Plan Review Details - Permit 19070082
Plan Review Stops For Permit 19070082
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-10-01 Cont ID  
Sent By cthroop Date 2019-10-01 Time 17:08 Rev Time 0.00
Received By cthroop Date 2019-10-01 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-09-20 Cont ID  
Sent By cthroop Date 2019-09-20 Time 10:13 Rev Time 0.00
Received By cthroop Date 2019-09-20 Time 07:43 Sent To  
Notes
2019-09-20 10:22:46BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. MULTIPLE SETS OF DOCUMENTS FOR WINDOWS IN SUBMITTAL.
 REMOVE ANY DOCUMENTS THAT DO NOT APPLY TO THIS SCOPE OF
 WORK.
  
 2. SITE SPECIFIC EVALUATION OF STORM PANELS BY J.W.
 KNEZEVCH, P.E. REQUIRES ORIGINAL SIGNATURE AND SEAL.
 DIGITAL COPIES ARE NOT ACCEPTABLE.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 3. DESIGN CALC'S BY ENGINEERING EXPRESS REQUIRES
 ORIGINAL SIGNATURE AND SEAL OF DESIGNER FRANK L.
 BENNARDO, P.E.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 4. COMMENT #3 FROM 3RD REVIEW HAS NOT BEEN ADDRESSED.
 PROVIDE INSTALLATION INSTRUCTIONS SWD014 FOR THE
 STRUCTURAL BEAM MULLIONS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 ADVISORY:
  
 4X FEES
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-08-09 Cont ID  
Sent By cthroop Date 2019-08-09 Time 09:21 Rev Time 0.00
Received By cthroop Date 2019-08-06 Time 16:50 Sent To  
Notes
2019-08-09 09:25:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUATION - BASED ON THE MARSHALL-SWIFT VALUATION
 SERVICE YOUR VALUE HAS BEEN DETERMINED TO BE $3,800.
 CITY OF WPB CHPT. 1 ? VALUE - 109.3 BUILDING PERMIT
 VALUATIONS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. BASED ON YOUR VIOLATION OF WORK WITHOUT PERMIT, YOUR
 PERMIT FEES WILL BE CALCULATED AT 4 TIMES THE STANDARD
 FEE PER AARON BORNGRABER, HISTORIC PRESERVATION
 PLANNER.
  
 3. PROVIDE INSTALLATION INSTRUCTIONS SWD014 FOR THE
 STRUCTURAL BEAM MULLIONS, PRODUCT APPROVAL # FL6067.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 4. PROVIDE AN ACCURATELY COMPLETED SHUTTER SCHEDULE.
 YOU MAY OBTAIN A COPY OF THE CITY OF WEST PALM BEACH
 SHUTTER SCHEDULE @
 FORMS - HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICE
 S/OVERVIEW
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 16:17 Rev Time 0.00
Received By cthroop Date 2019-07-18 Time 16:17 Sent To  
Notes
2019-07-18 16:23:28BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. PROVIDE PRODUCT APPROVALS FOR THE VYNAL WINDOWS AND
 WINDOW MULLIONS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND WINDOW MULLION
 SUBMITTALS.
  
 3. PROVIDE A SHUTTER SCHEDULE.
 A COPY OF THE CITY OF WPB SHUTTER SCHEDULE HAS BEEN
 INCLUDED IN THIS SUBMITTAL FOR YOUR REVIEW AND USE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-09 Cont ID  
Sent By cthroop Date 2019-07-09 Time 08:59 Rev Time 0.00
Received By cthroop Date 2019-07-09 Time 08:59 Sent To  
Notes
2019-07-09 09:20:58BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED PVC WINDOWS ARE STRCITLY PROHIBITED BY THE
 HISTORIC PRESERVATION AUTHORITY. SELECT AN APPROVED
 WINDOW AND RE-SUBMIT.
  
