Plan Review Details - Permit 19070105
Plan Review Stops For Permit 19070105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-02 Cont ID  
Sent By rmcdouga Date 2019-08-02 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2019-08-02 Time 17:58 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By rmcdouga Date 2019-07-12 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2019-07-12 Time 09:33 Sent To I
Notes
2019-07-12 10:03:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUATION OF $10,000.00 IS LOW FOR THIS POOL.
 THE COST FOR THIS POOL SHOULD BE AROUND $25,000.00. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) THE LOCATION OF THE POOL ON THE SURVEY AND THE SITE
 PLAN DO NOT MATCH. REVISE THE SET BACK DIMENSIONS SO
 THAT THE SITE PLAN AND SURVEY MATCH. FBC 107.2.1
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-02 Cont ID  
Sent By rmcdouga Date 2019-08-02 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2019-08-02 Time 18:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-12 Cont ID  
Sent By jleahy Date 2019-07-12 Time 09:28 Rev Time 0.00
Received By jleahy Date 2019-07-12 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-02 Cont ID  
Sent By rmcdouga Date 2019-08-02 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2019-07-17 Time 15:18 Sent To  
Notes
2019-08-02 15:07:00TO RM DESK
  
2019-07-18 15:18:51RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-12 Cont ID  
Sent By rmcdouga Date 2019-07-12 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2019-07-02 Time 13:48 Sent To  
Notes
2019-07-03 13:48:18ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-31 Cont ID  
Sent By tklarge Date 2019-07-31 Time 08:28 Rev Time 0.00
Received By tklarge Date 2019-07-31 Time 05:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By thunt Date 2019-07-08 Time 06:57 Rev Time 0.00
Received By thunt Date 2019-07-08 Time 06:39 Sent To  
Notes
2019-07-08 06:57:077/8/19 1ST PLUMBING REVIEW**DENIED** PLAN WAS APPROVED
 PENDING VALUATION OF JOB IS CORRECTED.
  
 1) PERMIT VALUE APPEARS LOW AND SHALL BE LISTED AS WHAT
 A AVERAGE POOL CONTRACTOR WIOULD CHARGE FOR SUCH JOB.
 WPB AMEND 109.3 IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATIOOF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-18 Cont ID  
Sent By jroach Date 2019-07-18 Time 16:47 Rev Time 0.00
Received By jroach Date 2019-07-18 Time 16:47 Sent To P
Notes
2019-07-18 16:47:57ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.18.2019
 PERMIT NO.: 19070105
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED
 (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS
 OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE
 GRADE.
  
 2. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.
  
 3. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE
 POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT
 NOT ONTO ADJACENT PROPERTIES.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By jroach Date 2019-07-05 Time 14:20 Rev Time 0.00
Received By jroach Date 2019-07-05 Time 14:20 Sent To  
Notes
2019-07-05 14:20:17ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.05.2019
 PERMIT NO.: 19070105
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. TWO DIFFERENT SURVEYS WERE PROVIDED, SHOWING TWO
 DIFFERENT SETS OF DIMENSIONS BETWEEN THE POOL AND
 PROPERTY LINE. PLEASE ENSURE THAT ALL PLANS ARE
 CONSISTENT.
  
 2. PLEASE PROVIDE THE DIMENSION BETWEEN THE POOL
 EQUIPMENT AND THE ADJACENT SIDE PROPERTY LINE. PURSUANT
 TO THE CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS,
 THE EQUIPMENT SHALL BE A MINIMUM OF 6 FEET FROM THE
 PROPERTY LINE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved