSO COMPLY
 WITH FHA. THE PROPOSED TUB TO SHOWER CONVERSION WILL
 NOT COMPLY AND PROVIDE THE REQUIRED CLEAR FLOOR SPACE
 AS TOILETS AND CABINETS SHALL NOT ENCROACH INTO THE
 CLEAR FLOOR SPACE. FHA 7.55. PROVIDE
 2) PROVIDE WHAT DESIGN SPEC ( A OR B) EACH UNIT
 CURRENTLY IS.
 3) PROVIDE CABINET HEIGHT DETAIL SHOWING MAX HEIGHT OF
 CABINETS WILL BE 34?. FHA 7.52
 4) SHT. CS-000 SHALL REFER TO THE CURRENT CODE AS THE
 2014 5TH ED FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE. FBC 107.1
 5) SHT. A-001 DETAIL #2 THE DISTANCE TO THE TOILET
 PAPER DISPENSER SHALL BE TO CENTER OF THE 1ST ROLL AND
 NOT THE CENTER OF A DOUBLE ROLL UNIT. FBC-ACC 604.7
 6) SHT. A-001 DETAIL #5 THE 40? MAX HEIGHT OF THE
 MIRROR IS TO THE REFLECTING SURFACE AND NOT THE BOTTOM
 EDGE. FBC-ACC 603.3
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-12-02 Cont ID  
Sent By shill Date 2019-12-02 Time 12:09 Rev Time 0.00
Received By shill Date 2019-11-21 Time 16:58 Sent To  
Notes
2019-12-02 12:10:13PLUMBING 2ND REVIEW**DENIED**
  
 PLEASE RESPOND TO ALL COMMENTS. YOU CALL OUT SHT.
 CS-000 AND A-100 IN YOUR RESPONSE TO COMMENTS BUT NO
 NEW SHEETS SUBMITTED. SEE 1ST REVIEW COMMENTS BELOW
  
  
  
 PLUMBING 1ST REVIEW**DENIED**
  
  
 1) SHT. CS-000 STATES BUILDING WAS CONSTRUCTED IN 1998.
 BUILDING BUILT AFTER MARCH 13, 1991 SHOULD HAVE BEEN
 CONSTRUCTED AND APPEARS BY EXISTING BATHROOM FIXTURE
 LAY OUT TO HAVE BEEN UNDER THE FAIR HOUSING MANUAL
 (FHA). THE NEW PROPOSED RENOVATIONS SHALL ALSO COMPLY
 WITH FHA. THE PROPOSED TUB TO SHOWER CONVERSION WILL
 NOT COMPLY AND PROVIDE THE REQUIRED CLEAR FLOOR SPACE
 AS TOILETS AND CABINETS SHALL NOT ENCROACH INTO THE
 CLEAR FLOOR SPACE. FHA 7.55. PROVIDE
  
 2) PROVIDE WHAT DESIGN SPEC ( A OR B) EACH UNIT
 CURRENTLY IS.
  
 3) PROVIDE CABINET HEIGHT DETAIL SHOWING MAX HEIGHT OF
 CABINETS WILL BE 34?. FHA 7.52
  
 4) SHT. CS-000 SHALL REFER TO THE CURRENT CODE AS THE
 2014 5TH ED FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE. FBC 107.1
  
 5) SHT. A-001 DETAIL #2 THE DISTANCE TO THE TOILET
 PAPER DISPENSER SHALL BE TO CENTER OF THE 1ST ROLL AND
 NOT THE CENTER OF A DOUBLE ROLL UNIT. FBC-ACC 604.7
  
 6) SHT. A-001 DETAIL #5 THE 40? MAX HEIGHT OF THE
 MIRROR IS TO THE REFLECTING SURFACE AND NOT THE BOTTOM
 EDGE. FBC-ACC 603.3
  
  
 TIM HUNT
  
 PLUMBING PLANS EXAMINER
  
 CITY OF WEST PALM BEACH
  
 561-248-2703
  
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By shill Date 2019-08-19 Time 06:22 Rev Time 0.00
Received By shill Date 2019-08-09 Time 12:26 Sent To  
Notes
2019-08-19 06:22:28PLUMBING 1ST REVIEW**DENIED**
  
