Plan Review Details - Permit 19070048
Plan Review Stops For Permit 19070048
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-12 Cont ID  
Sent By jwitmer Date 2019-08-12 Time 15:37 Rev Time 0.00
Received By jwitmer Date 2019-08-12 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By jwitmer Date 2019-07-17 Time 13:15 Rev Time 0.00
Received By jwitmer Date 2019-07-17 Time 11:14 Sent To  
Notes
2019-07-17 13:15:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070048
 ADD: 1540 PALM BEACH LAKES SUITE B-08
 CONT: MION CONSTRUCTION CO.
 TEL: 239-745-1115
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. CHAPTER 4 PRESCRIPTIVE
 COMPLIANCE METHOD. 401.2.2 NEW AND REPLACEMENT
 MATERIALS. EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY
 THIS CODE, MATERIALS PERMITTED BY THE APPLICABLE CODE
 FOR NEW CONSTRUCTION SHALL BE USED. LIKE MATERIALS
 SHALL BE PERMITTED FOR REPAIRS AND ALTERATIONS,
 PROVIDED NO HAZARD TO LIFE, HEALTH OR PROPERTY IS
 CREATED. HAZARDOUS MATERIALS SHALL NOT BE USED WHERE
 THE CODE FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR
 USE IN BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND
 LOCATION.
  
  
 1.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 17/2019
 ACTION: DENIED
  
 1A) DISCREPANCY IN THE PLANS THE COVER-SHEET A-0.1
 VERSES A-0.2. THE COVERSHEET INDICATES THE OCCUPANCY
 ORIGINAL AND PROPOSED OCCUPANCY AS MERCANTILE UNDER THE
 HEADING BUILDING CODE SUMMARY. THE COVERSHEET ALSO
 UNDER THE HEADING OF OCCUPANCY INFORMATION ALSO LIST
 THE OCCUPANCY AS M (MERCANTILE).
 SHEET A-0.2 ON THE LIFE SAFETY FLOOR PLAN LIST THE
 OCCUPANCY AS MERCANTILE BUT UNDER THE HEADING OF THE
 FLORIDA BUILDING CODE 2017 ALL THE INFORMATION IN THIS
 SECTION STATES A BUSINESS OCCUPANCY AND OCCUPANCY LOAD
 CALCULATIONS USING 100 SQ. FT. AS YOU WOULD FOR A
 BUSINESS OCCUPANCY IN TABLE 1004.1.2 OF THE 2017 FBC-B.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1: ADMINISTRATIVE CODE SECTION 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED SINCE THERE IS A
 DISCREPANCY IN OCCUPANCY TYPES BETWEEN THE 2 SHEETS.
  
 1B) THE COVERSHEET ALSO LIST THAT THE BUILDING IS FIRE
 SPRINKLERED BUT NO INFORMATION WAS SUBMITTED ON THE
 EXISTING SPRINKLER LAYOUT OR FOR THE NEW SPRINKLER
 LAYOUT. SHEET A-6.1 THE REFLECTIVE CEILING PLAN DOES
 NOT SHOW THE LOCATION OF EXISTING OR PROPOSED FIRE
 SPRINKLER HEADS IN THE CEILING. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1C) HEADING OCCUPANT LOAD & EXIT WIDTH. WITHIN THE
 TABLE ON THIS SHEET THE OCCUPANT LOAD FACTOR OF 30 SQ.
 FT. IS BEING USED. CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, THE
 2017 FBC-B TABLE 1004.1.2 LIST THE OCCUPANT LOAD FACTOR
 AS 60 FOR ALL FLOORS. PLEASE MAKE THE CORRECTION, THANK
 YOU.
  
 1D) HEADING EXIT REQUIREMENTS. THE PLANS INDICATE ONLY
 ONE MEANS OF EGRESS IS REQUIRED AND 2 ARE PROVIDED. THE
 ALLOWABLE COMMON PATH OF TRAVEL IS GIVEN AS 100 FEET.
 PLEASE NOTE (TABLE 1006.1.2 IS THE CORRECT CODE
 SECTION, NOT 1016.2.1) THE 100 FEET IS FOR EITHER
 BUSINESS OCCUPANCY WITH AND OCCUPANT LOAD OF < THAN 30
 OR FOR FIRE SPRINKLERED BUILDINGS. THE TEST IS TO SEE
 IF FROM THE FURTHEST POINT IN THE TENANT SPACE IF FOR
 MERCANTILE OCCUPANCY THE COMMON PATH OF TRAVEL IS 75
 FEET OR LESS. 1 FOOT OF THE RESTROOM WALL TO THE FRONT
 DOOR THE COMMON PATH OF TRAVEL EXCEEDS 75 FEET
 REQUIRING 2 MEANS OF EGRESS, 2 MEANS OF EGRESS ARE
 REQUIRED. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE
 SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 PLEASE PROVIDE IF THE BACK EXIT IS AN ACCESSIBLE MEANS
 OF EGRESS TO THE PUBLIC WAY.
  
