Plan Review Details - Permit 19070002
Plan Review Stops For Permit 19070002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-12-17 Cont ID  
Sent By rmcdouga Date 2019-12-17 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2019-12-17 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-25 Cont ID  
Sent By rmcdouga Date 2019-07-25 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2019-07-24 Time 18:17 Sent To I
Notes
2019-07-25 08:31:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS THAT WERE SUBMITTED HAVE A COPIED
 SIGNATURE AND SEAL OF A FLORIDA LICENSED ARCHITECT IN
 THE TITLE BLOCK. THE PLANS ARE REQUIRED TO HAVE THE
 ARCHITECT'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL.
 61G1-16.003 USE OF SEAL. (1) THE PERSONAL SEAL,
 SIGNATURE AND DATE OF THE ARCHITECT OR INTERIOR
 DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR INTERIOR
 DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD AND
 SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS
 CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT.
 DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE
 RESPONSIBLE ARCHITECT OR INTERIOR DESIGNER. FINAL
 OFFICIAL RECORD DOCUMENTS (NOT TRACINGS, ETC.) SHALL BE
 SO SIGNED. THE SIGNING AND SEALING OF THE SPECIFICATION
 INDEX SHEETS SHALL BE CONSIDERED ADEQUATE. ALL DRAWING
 SHEETS AND PAGES SHALL BE SO SIGNED AND SEALED. AN
 ARCHITECT OR INTERIOR DESIGNER SHALL NOT AFFIX, OR
 PERMIT TO BE AFFIXED, HIS SEAL OR NAME TO ANY PLAN,
 SPECIFICATIONS, DRAWINGS, OR OTHER RELATED DOCUMENT
 WHICH WAS NOT PREPARED BY HIM OR UNDER HIS RESPONSIBLE
 SUPERVISING CONTROL AS PROVIDED IN RULE CHAPTER
 61G1-23, F.A.C. AN ARCHITECT OR INTERIOR DESIGNER SHALL
 NOT USE HIS SEAL OR DO ANY OTHER ACT AS AN ARCHITECT OR
 INTERIOR DESIGNER UNLESS HOLDING AT THE TIME A
 CERTIFICATE OF REGISTRATION AND ALL REQUIRED RENEWALS
 THEREOF.
 (2) WHEN UTILIZING ELECTRONICALLY TRANSMITTED PLANS,
 WHICH ARE DIGITALLY SIGNED AND SEALED PURSUANT TO THE
 PROVISIONS OF RULE 61G1-16.005, F.A.C., AND WHEN ALL
 THE TRANSMITTED DRAWINGS ARE TRANSMITTED AS A
 SINGLE-BOUND AND SECURED SET, IT SHALL BE SUFFICIENT
 FOR THE ARCHITECT OR INTERIOR DESIGNER TO APPLY THEIR
 DIGITAL SIGNATURE AND SEAL TO THE COVER OR FIRST SHEET
 OF THAT BOUND SET, AS LONG AS AN ACCURATE INDEX OF
 DRAWINGS, LISTING ALL THE ARCHITECTURAL OR INTERIOR
 DESIGN SHEETS, WITH THEIR SHEET NUMBER AND LATEST
 REVISE DATE, WHICH ARE INTENDED TO BE SIGNED AND SEALED
 IS INCLUDED WITHIN THAT COVER OR FIRST SHEET.
  
 2) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 3) BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 4) PROVIDE A BOND BREAK BETWEEN THE WATER RESISTIVE
 BARRIER AND THE STUCCO. R703.7.3 WATER-RESISTIVE
 BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
 EXCEPTION: WHERE THE WATER-RESISTIVE BARRIER THAT IS
 APPLIED OVER WOOD-BASED SHEATHING HAS A WATER
 RESISTANCE EQUAL TO OR GREATER THAN THAT OF 60-MINUTE
 GRADE D PAPER AND IS SEPARATED FROM THE STUCCO BY AN
 INTERVENING, SUBSTANTIALLY NON-WATER-ABSORBING LAYER OR
 DESIGNED DRAINAGE SPACE.
  
 5) A WEEP SCREED IS REQUIRED AT THE BOTTOM OF THE WOOD
 FRAME AND STUCCO WALLS. R703.7.2.1 WEEP SCREEDS.
 A MINIMUM 0.019-INCH (0.5 MM) (NO. 26 GALVANIZED SHEET
 GAGE), CORROSION-RESISTANT WEEP SCREED OR PLASTIC WEEP
 SCREED, WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF
 31/2 INCHES (89 MM) SHALL BE PROVIDED AT OR BELOW THE
 FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS IN
 ACCORDANCE WITH ASTM C926. THE WEEP SCREED SHALL BE
 PLACED NOT LESS THAN 4 INCHES (102 MM) ABOVE THE EARTH
 OR 2 INCHES (51 MM) ABOVE PAVED AREAS AND SHALL BE OF A
 TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE
 EXTERIOR OF THE BUILDING. THE WEATHER-RESISTANT BARRIER
 SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH
 SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF
 THE WEEP SCREED.
  