 1) SHT. CS-000 STATES BUILDING WAS CONSTRUCTED IN 1998.
 BUILDING BUILT AFTER MARCH 13, 1991 SHOULD HAVE BEEN
 CONSTRUCTED AND APPEARS BY EXISTING BATHROOM FIXTURE
 LAY OUT TO HAVE BEEN UNDER THE FAIR HOUSING MANUAL
 (FHA). THE NEW PROPOSED RENOVATIONS SHALL ALSO COMPLY
 WITH FHA. THE PROPOSED TUB TO SHOWER CONVERSION WILL
 NOT COMPLY AND PROVIDE THE REQUIRED CLEAR FLOOR SPACE
 AS TOILETS AND CABINETS SHALL NOT ENCROACH INTO THE
 CLEAR FLOOR SPACE. FHA 7.55. PROVIDE
 2) PROVIDE WHAT DESIGN SPEC ( A OR B) EACH UNIT
 CURRENTLY IS.
 3) PROVIDE CABINET HEIGHT DETAIL SHOWING MAX HEIGHT OF
 CABINETS WILL BE 34?. FHA 7.52
 4) SHT. CS-000 SHALL REFER TO THE CURRENT CODE AS THE
 2017 5TH ED FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE. FBC 107.1
 5) SHT. A-001 DETAIL #2 THE DISTANCE TO THE TOILET
 PAPER DISPENSER SHALL BE TO CENTER OF THE 1ST ROLL AND
 NOT THE CENTER OF A DOUBLE ROLL UNIT. FBC-ACC 604.7
 6) SHT. A-001 DETAIL #5 THE 40? MAX HEIGHT OF THE
 MIRROR IS TO THE REFLECTING SURFACE AND NOT THE BOTTOM
 EDGE. FBC-ACC 603.3
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-08-02 Cont ID  
Sent By rmcphers Date 2021-08-02 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-08-02 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 10:39 Rev Time 0.00
Received By shill Date 2020-03-24 Time 10:39 Sent To  
Notes
2020-03-24 10:46:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 MEP PAGES ARE NOT DIGITALLY SIGNED. IT IS NOT CLEAR WHY
 THIS PROJECT WAS RESUBMITTED WITHOUT A DISCUSSION AS TO
 HOW THIS WOULD BE ADDRESSED, SEE PREVIOUS REVIEW, AND I
 WAS UNABLE TO LOCATE A RESPONSE LETTER.
  
 AFTER ALL REVIEWS ARE COMPLETE, PLEASE CONTACT ME TO
 DISCUSS HOW THIS CAN BE RESOLVED.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-02-13 Cont ID  
Sent By rmcphers Date 2020-02-05 Time 15:53 Rev Time 0.00
Received By rmcphers Date 2020-02-05 Time 15:53 Sent To  
Notes
2020-02-13 15:13:09NOT ALL DRAWINGS ARE SIGNED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-11-26 Cont ID  
Sent By dbattles Date 2019-11-26 Time 14:13 Rev Time 0.00
Received By dbattles Date 2019-11-26 Time 14:13 Sent To  
Notes
2019-11-26 14:14:19DIGITAL SIGNATURE ON ALL SHEETS OK.
 ANY ADDITIONAL SHEETS WILL NEED TO BE DIGITALLY SIGNED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-12 Cont ID  
Sent By dbattles Date 2019-08-12 Time 16:42 Rev Time 0.00
Received By dbattles Date 2019-08-12 Time 16:42 Sent To  
Notes
2019-08-12 16:45:37DIGITAL SIGNATURE ON INITIAL SHEETS OK.
 ANY ADDITIONAL SHEETS WILL NEED TO BE DIGITALLY SIGNED.
  

Review Stop Z ZONING
Rev No 5 Status P Date 2021-07-29 Cont ID  
Sent By llouie Date 2021-07-29 Time   Rev Time 0.00
Received By llouie Date 2021-07-29 Time   Sent To  
Notes
2021-07-29 12:59:56INTERIOR MODIFICATIONS ONLY. SEPARATE PERMITS REQUIRED
 FOR ANY EXTERIOR SITE WORK.

Review Stop Z ZONING
Rev No 4 Status P Date 2021-06-30 Cont ID  
Sent By llouie Date 2021-06-30 Time   Rev Time 0.00
Received By llouie Date 2021-06-30 Time   Sent To  
Notes
2021-06-30 12:27:09* SEPARATE PERMITS REQUIRED FOR ANY EXTERIOR SITE WORK
 (I.E. PARKING AREA, ETC.).

Review Stop Z ZONING
Rev No 3 Status P Date 2020-03-04 Cont ID  
Sent By llouie Date 2020-03-04 Time   Rev Time 0.00
Received By llouie Date 2020-03-04 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-05 Cont ID  
Sent By llouie Date 2020-02-05 Time   Rev Time 0.00
Received By llouie Date 2020-02-05 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-19 Cont ID  
Sent By llouie Date 2019-07-19 Time   Rev Time  
Received By llouie Date 2019-07-19 Time   Sent To  
Notes
***NONE***