 2. PROVIDE A SITE PLAN INDICATING THE LOCATION OF EACH
 WINDOW TO RECIEVE A SHUTTER.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION ...
  
 3. PROVIDE A CITY OF WEST PALM BEACH SHUTTER SCHEDULE.
 SCHEDULE CAN BE LOCATED ON THE CITY OF WEST PALM BEACH
 WEB SITE.
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX .
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2019-10-01 Cont ID  
Sent By aborngra Date 2019-10-01 Time 15:55 Rev Time 0.00
Received By aborngra Date 2019-10-01 Time 15:55 Sent To B
Notes
2019-10-01 15:55:28THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITIONS:
  
 A. THE MULLIONS ON THE FRONT ELEVATION SHALL BE
 APPROXIMATELY THREE INCHES.
 B. ALL WINDOWS INSTALLED FOR THIS PERMIT SHALL BE SIZED
 TO FIT THE ORIGINAL WINDOW OPENING. ALL WINDOWS SHALL
 MATCH THE INSET/DEPTH OF THE ORIGINAL WINDOWS WITHIN
 THE WINDOW OPENING.
 C. ALL WINDOWS INSTALLED FOR THIS PERMIT SHALL HAVE
 CLEAR GLASS OR CLEAR GLASS WITH LOW-E COATING.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2019-09-18 Cont ID  
Sent By aborngra Date 2019-09-18 Time 13:25 Rev Time 0.00
Received By aborngra Date 2019-09-18 Time 13:25 Sent To B
Notes
2019-09-18 13:26:09THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITIONS:
  
 A. THE MULLIONS ON THE FRONT ELEVATION SHALL BE
 APPROXIMATELY THREE INCHES.
 B. ALL WINDOWS INSTALLED FOR THIS PERMIT SHALL BE SIZED
 TO FIT THE ORIGINAL WINDOW OPENING. ALL WINDOWS SHALL
 MATCH THE INSET/DEPTH OF THE ORIGINAL WINDOWS WITHIN
 THE WINDOW OPENING.
 C. ALL WINDOWS INSTALLED FOR THIS PERMIT SHALL HAVE
 CLEAR GLASS OR CLEAR GLASS WITH LOW-E COATING.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-08-05 Cont ID  
Sent By aborngra Date 2019-08-05 Time 14:51 Rev Time 0.00
Received By aborngra Date 2019-08-05 Time 14:49 Sent To B
Notes
2019-08-05 14:51:14THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITIONS:
  
 A. THE MULLIONS ON THE FRONT ELEVATION SHALL BE
 APPROXIMATELY THREE INCHES.
 B. ALL WINDOWS INSTALLED FOR THIS PERMIT SHALL BE SIZED
 TO FIT THE ORIGINAL WINDOW OPENING. ALL WINDOWS SHALL
 MATCH THE INSET/DEPTH OF THE ORIGINAL WINDOWS WITHIN
 THE WINDOW OPENING.
 C. ALL WINDOWS INSTALLED FOR THIS PERMIT SHALL HAVE
 CLEAR GLASS OR CLEAR GLASS WITH LOW-E COATING.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2019-07-18 Cont ID  
Sent By aborngra Date 2019-07-18 Time 15:52 Rev Time 0.00
Received By aborngra Date 2019-07-18 Time 15:36 Sent To PC
Notes
2019-07-18 15:48:18THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. THE PROPOSED WINDOWS ON THE FRONT ELEVATION DO NOT
 APPEAR TO ACCURATELY REFLECT THE ORIGINAL SIZE OF THE
 PREVIOUS WINDOWS THAT WERE REPLACED. STAFF RESEARCH HAS
 SHOWN THE WINDOWS WERE ROUGHLY 30 INCHES WIDE AND 47
 INCHES TALL WITH A 4-INCH-WIDE MULLION. REVISE DRAWING
 TO SHOW COMPLIANCE OR PROVIDE PROOF THAT THE PROPOSED
 WINDOW SIZES MATCH THE PREVIOUS WINDOWS THAT WERE
 REPLACED.
 2. PROVIDE A PRODUCT APPROVAL OR OTHER DOCUMENT FOR
 ALUMINUM MULLIONS.
 3. PROVIDE A SITE PLAN ILLUSTRATING LOCATION OF VINYL
 WINDOWS AND RESPECTIVE PRODUCT APPROVALS FOR VINYL
 WINDOWS THAT HAVE ALREADY BEEN INSTALLED. THESE WINDOWS
 WILL BE APPROVED (BY HISTORIC).
 4. PROVIDE OR LABEL INFORMATION THAT THE NEWLY
 INSTALLED WINDOWS WILL HAVE CLEAR GLASS OR WILL HAVE
 CLEAR GLASS WITH LOW-E COATING.
  
