Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-06 Cont ID  
Sent By jwitmer Date 2019-09-06 Time 06:40 Rev Time 0.00
Received By jwitmer Date 2019-09-05 Time 17:25 Sent To  
Notes
2019-09-06 06:27:532017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070042
 ADD: 2921 N. AUSTRALIAN AVE.
 CONT: BENITZ BUILDING LLC
 TEL: 561-659-4024
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. SEPT. 06/2019
 ACTION: BUILDING PROVISO
  
 1) BEFORE BUCK INSPECTION PLEASE SUBMIT (2) COPIES OF
 THE EXTERIOR DOOR REPORTS IN COMPLIANCE WITH:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 2) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-23 Cont ID  
Sent By jwitmer Date 2019-07-23 Time 10:05 Rev Time 0.00
Received By jwitmer Date 2019-07-23 Time 08:37 Sent To  
Notes
2019-07-23 10:05:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19070042
 ADD: 2921 N. AUSTRALIAN AVE.
 CONT: BENITZ BUILDING LLC
 TEL: 561-659-4024
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 23/2017
 ACTION: DENIED
  
 1) SHEET A101:
  
 1A) THE SHEET INDICATES THE POSITIVE AND NEGATIVE
 PRESSURES. THERE IS NO INFORMATION IF THESE PRESSURES
 ARE IN VULT OR VASD NOR IS THERE ANY WIND DESIGN
 CRITERIA.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1A)(1.) ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1A)(2.) RISK CATEGORY.
  
 1A)(3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF
 MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE.
  
 1A)(4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1A)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 1A)(6.) TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1A)(7.) SHOW PRESSURES IN VASD SINCE THE PRODUCT
 APPROVALS ARE ALSO IN VASD. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 1B) SUBMIT PRODUCT APPROVALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,& MULLIONS.
 (31)(B) WINDOWS & MULLIONS
  
 1C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 1D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2) SHEET A102:
  
 2A) THE RESTROOM ELEVATIONS SHOW THE ACCESSIBLE GRAB
 BARS ASSOCIATED WITH THE WATER CLOSET DIMENSIONED FROM
 THE CENTERLINE OF THE GRAB BAR TO THE FINISH FLOOR.
 PLEASE REVIEW A CODE CHANGE IN THE 2010
 FBC-ACCESSIBILITY CODE AND THE CURRENT 2017
 ACCESSIBILITY CODE.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 2B) PLEASE NOTE SHEET A101 INDICATES A FUTURE COUNTER
 AND SINK. SHEET A102 DOES NOT PROVIDE ANY DETAILS FOR
 THE COUNTER NOR SINK.
 606 LAVATORIES AND SINKS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2C) DETAIL: WALL SECTION AND SOFFIT REPAIR. THE PLANS
 INDICATE THE INSTALLATION OF POLYICYNENE INSULATION
 SPRAYED TO THE UNDERSIDE OF THE ROOF DECK. THE PLANS DO
 NOT STATE IF THIS ATTIC SPACE IS TO BE AN ENCLOSED
 ATTIC SPACE WITH NO VENTILATION? PLEASE PROVIDE
 ADDITIONAL INFORMATION. 107.2.1.2.
  
 2D) IF THE ATTIC SPACE IS TO BE AN ENCLOSED SPACE
 PLEASE SUBMIT THE POLYICYNENE ICC REPORT. WITHIN THE
 REPORT, THERE IS MANY SUB-SYSTEMS FOR INSTALLATION.
 PLEASE IDENTIFY WHICH SYSTEM (CLASSIC, CLASSIC PLUS,
 CLASSIC ULTRA-SELECT AND CLASSIC PLUS) IS TO BE
 APPLIED, IS THERE ELECTRICAL AND OR A/C DUCT AND OR
 UNITS WITH THIS SPACE. PROVIDE THE SURFACE BURNING
 CHARACTERISTICS FOR THE FOAM AND COMPLIANCE WITH FBC-B
 2603.3.
 PLEASE ALSO CONSIDER THE REQUIREMENTS FOUND IN THE
 FBC-B 2603.4.1.6 FOR PROTECTION AGAINST IGNITION. THE
 PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE
 REQUIREMENTS FOR THE TYPE OF CONSTRUCTION.
  
 2E) DETAIL: WALL SECTION AND SOFFIT REPAIR. WITHIN THE
 SAME DETAIL THERE IS STATEMENTS FOR LATH AND A 3 COAT
 STUCCO PLASTER (ASTM C1063) ON A METAL PLASTER BASE PER
 TABLE 1405.2. THE PLANS ARE SILENT AS TO THE TYPE OF
 WIRE LATH TO BE INSTALLED ON THE HORIZONTAL SURFACE.
 ASTM C1063, IF THE 3/8 INCH RIB LATH IS TO BE INSTALLED
 FASTENERS ARE TO BE ATTACHED TO EACH RIB. (7.10.1.1).
 7.10.2.2. DIAMOND MESH EXPANDED METAL LATH, FLAT RIB
 EXPANDED METAL , AND WIRE LATH SHALL BE ATTACHED TO
 HORIZONTAL WOOD FRAMING MEMBERS WITH 1 ? INCH ROOFING
 NAILS.
 7.10.2.3. EXPANDED 3/8 INCH RIB LATH SHALL BE ATTACHED
 TO HORIZONTAL WOOD FRAMING MEMBERS WITH NAILS OR
 STAPLES TO PROVIDE NOT LESS THAN 1 ? INCH PENETRATION
 INTO THE HORIZONTAL FRAMING MEMBERS.
 7.10.2.5. SCREWS USED TO ATTACH METAL PLASTER BASE TO
 HORIZONTAL WOOD FRAMING MEMBERS SHALL PENETRATE NOT
 LESS THAN 5/8 INCH INTO THE FRAMING MEMBER. WHEN SCREWS
 ARE INSTALLED INTO RIB LATH, THE SCREWS SHALL PASS
 THROUGH, BUT NOT DEFORM THE RIB.
  