 1E) THE COVERSHEET UNDER THE HEADING OF EXIT
 REQUIREMENTS LIST THE DEAD ENDS AS ALLOWABLE 50 FEET
 AND CODE SECTION 1020.4. THIS IS TRUE FOR BOTH
 MERCANTILE AND BUSINESS OCCUPANCIES WHEN THERE IS FIRE
 SPRINKLERS, IF TAKING THE EXCEPTION PLEASE PROVIDE THE
 EXISTING AND PROPOSED FIRE SPRINKLER LAYOUT.
  
 2) SHEET A-0.2 IN THE LIFE SAFETY FLOOR PLAN IN THE
 AREA FOR THE MERCANTILE OCCUPANCY THE PLAN INDICATES
 THE OCCUPANT LOAD FACTOR OF 30 SQ. FT. / OCCUPANT CODE
 W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, THE 2017 FBC-B TABLE 1004.1.2
 LIST THE OCCUPANT LOAD FACTOR AS 60 FOR ALL FLOORS.
 PLEASE MAKE THE CORRECTION, THANK YOU.
  
 3) SHEET A-3.1 RESTROOM ELEVATIONS SHOW A MIRROR OVER
 THE LAV WITH THE VERTICAL MEASUREMENT OF 3 FEET 4
 INCHES TO THE BOTTOM OF THE MIRROR FRAME NOT THE
 REFLECTIVE SURFACE. 2017 FBC-ACCESSIBILITY CODE 603.3
 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-14 Cont ID  
Sent By jpearson Date 2019-07-14 Time 09:40 Rev Time 0.00
Received By jpearson Date 2019-07-14 Time 09:27 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-07-14 Cont ID  
Sent By jpearson Date 2019-07-14 Time 09:59 Rev Time 0.00
Received By jpearson Date 2019-07-14 Time 09:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-05 Cont ID  
Sent By jesmith Date 2019-08-13 Time 08:29 Rev Time 0.00
Received By pleduc Date 2019-08-05 Time 11:02 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By pleduc Date 2019-07-12 Time   Rev Time 0.00
Received By pleduc Date 2019-07-12 Time 14:07 Sent To  
Notes
2019-07-12 14:33:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 02 - DOOR D 4 IS INDICATED OPENING INTO THE
 EXIT CORRIDOR OBSTRUCTING THE REQUIRED EGRESS WIDTH.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 2) SHEET A 02 - THERE ARE NO INDICATIONS OF FIRE
 SPRINKLERS WITHIN THIS SUITE.
  
 PLEASE CONFIRM.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
  
 3) SHEET E 1 - THERE ARE INDICATIONS OF FIRE ALARM
 EQUIPMENT/DEVICES.
  
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
  
 4) ELECTRICAL SHEETS - INFORMATION: ANY ACCESS CONTROL
 EQUIPMENT/DEVICES SHALL BE INSTALLED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE SEPARATE SUBMITTAL IF APPLICABLE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-13 Cont ID  
Sent By jesmith Date 2019-08-13 Time 08:29 Rev Time 0.00
Received By jesmith Date 2019-08-13 Time 08:29 Sent To FIRE
Notes
2019-08-12 08:23:40TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-07-17 Time   Rev Time 0.00
Received By lmarchan Date 2019-07-01 Time 12:46 Sent To  
Notes
2019-07-02 15:28:43B23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-17 Cont ID  
Sent By jwitmer Date 2019-07-17 Time 13:15 Rev Time 0.00
Received By jwitmer Date 2019-07-17 Time 13:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-17 Cont ID  
Sent By ccole Date 2019-07-17 Time 08:32 Rev Time 0.00
Received By ccole Date 2019-07-16 Time 17:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-13 Cont ID  
Sent By jesmith Date 2019-08-13 Time 08:29 Rev Time 0.00
Received By jesmith Date 2019-08-13 Time 08:29 Sent To  
Notes
2019-08-13 08:29:22APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-11 Cont ID  
Sent By jesmith Date 2019-07-11 Time 13:40 Rev Time 0.00
Received By jesmith Date 2019-07-11 Time 10:00 Sent To  
Notes
2019-07-11 13:27:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
  
 COMMENTS REQUIRING ARCHITECTURAL RESPONSE:
 SATISFACTORY RESPONSE TO ARCHITECTURAL COMMENTS ARE
 REQUIRED FOR PLUMBING APPROVAL TO COMPLY WITH THE
 REQUIREMENTS OF FBC PL 404.
  