  
 RE-SUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-17 Cont ID  
Sent By jpearson Date 2019-12-17 Time 10:16 Rev Time 0.00
Received By jpearson Date 2019-12-17 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-24 Cont ID  
Sent By jpearson Date 2019-07-24 Time 15:31 Rev Time 0.00
Received By jpearson Date 2019-07-24 Time 15:27 Sent To  
Notes
2019-07-24 15:31:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 6. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-03 Cont ID  
Sent By dbattles Date 2020-02-03 Time 14:04 Rev Time 0.00
Received By dbattles Date 2020-01-24 Time 13:45 Sent To  
Notes
2020-01-27 13:45:32RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-17 Cont ID  
Sent By cmontell Date 2019-12-17 Time 14:44 Rev Time 0.00
Received By cmontell Date 2019-12-17 Time 14:44 Sent To  
Notes
2019-11-25 14:03:56R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-25 Cont ID  
Sent By rmcdouga Date 2019-07-25 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2019-07-01 Time 15:14 Sent To  
Notes
2019-07-02 15:14:58R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2020-02-03 Cont ID  
Sent By dbattles Date 2020-02-03 Time 14:03 Rev Time 0.00
Received By dbattles Date 2020-02-03 Time 14:03 Sent To  
Notes
2020-02-03 14:04:23MU-2020-003532-0000
 OK-PLANS STAMPED
 NO FEES PD.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-12-17 Cont ID  
Sent By rmcdouga Date 2019-12-17 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2019-12-17 Time 14:01 Sent To  
Notes
2019-12-17 14:01:18BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-24 Cont ID  
Sent By rmcdouga Date 2019-07-24 Time 18:19 Rev Time 0.00
Received By rmcdouga Date 2019-07-24 Time 18:17 Sent To  
Notes
2019-12-17 14:00:50BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-12-17 Cont ID  
Sent By cmontell Date 2019-12-17 Time 14:44 Rev Time 0.00
Received By cmontell Date 2019-12-17 Time 14:44 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By cmontell Date 2019-07-19 Time 11:27 Rev Time 0.00
Received By cmontell Date 2019-07-19 Time 11:23 Sent To  
Notes
2019-07-19 11:27:54MECHANICAL PLAN REVIEW FAIL
  
  
 1 - SHOW ANY MECHANICAL WORK TO BE DONE. PER WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE 6TH
 EDITION (2017), CHAPTER 1, ADMINISTRATION, SEC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 CHRIS MONTELLO
 561-805-6733
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-07-18 Cont ID  
Sent By lcrespo Date 2019-07-18 Time 07:25 Rev Time 0.00
Received By lcrespo Date 2019-07-18 Time 07:25 Sent To  
Notes
2019-07-18 07:25:29NO NEW PLUMBING TO BE DONE, IF FIXTURES, SHOWER PAN OR
 VALVES TO BE REPLACE IT WILL REQUIRE A PERMIT AND
 INSPECTIONS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-07-24 Cont ID  
Sent By rmcdouga Date 2019-07-24 Time 18:20 Rev Time 0.00
Received By rmcdouga Date 2019-07-24 Time 18:20 Sent To  
Notes
2019-07-24 18:21:06EXITING ROOF TO REMAIN.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-01-28 Cont ID  
Sent By awooten Date 2020-01-28 Time   Rev Time 0.00
Received By awooten Date 2020-01-28 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-12-06 Cont ID  
Sent By awooten Date 2019-12-06 Time   Rev Time 0.00
Received By awooten Date 2019-12-06 Time   Sent To  
Notes
2019-12-06 15:45:50**************************ZONING REVIEW
 FAILED**********************
  
 PROVIDE THE FRONT SETBACK FOR THE PROPOSED CARPORT
 ENCLOSURE ON SITE PLAN. IT HAS TO BE A MINIMUM OF 25
 FEET BY CODE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-10 Cont ID  
Sent By awooten Date 2019-07-10 Time   Rev Time  
Received By awooten Date 2019-07-10 Time   Sent To  
Notes
2019-07-10 14:34:59***************************ZONING REVIEW
 FAILED**********************
  
 PROVIDE THE FRONT SETBACK FOR THE PROPOSED CARPORT
 ENCLOSURE ON SITE PLAN. IT HAS TO BE A MINIMUM OF 25
 FEET BY CODE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449