Plan Review Details - Permit 19070038
Plan Review Stops For Permit 19070038
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 12:03 Rev Time 0.00
Received By cthroop Date 2019-07-17 Time 10:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 11:09 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By jpearson Date 2019-07-16 Time 07:01 Rev Time 0.00
Received By jpearson Date 2019-07-16 Time 06:17 Sent To  
Notes
2019-07-16 07:01:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE
 CORRECTIONS. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3901.6
 2. THE ISLAND SHOWS A SINK INSTALLED, WHICH DIVIDES THE
 SPACE INTO 2 SEPARATE SPACES. A GFCI PROTECTED
 RECEPTACLE OUTLET IS REQUIRED FOR EACH SPACE. THIS
 RECEPTACLE OUTLET IS NOT PERMITTED TO BE INSTALLED IN
 AN AREA WHERE THE COUNTER TOP IS DEEPER THAN 6 INCHES.
 PROVIDE CORRECTION. NEC 210.52; FBC RE E301.4
 3. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 11:09 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 14:18 Rev Time 0.00
Received By cthroop Date 2019-07-17 Time 14:18 Sent To  
Notes
2019-07-17 14:37:01GAS PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE
 USED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-RES. SEC.G2426 THROUGH G2439.
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FBC-RES. SEC.G2408.1.
  
 10) PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS
 PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A
 CONDUIT OF WROUGHT IRON, PLASTIC PIPE, STEEL PIPE OR
 OTHER APPROVED CONDUIT MATERIAL DESIGNED TO WITHSTAND
 THE SUPERIMPOSED LOADS. THE CONDUIT SHALL BE PROTECTED
 FROM CORROSION IN ACCORDANCE WITH SECTION G2415.11 AND
 SHALL BE INSTALLED IN ACCORDANCE WITH SECTION
 G2415.14.1 OR G2415.14.2.
  
 11) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 12) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
  
 THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 11:09 Rev Time 0.00
Received By cthroop Date 2019-09-24 Time 13:31 Sent To  
Notes
2019-09-25 13:31:53RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 12:03 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 16:22 Sent To  
Notes
2019-07-02 16:22:55R09

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 11:10 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 12:02 Rev Time 0.00
Received By cthroop Date 2019-07-17 Time 11:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By cmontell Date 2019-07-16 Time 14:33 Rev Time 0.00
Received By cmontell Date 2019-07-16 Time 14:29 Sent To  
Notes
2019-07-16 14:33:01MECHANICAL PLAN REVIEW FAIL
  
 1 - PLEASE PROVIDE A MECHANICAL SCOPE OF WORK PER WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, 6TH
 EDITION (2017), CHAPTER 1, ADMINISTRATION SEC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CHRIS MONTELLO
 561-805-6733
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 11:09 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 12:03 Rev Time 0.00
Received By cthroop Date 2019-07-17 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-13 Cont ID  
Sent By tklarge Date 2019-07-13 Time 13:17 Rev Time  
Received By abelisle Date   Time   Sent To  
Notes
2019-07-13 13:50:037/13/19 DENIED
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK NARRATIVE
 CLEARLY SHOWING WHAT WORK IS TO BE PERFORMED
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  