 1. PLAN SHEET A-0.1: WPB FBC HAS ADOPTED FBC
 ACCESSIBILITY, 6TH EDITION 2017. PER WPB FBC 107.2.1,
 CHANGE BUILDING CODE SUMMARY TO REFLECT THE SAME.
 2. BREAK AREA SINK: PLAN SHEET A-2.1 INDICATES A 30? X
 48? CLEAR FLOOR SPACE FRONT APPROACH TO THE SINK THAT
 TERMINATES AT THE FRONT OF THE CABINET AND PLAN SHEET
 A-3.1 PROVIDES NOTE FOR OPTIONAL DOORS WITH INTEGRAL
 TOEKICK TO PROVIDE FRONT APPROACH ACCESSIBILITY
 CLEARANCE.
 A. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING:
 1) DELETE REFERENCE TO OPTIONAL
 2) INDICATE ON THE PLAN VIEW (PLAN SHEET A-2.1), THE
 CLEAR FLOOR DIMENSIONED SPACE FOR THE FRONT APPROACH TO
 THE SINK COMPLYING WITH FBC ACC 306.
 3) PROVIDE A SIDE VIEW ELEVATION ON PLAN SHEET A-3.1 OF
 SINK SECTION SHOWING KNEE AND TOE CLEARANCE FOR THE
 SINK COMPLYING WITH FBC ACC 306.
 3. ELECTRIC WATER COOLER: PER WPB FBC 107.2.1, PROVIDE
 A SIDE AND FRONT VIEW ELEVATION ON PLAN SHEET A-3.1 OF
 BI-LEVEL WATER COOLER SHOWING SPOUT HEIGHT AND LOCATION
 PER FBC 602.4, 602.5 AS WELL AS KNEE AND TOE CLEARANCE
 FOR THE SINK COMPLYING WITH FBC ACC 306.
 4. PLAN SHEET A-3.1 DETAIL 2
 A. CENTERLINE OF WATER CLOSET TO SIDE WALL SHALL BE 16?
 MIN/18? MAX PER FBC ACC 604.2. THIS REQUIREMENT IS
 NOTED ON PLAN SHEET TI-2.2 BUT IS LUMPED IN WITH
 NUMEROUS OTHER DETAILS MAKING IT DIFFICULT FOR USERS.
 PER WPB FBC 107.2.1, PLACE THIS INFORMATION ON PLAN
 SHEET A-3.1 DETAIL 2.
 B. REAR WALL GRAB BAR SHALL BE 12? FROM CENTERLINE OF
 WATER CLOSET TOWARD SIDE WALL AND 24? MINIMUM
 CENTERLINE OF WATER CLOSET TO THE OTHER SIDE. THIS
 REQUIREMENT IS NOTED ON PLAN SHEET TI-2.2 BUT IS LUMPED
 IN WITH NUMEROUS OTHER DETAILS MAKING IT DIFFICULT FOR
 USERS. PER WPB FBC 107.2.1, PLACE THIS INFORMATION ON
 PLAN SHEET A-3.1 DETAIL 2.
  
  
 COMMENTS REQUIRING PE RESPONSE
  
 1. PLAN SHEET P-1: FIXTURE SCHEDULE
 A. LAV
 1)PER FBC PL 416.5, PROVIDE TEMPERED WATER DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3.
 2)PER WPB FBC 107.2.1, PROVIDE AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 B. EWC
 1) PER WPB FBC 107.2.1 PROVIDE SPECIFICATION SHEET FORE
 OWNER SUPPLIED BILEVEL WATER COOLER SHOWING ADA
 COMPLIANCE. PER WPB FBC 107.3.4.1, THIS MAY BE PROVIDED
 AS A DEFERRED SUBMITTAL. ***SEE 107.3.4.1 DEFERRED
 SUBMITTALS BELOW
 A. SINK
 1)PER WPB FBC 107.2.1 PROVIDE SPECIFICATION SHEET FORE
 OWNER SUPPLIED SINK AND FAUCET SHOWING ADA COMPLIANCE.
 PER WPB FBC 107.3.4.1, THIS MAY BE PROVIDED AS A
 DEFERRED SUBMITTAL. ***SEE 107.3.4.1 DEFERRED
 SUBMITTALS BELOW
  
 *** 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19070048 1540 PALM BEACH LAKES BLVD # B08
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-09 Cont ID  
Sent By jroach Date 2019-07-09 Time 12:00 Rev Time 0.00
Received By jroach Date 2019-07-08 Time 16:13 Sent To  
Notes
***NONE***