 3) NO FLOOR PLAN, NOR LIFE SAFETY PLAN WAS SUBMITTED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY
 THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING
 MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING LIFE SAFETY FLOOR PLAN
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-06 Cont ID  
Sent By jpearson Date 2019-09-06 Time 10:09 Rev Time 0.00
Received By jpearson Date 2019-09-06 Time 10:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-10 Cont ID  
Sent By jleahy Date 2019-07-10 Time 15:48 Rev Time 0.00
Received By jleahy Date 2019-07-10 Time 15:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-28 Cont ID  
Sent By bwoods Date 2019-08-28 Time   Rev Time 0.00
Received By bwoods Date 2019-08-28 Time   Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-10 Cont ID  
Sent By bwoods Date 2019-07-10 Time   Rev Time 0.00
Received By bwoods Date 2019-07-10 Time 00:00 Sent To  
Notes
2019-07-10 08:48:33PERMIT 19070042
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH THE
 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
  
 BRITTANY WOODS
 FIRE INVESTIGATOR & INSPECTOR II
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4754
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-13 Cont ID  
Sent By shill Date 2019-09-13 Time 08:53 Rev Time 0.00
Received By shill Date 2019-08-15 Time 14:10 Sent To  
Notes
2019-08-16 14:10:17B14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-27 Cont ID  
Sent By cmontell Date 2019-07-27 Time 05:26 Rev Time 0.00
Received By cmontell Date 2019-07-27 Time 05:26 Sent To  
Notes
2019-07-02 13:46:30B05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-23 Cont ID  
Sent By jwitmer Date 2019-07-23 Time 10:05 Rev Time 0.00
Received By jwitmer Date 2019-07-23 Time 08:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-11 Cont ID  
Sent By cmontell Date 2019-09-11 Time 13:11 Rev Time 0.00
Received By cmontell Date 2019-09-11 Time 13:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-27 Cont ID  
Sent By cmontell Date 2019-07-27 Time 05:26 Rev Time 0.00
Received By cmontell Date 2019-07-27 Time 05:26 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By gjohnson Date 2019-09-10 Time 11:32 Rev Time 0.00
Received By gjohnson Date 2019-09-10 Time 10:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By jesmith Date 2019-07-18 Time 17:06 Rev Time 0.00
Received By jesmith Date 2019-07-18 Time 17:05 Sent To  
Notes
2019-07-18 17:05:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. A COMPLETE REVIEW COULD NOT BE DONE AT THIS TIME.
 2. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT TO THE CENTER.
 3. PER 604.8.1.2, DOORS SHALL BE LOCATED IN THE FRONT
 PARTITION OR IN THE SIDE WALL OR PARTITION FARTHEST
 FROM THE WATER CLOSET. WHERE LOCATED IN THE FRONT
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE SIDE WALL OR PARTITION FARTHEST FROM
 THE WATER CLOSET. WHERE LOCATED IN THE SIDE WALL OR
 PARTITION, THE DOOR OPENING SHALL BE 4 INCHES (100 MM)
 MAXIMUM FROM THE FRONT PARTITION. DOOR FOR THE TOILET
 ROOM ADJACENT TO JANITOR CLOSET IS NOT COMPLIANT.
 4. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE THE
 FOLLOWING:
 A. FLOOR PLAN SHOWING SANITARY AND WATER DISTRIBUTION;
 SHOW POINTS OF CONNECTION TO EXISTING WATER SERVICE AND
 SEWER
 B. SHOW LOCATION OF EXISTING BACKFLOW PREVENTER OR
 PROVIDE NEW.
 C. WATER RISER DIAGRAM
 D. WATER HEATER SCHEDULE AND DETAIL SHOWING COMPLIANCE
 WITH FBC PL CHAPTER 5.
 E. FIXTURE SCHEDULE
 F. THERMAL MIXING VALVES FOR LAVATORIES
 5. REGARDING SANITARY PLUMBING RISER ON E101:
 A. PLACE ON DEDICATED PLUMBING PAGE (S) WITH OTHER
 REQUIRED INFORMATION AND SHALL MATCH THE FLOOR PLAN.
 B. MOP SINK SHALL BE INDIVIDUALLY VENTED PER FBC PL
 910.1. THE FUTURE SINK VENT DOES NOT PROVIDE A VENT FOR
 THE MOP SINK UNDER SECTION 911 OR 912.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19070042 2921 N AUSTRALIAN AVE
  

Review Stop Z ZONING
Rev No 2 Status N Date 2019-09-13 Cont ID  
Sent By shill Date 2019-09-13 Time 08:52 Rev Time 0.00
Received By shill Date 2019-09-13 Time 08:28 Sent To  
Notes
2019-09-13 08:53:17NO EXTERIOR WORK (NOTE REGARDING THE PLANTER CROSSED
 OUT)
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2019-07-22 Time   Rev Time 0.00
Received By pgreilic Date 2019-07-22 Time 15:07 Sent To  
Notes
2019-07-22 15:08:401.) PROVIDE SURVEY OR SITE PLAN INDICATING EXTENT OF
 WORK IS LIMITED TO EXISTING BUILDING FOOTPRINT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]