 THE PROPOSED REMOVABLE ALUMINUM SHUTTERS ARE FINE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-07-05 Cont ID  
Sent By aborngra Date 2019-07-05 Time 08:54 Rev Time 0.00
Received By aborngra Date 2019-07-05 Time 08:53 Sent To B
Notes
2019-07-05 08:54:25THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. VINYL WINDOWS ARE STRICTLY PROHIBITED WITHIN THE
 HISTORIC DISTRICT.
  
 THE INFORMATION SUBMITTED IS INSUFFICIENT TO BE
 APPROVED EVEN IF THE REPLACEMENT WINDOWS COMPLIED WITH
 THE DESIGN GUIDELINES. THE DIMENSIONS OF THE WINDOW
 OPENING, OR DIMENSIONS OF THE EXISTING AND PROPOSED
 WINDOWS NEED TO BE SUBMITTED. THE REPLACEMENT WINDOWS
 WILL NEED TO MATCH THE EXISTING WINDOWS AS CLOSELY AS
 POSSIBLE INCLUDING LITE PATTERN (1/1), NUMBER OF
 WINDOWS (3+3+1+1), WIDTH/NUMBER OF MULLIONS (2+2+0+0),
 SIZE OF WINDOW, AND INSET/DEPTH WITHIN THE WINDOW
 OPENING. PRIVACY AND/OR TINTED GLASS IS PROHIBITED IN
 THE HISTORIC DISTRICT, ALL GLASS MUST BE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E COATING.
  
 SHUTTER INFORMATION WAS NOT PROVIDED. BAHAMA SHUTTERS
 WOULD BE CONSIDERED APPROPRIATE FOR THIS STRUCTURE.
  
 IF THE PROPERTY OWNER WOULD LIKE TO MOVE FORWARD WITH
 VINYL WINDOWS, A CERTIFICATE OF APPROPRIATENESS
 APPLICATION WILL NEED TO BE COMPLETED AND REVIEWED BY
 THE HISTORIC PRESERVATION BOARD. STAFF WILL RECOMMEND A
 DENIAL.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-10-01 Cont ID  
Sent By cthroop Date 2019-10-01 Time 17:08 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 13:39 Sent To  
Notes
2019-10-01 13:40:04RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-09-20 Cont ID  
Sent By cthroop Date 2019-09-20 Time 10:22 Rev Time 0.00
Received By cthroop Date 2019-09-16 Time 09:24 Sent To  
Notes
2019-09-18 09:24:54RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-09 Cont ID  
Sent By cthroop Date 2019-08-09 Time 09:47 Rev Time 0.00
Received By cthroop Date 2019-08-01 Time 14:05 Sent To  
Notes
2019-08-02 14:05:35RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 16:23 Rev Time 0.00
Received By cthroop Date 2019-07-12 Time 12:50 Sent To  
Notes
2019-07-15 12:50:51RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-09 Cont ID  
Sent By cthroop Date 2019-07-09 Time 10:31 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 11:34 Sent To  
Notes
2019-07-02 11:34:55ROUTED TO HISTORIC INBOX